TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Highlights & Features  
Universal AC input voltage: 3 x 320Vac – 600Vac (3-Phase)  
or 2 x 360Vac – 600Vac (2-Phase)  
Power will not de-rate for the entire input voltage range  
Power Boost of 150% for 5 seconds  
Full corrosion resistant aluminium chassis  
Conformal coating on PCBA to protect against chemical and  
dust pollutants  
Hazardous Locations approval to ATEX and Class I, Div 2  
(DRP024V240W3BA)  
Safety Standards  
CB Certified for worldwide use  
Model Number:  
DRP024V240W3B  
Unit Weight:  
0.89 kg  
Dimensions (L x W x D): 121 x 70 x 117.3 mm  
General Description  
The CliQ II 3-phase DIN rail power supply series offers output voltage of 24V. These products are encased in rugged yet lightweight full  
aluminium body that can withstand shock and vibration according to IEC 60068-2 standard. The series of 3-phase products can  
operate over a wide temperature range of -25°C to +80°C. These products also feature universal AC input voltage range for 3-phase  
from 320Vac to 600Vac or 2-phase from 360Vac to 600Vac, and the power will not de-rate throughout the entire range. Another great  
feature is the conformal coating on the PCBA which allows selected models to be certified to ATEX and Class I, Div 2 for use in  
hazardous locations. The design conforms to harmonic current emission IEC/EN 61000-3-2, Class A.  
Model Information  
CliQ II DIN Rail Power Supply  
Model Number  
Input Voltage Range  
Output  
Voltage  
Output Current  
DRP024V240W3B☐  
3 x 320-600Vac (3-Phase) or  
2 x 360-600Vac (2-Phase)  
24Vdc  
10.0A  
Model Numbering  
DR  
P
024V  
Output Voltage Output Power  
240W  
3
B
DIN Rail  
Power Supply  
Three Phase  
CliQ II Series  
A - Metal Case,  
with Class I, Div 2  
N - Metal Case,  
without Class I, Div 2  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
1
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Specifications  
Input Ratings / Characteristics  
Nominal Input Voltage  
Input Voltage Range*  
Nominal Input Frequency  
Input Frequency Range  
DC Input Voltage Range**  
Input Current  
3 x 400-500Vac  
3 x 320-600Vac (3-Phase) or 2 x 360-600Vac (2-Phase)  
50-60Hz  
47-63Hz  
450-800Vdc  
< 0.75A @ 3 x 400Vac, < 0.65A @ 3 x 500Vac  
> 92.0% @ 3 x 400Vac & 3 x 500Vac  
< 40A @ 3 x 400Vac & 3 x 500Vac  
< 3.5mA @ 500Vac  
Efficiency at 100% Load  
Max Inrush Current (Cold Start)  
Leakage Current  
*Fulfills test conditions for up to 600Vac input voltage.  
**Fulfills the test conditions for this range.  
Output Ratings / Characteristics  
Nominal Output Voltage  
Output Voltage Tolerance  
Output Voltage Adjustment Range  
Output Current  
24Vdc  
± 2% (initial set point tolerance from factory)  
24-28Vdc  
10.0A (continuously operating at 24V)  
15.0A (Power Boost for 5 seconds at 24V, refer to the  
details in the Functions section)  
Output Power  
240W (continuously operating at 24V)  
360W (Power Boost for 5 seconds at 24V, refer to the  
details in the Functions section)  
Line Regulation  
Load Regulation  
PARD (20MHz)  
Rise Time  
< 0.5% typ. (@ 320-600Vac input, 100% load)  
< 1% typ. (@ 320-600Vac input, 0-100% load)  
< 150mVpp  
< 100ms @ nominal input (100% load)  
< 1,000ms @ nominal input (100% load)  
Start-up Time  
Hold-up Time  
> 20ms @ 3 x 400Vac,  
> 40ms @ 3 x 500Vac (100% load)  
Dynamic Response (Overshoot & Undershoot O/P Voltage)  
Start-up with Capacitive Loads  
± 5% @ 0-100% load  
10,000µF Max  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
2
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Mechanical  
Case Cover / Chassis  
Dimensions (L x W x D)  
Unit Weight  
Aluminium  
121 x 70 x 117.3 mm  
0.89 kg  
Indicator  
Green LED (DC OK)  
Cooling System  
Terminal  
Convection  
Input 4 Pins (Rated 600V/35A)  
Output 4 Pins (Rated 300V/28A)  
Wire  
Input  
AWG 18-12  
Output  
AWG 16-12  
Mounting Rail  
Standard TS35 DIN Rail in accordance with EN 60715  
Sound Pressure Level (SPL) < 40dBA  
Noise (1 Meter from power supply)  
Environment  
Surrounding Air Temperature*  
Operating -25°C to +80°C (Cold Start at -40°C)  
Storage -40°C to +85°C  
Power De-rating  
Vertical Mounting > 50°C de-rate power by 2.5% / °C,  
> 70°C de-rate power by 5% / °C  
Horizontal Mounting > 40°C de-rate power by 2.5% / °C,  
> 60°C de-rate power by 5% / °C  
Operating Humidity  
Operating Altitude  
0 to 95% RH (Non-Condensing)  
0 to 2,500 Meters for ITE application (@ 50°C)  
0 to 2,000 Meters for Industrial application (@ 50°C)  
Shock Test (Non-Operating)  
Vibration (Non-Operating)  
Pollution Degree  
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,  
1 time per direction, 2 times in total  
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);  
60 min per axis for all X, Y, Z direction  
2
*Cold start at I/P: 320Vac, Ta: -25°C, PSU will need 30 seconds to fully turn on  
Protections  
Overvoltage  
32V ±10%, SELV Output, Hiccup Mode,  
Non-Latching (Auto-Recovery)  
Overload / Overcurrent  
Over Temperature  
Short Circuit  
> 150% of rated load current, Hiccup Mode,  
Non-Latching (Auto-Recovery)  
< 80°C Surrounding Air Temperature @ 100% load,  
Non-Latching (Auto-Recovery)  
Hiccup Mode, Non-Latching  
(Auto-Recovery when the fault is removed)  
Degree of Protection  
IP20  
Protection Against Shock  
Class I with PE** connection  
**PE: Primary Earth  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
3
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Reliability Data  
MTBF  
> 500,000 hrs. as per Telcordia SR-332  
I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C  
Expected Cap Life Time  
10 years (3 x 400Vac & 3 x 500Vac, 50% load @ 40°C)  
Safety Standards / Directives  
Electrical Equipment in Power Installations  
Electrical Safety  
EN 50178 / IEC 62103  
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1  
and CSA C22.2 No. 60950-1, CB scheme to  
IEC 60950-1  
Industrial Control Equipment  
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01,  
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)  
Hazardous Location / ATEX (For DRP024V240W3BA)  
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA  
12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4,  
Ta = -25°C to +80°C for Vertical (> +50°C derating) and  
-25°C to +70°C for Horizontal (> +40°C derating)]  
EN 60079-0:2012, EN 60079-15:2010 [  
II 3G Ex nA  
IIC T4 Gc, Ta= -25°C to +80°C for Vertical (> +50°C  
derating) and -25°C to +70°C for Horizontal (> +40°C  
derating)]  
II 3G ATEX 94/9/EC (For DRP024V240W3BA)  
CE  
Certificate No. EPS 13 ATEX 1 575 X  
In conformance with EMC Directive 2004/108/EC and  
Low Voltage Directive 2006/95/EC  
For DRP024V240W3BA:  
In conformance with Equipment for explosive  
atmospheres (ATEX) directive 94/9/EC  
Material and Parts  
Galvanic Isolation  
RoHS Directive 2011/65/EU Compliant  
Input to Output 4.0KVac  
Input to Ground 2.0KVac  
Output to Ground 1.5KVac  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
4
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
EMC  
EMC / Emissions  
CISPR 22, EN 55022, CISPR 11, EN 55011,  
FCC Title 47: Class B  
Component Power Supply for General Use  
Immunity to  
EN 61204-3  
EN 55024, EN 61000-6-2  
Electrostatic Discharge  
IEC 61000-4-2 Level 4 Criteria A1)  
Air Discharge: 15kV  
Contact Discharge: 8kV  
Radiated Field  
IEC 61000-4-3 Level 3 Criteria A1)  
80MHz-1GHz, 10V/M, 80% modulation (1KHz)  
1.4GHz-2GHz, 3V/M, 80% modulation (1KHz)  
2GHz-2.7GHz, 1V/M, 80% modulation (1KHz)  
Electrical Fast Transient / Burst  
Surge  
IEC 61000-4-4 Level 3 Criteria A1)  
2kV  
IEC 61000-4-5 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
Conducted  
IEC 61000-4-6 Level 3 Criteria A1)  
150kHz-80MHz, 10Vrms  
Power Frequency Magnetic Fields  
IEC 61000-4-8 Criteria A1)  
30A/Meter  
Voltage Dips  
IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable  
Low Energy Pulse Test (Ring Wave)  
IEC 61000-4-12 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
Harmonic Current Emission  
IEC/EN 61000-3-2, Class A  
IEC/EN 61000-3-3  
Voltage Fluctuation and Flicker  
1) Criteria A: Normal performance within the specification limits  
2) Asymmetrical: Common mode (Line to earth)  
3) Symmetrical: Differential mode (Line to line)  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
5
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Block Diagram  
Device Description  
1) Input terminal block connector  
2) Output terminal block connector  
3) DC Voltage adjustment potentiometer  
4) DC OK control LED (Green)  
5) Universal mounting rail system  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
6
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Dimensions  
L x W x D: 121 x 70 x 117.3 mm  
Engineering Data  
De-rating  
Note  
1. Power supply components may degrade, or  
be damaged, when the power supply is  
continuously used outside the shaded region,  
refer to the graph shown in Fig. 1.  
2. If the output capacity is not reduced when the  
surrounding air temperature >50°C (Vertical)  
or >40°C (Horizontal), the device may run  
into Over Temperature Protection. When  
activated, the output voltage will go into  
bouncing mode and will recover when the  
surrounding air temperature is lowered or the  
load is reduced as far as necessary to keep  
the device in working condition.  
3. In order for the device to function in the  
manner intended, it is also necessary to keep  
a
safety distance of 5mm (for Vertical  
Mounting) or 50mm (for Horizontal Mounting)  
with adjacent units while the device is in  
operation.  
4. Depending  
on  
the  
surrounding  
air  
temperature and output load delivered by the  
power supply, the device can be very hot!  
5. If the device has to be mounted in any other  
orientation, please do not hesitate to contact  
Fig. 1 De-rating for Vertical Mounting Orientation  
> 50°C de-rate power by 2.5% / °C,  
> 70°C de-rate power by 5% / °C  
De-rating for Horizontal Mounting Orientation  
> 40°C de-rate power by 2.5% / °C,  
> 60°C de-rate power by 5% / °C  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
7
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Output De-rating VS. Input Voltage  
No output power de-rating across the entire  
input voltage range 320-600Vac  
(3-Phase) or 2 x 360-600Vac (2-Phase)  
3
x
Assembly & Installation  
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN 60715. For Vertical Mounting, the device  
should be installed with input terminal block at the bottom. For Horizontal Mounting, the device should be installed with input terminal  
block on the left side.  
Each device is delivered ready to install.  
Mounting  
Dismounting  
Fig. 2.1 Mounting  
Fig. 2.2 Dismounting  
Snap on the DIN rail as shown in Fig. 2.1:  
1. Tilt the unit upwards and insert it onto the DIN rail.  
2. Push downwards until stopped.  
3. Press against the bottom front side for locking.  
4. Shake the unit slightly to ensure that it is secured.  
To uninstall, pull or slide down the latch with screw driver as  
shown in Fig. 2.2. Then slide the power supply unit (PSU) in  
the opposite direction, release the latch and pull out the power  
supply unit (PSU) from the rail.  
In accordance to EN 60950 / UL 50950, flexible cables require ferrules.  
Use appropriate copper cables designed to sustain operating temperature of:  
1. 60°C, 60°C / 75°C for USA  
2. At least 75°C for ambient not exceeding 40°C, and 90°C for ambient exceeding 40°C for Canada.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
8
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Safety Instructions  
Vertical Mounting  
Horizontal Mounting  
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not  
turned OFF, there is risk of explosion / severe damage.  
To guarantee sufficient convection cooling, keep a distance of 50mm above and below the device as well as a lateral  
distance of 5mm (for Vertical Mounting) or 50mm (for Horizontal Mounting) to other units.  
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power  
supply. Risk of burns!  
Only plug in and unplug connectors when power is turned off!  
DO NOT insert any objects into the unit.  
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during  
this time.  
The power supplies unit should be installed in minimum IP54 rated enclosure.  
The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor  
location) that is relatively free of conductive contaminants.  
CAUTION: “For use in a controlled environment”.  
For DRP024V240W3BA:  
The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must  
comply with EN60079-0 or EN60079-15.  
Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.  
Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer unless the power has been switched off or the  
area is known to be non-hazardous.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
9
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Functions  
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time  
Start-up Time  
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.  
Rise Time  
The time required for the output voltage to change from 10% to 90% of its set value.  
Hold-up Time  
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time  
required for the output to reach 90% of its set value, after the input voltage is removed.  
Inrush Current  
Dynamic Response  
Inrush current is the peak, instantaneous, input current measured  
and, occurs when the input voltage is first applied. For AC input  
voltages, the maximum peak value of inrush current will occur  
during the first half cycle of the applied AC voltage. This peak  
value decreases exponentially during subsequent cycles of AC  
voltage.  
The power supply output voltage will remains within ±5% of its  
steady state value, when subjected to a dynamic load from 0 to  
100% of its rated current.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
10  
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Power Boost  
Power Boost is the reserve power available  
constantly that allows reliable startup to support  
sudden and short spike of loads with high inrush  
current typically during turn on to remove the  
need of more expensive higher rated power  
supply unit. After the output has reached its  
steady state set value, the power supply can  
support surge loads with a higher short-term  
power demand up to 150% of maximum rated  
load (IO Max), for a maximum duration of 5  
seconds. The Power Boost is also available to  
repeatedly basis with according to the condition of  
an average (R.M.S) output power shall not  
exceed continuous operating condition or refer to  
duty cycle calculation below.  
푃  
( )  
퐷푢푡푦 푐푦푐푙푒 % =  
푇표푡푎푙 푇푖푚푒  
(
)
(ꢀ표푤푒푟 퐵표표푠푡 × ) + 푁표푛-ꢀ푒푎푘 ꢀ표푤푒푟 × ꢄ  
퐴푣푒푟푎푔푒 푂푢푡푝푢푡 ꢀ표푤푒푟 (ꢁꢂ) =  
푇표푡푎푙 푇푖푚푒  
OR  
(
)
�ꢀ × 푇표푡푎푙 푇푖푚푒ꢅ − ꢀ표푤푒푟 퐵표표푠푡 × 푃  
ꢁꢂꢃ  
푁표푛-ꢀ푒푎푘 ꢀ표푤푒푟 =  
ꢄ  
An example of Power Boost and Average Output Power  
Peak Power  
(WP)  
Power Boost  
Duration (TP)  
Non-Peak  
Power (WN)  
Non-Peak Power  
Duration (TN)  
Total Time  
(T)  
Power Boost  
Duty Cycle  
10%  
150%  
150%  
120%  
120%  
360  
5 sec  
226W  
45 sec  
9.3 sec  
40 sec  
18.5 sec  
50 sec  
360  
288  
288  
5 sec  
35%  
20%  
35%  
175W  
14.3 sec  
50 sec  
10 sec  
10 sec  
228W  
214W  
28.5 sec  
It is not recommended to prolong the duration of Power Boost to be longer than the specified duty cycle calculation, this may cause  
damage to the PSU.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
11  
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Overload & Overcurrent Protections  
Overvoltage Protection  
The power supply’s Overload (OLP) and Overcurrent (OCP)  
Protections will be activated when output current exceeds 150%  
of IO (Max load). In such occurrence, the VO will start to droop and  
once the power supply has reached its maximum power limit, the  
protection is activated and the power supply will go into “Hiccup  
mode” (Auto-Recovery). The power supply will recover once the  
fault condition of the OLP and OCP is removed and IO is back  
within the specifications.  
The power supply’s overvoltage circuit will be activated when its  
internal feedback circuit fails. The output voltage shall not exceed  
its specifications defined on Page 3 under “Protections”.  
Over Temperature Protection  
As mentioned above, the power supply also has Over  
Temperature Protection (OTP). In the event of a higher operating  
temperature at 100% load, the power supply will run into OTP  
when the operating temperature is beyond what is recommended  
in the de-rating graph. When activated, the output voltage will go  
into bouncing mode until the temperature drops to its normal  
operating temperature as recommended in the de-rating graph.  
It is not recommended to prolong the duration of IO when it is  
<150% but >100%, since it may cause damage to the PSU.  
Short Circuit Protection  
The power supply’s output OLP/OCP function also provides  
protection against short circuits. When a short circuit is applied,  
the output current will operate in “Hiccup mode”, as shown in the  
illustration in the OLP/OCP section on this page. The power  
supply will return to normal operation after the short circuit is  
removed.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
12  
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Operating Mode  
Fig. 3  
Redundancy / Parallel Operation Connection Diagram  
Redundancy Operation  
In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output voltage difference between the  
two units is kept at 0.45~0.50V for 24V supplies. Follow simple steps given below to verify:  
Step 1.  
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then VO of PSU 1 must be higher than PSU 2.  
In order to set the output voltage, connect the power supply to 50% load and set the PSU 1 and PSU 2 output voltage.  
Step 2.  
Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin  
respectively.  
2
Step 3.  
Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power  
supply) – Vdrop* (in DRR module).  
Parallel Operation  
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A  
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRP024V240W3B☐  
is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as  
below (Refer to Fig. 3 for the Connection Diagram).  
Step 3.  
Step 1.  
Connect PSU 1 and PSU 2 with the DRR-20A module and  
Set output load condition for both supplies at 50% and measure  
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure  
the output voltages.  
the voltages are within ±25mV.  
Step 2.  
Step 4.  
Adjust output voltages to the same level or within ±25mV  
difference.  
Output voltage from DRR module Vout will be = VO (output  
voltage of power supply) – Vdrop* (in DRR module).  
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
13  
www.DeltaPSU.com (May 2014, Rev. 03)  
TECHNICAL DATASHEET  
CliQ II DIN Rail Power Supply  
24V 240W 3 Phase / DRP024V240W3B□  
Others  
Delta RoHS Compliant  
Restriction of the usage of hazardous substances  
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,  
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and  
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in  
electrical and electronic equipment”.  
This product conforms to this standard.  
Conformal Coating  
The Protective Coating Technology  
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including  
under device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circuit board.  
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants  
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem  
especially in highly conversing atmosphere.  
PFC – Norm EN 61000-3-2  
Line Current Harmonic content  
Typically, the input current waveform is not sinusoidal due to the periodical peak charging of the input capacitor.  
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying  
to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial  
aspects such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard,  
therefore, it is important to know whether it is mandatory to meet this standard for a specific application.  
All parameters are specified at 25°C ambient unless otherwise indicated.  
www.DeltaPSU.com (May 2014, Rev. 03)  
14  

相关型号:

DRP024V480W1AA

CliQ Din Rail Power Supply 24V 480W 1 Phase
DELTA

DRP024V480W1BA

CliQ II DIN Rail Power Supply
DELTA

DRP024V480W1BN

Power will not de-rate for the entire input voltage range
POWERBOX

DRP024V480W1BN

CliQ II DIN Rail Power Supply
DELTA

DRP024V480W3AA

CliQ Din Rail Power Supply 24V 480W 3 Phase
DELTA

DRP024V480W3BA

CliQ II DIN Rail Power Supply
DELTA

DRP024V480W3BN

CliQ II DIN Rail Power Supply
DELTA

DRP024V480W3BX

CliQ II DIN Rail Power Supply
DELTA

DRP048V060W1BA

CliQ II DIN Rail Power Supply
DELTA

DRP048V060W1BN

Power will not de-rate for the entire input voltage range
POWERBOX

DRP048V060W1BN

CliQ II DIN Rail Power Supply
DELTA

DRP048V120W1BA

CliQ II DIN Rail Power Supply
DELTA