PMC-24V150W1AJ [DELTA]

PMC Panel Mount Power Supply;
PMC-24V150W1AJ
型号: PMC-24V150W1AJ
厂家: DELTA ELECTRONICS, INC.    DELTA ELECTRONICS, INC.
描述:

PMC Panel Mount Power Supply

文件: 总12页 (文件大小:646K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
PMC  
Highlights & Features  
– Universal AC input range from 85Vac to 264Vac without power  
deꢀrating  
– Full Aluminum casing for light weight and corrosion resistant  
handling  
– High MTBF > 700,000 hrs. as per Telcordia SRꢀ332  
– Overvoltage / Overcurrent / Over Temperature Protections  
IP 20 Compliant (for PMCꢀ24V150W1AJ)  
Safety Standards  
CB Certified for worldwide use  
Model Number:  
Unit Weight:  
PMCꢀ24V150W1AX  
0.48 kg  
Dimensions (L x W x D): 178 mm x 97 mm x 38 mm  
General Description  
The new Panel Mount Power Supply is the latest offering from one of the world’s largest power supply manufacturers and solution  
providers ꢀ Delta. The product range offers a nominal output voltage of 24V, a wide temperature range from ꢀ10°C to +70°C and a  
highly dependable minimum holdup time. The stateꢀofꢀtheꢀart design is made to withstand harsh industrial environments. What makes  
the product stands out from the crowd is its lightweight full aluminum body design which can withstand shock and vibration according to  
IEC60068ꢀ2. Delta’s Panel Mount Power Supply also offers overvoltage and overload protection. Using a wide input voltage range  
design, it is compatible worldwide. The input also includes DC operating voltage from 125ꢀ375Vdc. Best of all, this excellent design and  
quality does not come with a big price tag.  
Model Information  
PMC Panel Mount Power Supply  
Model Number  
Input Voltage Range  
Output  
Voltage  
Output Current  
PMCꢀ24V150W1AX  
85ꢀ264Vac (125ꢀ375Vdc)  
24Vdc  
6.25A  
Model Numbering  
PMC  
24V  
Output Voltage  
150W  
1
A
X
A ꢀ Terminal Block  
PMC Series  
Output Power  
Single Phase  
Delta Standard  
Connector  
J ꢀ IP 20 Connector  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
1
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Specifications  
Input Ratings / Characteristics  
Nominal Input Voltage  
Input Voltage Range  
Nominal Input Frequency  
Input Frequency Range  
Nominal DC Input Voltage  
DC Input Voltage Range  
Input Current  
100ꢀ240Vac  
85ꢀ264Vac  
50ꢀ60Hz  
47ꢀ63Hz  
125ꢀ250Vdc  
125ꢀ375Vdc  
< 3.1A @ 115Vac, < 2.0A @ 230Vac  
> 87% @ 115Vac, > 88% @ 230Vac  
< 60A @ 115Vac, < 120A @ 230Vac  
NA  
Efficiency at 100% Load  
Max Inrush Current  
Power Factor  
Leakage Current  
< 1mA @ 240Vac  
Output Ratings / Characteristics  
Nominal Output Voltage  
Output Voltage Tolerance  
Output Voltage Adjustment Range  
Output Current  
24Vdc  
± 2% (initial set point tolerance from factory)  
22ꢀ28Vdc  
6.25A  
Output Power  
150W  
Line Regulation  
< 0.5% typ. (@ 85ꢀ264Vac input, 100% load)  
< 1% typ. (@ 85ꢀ264Vac input, 0ꢀ100% load)  
< 100mVpp  
Load Regulation  
PARD (20MHz)  
RiseTime  
< 30ms @ nominal input (100% load)  
< 1000ms @ nominal input (100% load)  
> 15ms @ 115Vac, > 80ms @ 230Vac (100% load)  
± 5% @ 0ꢀ100% load  
Startꢀup Time  
Holdꢀup Time  
Dynamic Response (Overshoot & Undershoot O/P Voltage)  
Startꢀup with Capacitive Loads  
8,000ꢁF Max  
Mechanical  
Case Cover  
Aluminium  
Dimensions (L x W x D)  
178 mm x 97 mm x 38 mm  
Unit Weight  
Indicator  
0.48 kg  
Green LED (DC OK)  
Convection  
System Cooling  
Terminal  
Input and Output PMCꢀ24V150W1AA: M3.5 x 7 Pins (Rated 300V/15A)  
PMCꢀ24V150W1AJ: M3.5 x 7 Pins (Rated 300V/20A)  
PMCꢀ24V150W1AA: AWG 22ꢀ14  
Wire  
PMCꢀ24V150W1AJ: AWG 22ꢀ12  
Noise  
Sound Pressure Level (SPL) <40dBA  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
2
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Environment  
Surrounding Air Temperature  
Operating ꢀ10°C to +70°C  
Storage ꢀ25°C to +85°C  
> 50°C deꢀrate power by 2.5% / °C  
Power Deꢀrating  
Operating Humidity  
Operating Altitude  
< 95% RH  
3,000 Meters  
Shock Test (NonꢀOperating)  
IEC60068ꢀ2ꢀ27, 30G (300m/S²) for a duration of 18ms  
3 times per direction, 18 times in total  
Vibration (NonꢀOperating)  
Pollution Degree  
IEC60068ꢀ2ꢀ6, 10Hz to 500Hz @ 50m/S² (5G peak);  
20 min per axis for all X, Y, Z direction  
2
Protections  
Overvoltage  
< 32V ±10%, SELV output, Hiccꢀup Mode,  
NonꢀLatching (Auto recovery).  
Overload / Overcurrent  
Over Temperature  
Short Circuit  
> 120% of rated load current, Hiccꢀup Mode,  
NonꢀLatching (Auto recovery).  
< 75°C Ambient Temp@ 100% load,  
NonꢀLatching (Autoꢀrecovery).  
Hiccꢀup Mode, NonꢀLatching  
(Autoꢀrecovery when the fault is removed).  
Class I with PE* connection  
Protection Against Shock  
*PE: Primary Earth  
Reliability Data  
MTBF  
> 700,000 hrs, as per per Telcordia SRꢀ332  
Expected Cap Life Time  
10 years (115Vac & 230Vac, 50% load @ 40°C)  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
3
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Safety Standards / Directives  
Electrical Safety  
TUV Bauart to EN60950ꢀ1, UL/cUL recognized to  
UL60950ꢀ1 and CSA C22.2 No. 60950ꢀ1, CB scheme to  
IEC60950ꢀ1  
CE  
In conformance with EMC Directive 2004/108/EC and  
Low Voltage Directive 2006/95/EC  
Material and Parts  
RoHS Directive 2011/65/EU Compliant  
Galvanic Isolation  
Input to Output 3.0 KVac  
Input to Ground 1.5 KVac  
Output to Ground 500 Vac  
EMC  
EMC / Emissions  
Immunity to  
CISPR22, EN55022, FCC Title 47: Class B  
Electrostatic Discharge  
IEC61000ꢀ4ꢀ2 Level 4 Criteria A1)  
Air Discharge: 15kV  
Contact Discharge: 8kV  
Radiated Field  
IEC61000ꢀ4ꢀ3 Level 3 Criteria A1)  
80MHzꢀ1GHz, 10V/M with 1kHz tone / 80% modulation  
Electrical Fast Transient / Burst  
Surge  
IEC61000ꢀ4ꢀ4 Level 3 Criteria A1)  
2kV  
IEC61000ꢀ4ꢀ5 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 2kV  
Conducted  
IEC61000ꢀ4ꢀ6 Level 3 Criteria A1)  
150kHzꢀ80MHz, 10Vrms  
Power Frequency Magnetic Fields  
IEC61000ꢀ4ꢀ8 Criteria A1)  
10A/Meter  
Voltage Dips  
IEC61000ꢀ4ꢀ11 100% dip; 1 cycle (20ms); Self Recoverable  
Low Energy Pulse Test (Ring Wave)  
IEC61000ꢀ4ꢀ12 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
1) Criteria A: Normal performance within the specification limits  
2) Asymmetrical: Common mode (Line to earth)  
3) Symmetrical: Differential mode (Line to line)  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
4
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Block Diagram  
Device Description  
1)  
2)  
3)  
Input & Output terminal block connector  
DC Voltage adjustment potentiometer  
DC OK control LED (Green)  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
5
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Dimensions  
L x W x D: 178 x 97 x 38 mm  
Engineering Data  
Deꢀrating VS surrounding air temperature  
Note  
1. Power supply components may degrade, or be  
damaged, when the power supply is  
continuously used outside the shaded region,  
refer to the graph shown in Fig. 1.  
2. If the output capacity is not reduced when the  
surrounding air temperature > 50°C, the device  
may run into Over Temperature Protection.  
When activated, the output voltage will go into  
bouncing mode and will recover when the  
surrounding air temperature is lowered or the  
load is reduced as far as necessary to keep the  
device in working condition.  
3. If the device has to be mounted in any other  
orientation, please do not hesitate to contact  
info@deltapsu.com for more details.  
4. In order for the device to function in the manner  
intended, it is also necessary to keep a safety  
distance of 20mm with adjacent units while the  
device is in operation.  
5. Depending on the surrounding air temperature  
and output load delivered by the power supply,  
the device housing can be very hot!  
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation  
> 50°C de-rate power by 2.5% / °C  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
6
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Deꢀrating VS AC input voltage  
No output power deꢀrating across the entire  
input voltage range  
Assembly & Installation  
Mounting  
Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on minimum 2 mounting  
holes using M3 screw minimum 5 mm length.  
This surface belongs to customer’s end system or panel where the power supply is mounted.  
Connector.  
Side Mounting (Vertical)  
Base Mounting (Vertical)  
Side Mounting (Horizontal)  
Fig. 2 Mounting Orientation  
Installation  
Only use M3 screw ≤ 6 mm through the base mounting holes. This is to  
keep a safe distance between the screw and internal components.  
Recommended mounting tightening torque : 4~8Kgf.cm  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
7
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Safety Instructions  
To ensure sufficient convection cooling, always maintain a safety distance of > 20mm from all ventilated surfaces while the  
device is in operation.  
The device is not recommended to be placed on low thermal conductive surface, for example, plastics.  
Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power  
supply. Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!  
Do not touch the terminals while power is being supplied. Risk of electric shock.  
Prevent any foreign metal, particles or conductors to enter the device through the openings during installation. It can cause: ꢀ  
ꢀ Electric shock; Safety Hazard; Fire; Product failure  
Warning: When connecting the device, secure Earth connection before connecting L and N. When disconnecting the device,  
remove L and N connections before removing the Earth connection.  
Functions  
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time  
Startꢀup Time  
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.  
Rise Time  
The time required for the output voltage to change from 10% to 90% of its set value.  
Holdꢀup Time  
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time  
required for the output to reach 95% of its set value, after the input voltage is removed.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
8
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Inrush Current  
Overload & Overcurrent Protections  
Inrush Current is the first surge current seen on the input side  
when AC input is applied to the power supply. It is the first pulse  
captured; see a typical picture for the inrush current as seen in  
the power supply.  
The power supply’s Overload (OLP) and Over current (OCP)  
Protections will be activated when output current exceeds 120%  
of IO (Max load). In such occurrence, the VO will start to droop and  
once the power supply has reached its maximum power limit, the  
protection is activated and the power supply will go into “Hiccup  
mode” (AutoꢀRecovery). The power supply will recover once the  
fault condition of the OLP and OCP is removed and IO is back  
within the specifications.  
Additionally, if the IO is < 120% but > 100% for a prolong period of  
time (depending on the load), the Over Temperature Protection  
(OTP) will be activated due to high temperature on critical  
components. The power supply will then go into “Hiccup mode”  
until power supply cool down.  
Dynamic Response  
The power supply output voltage will remains within ±5% of its  
steady state value, when subjected to a dynamic load from 0 to  
100% of its rated current.  
Over Temperature Protection  
As mentioned above, the power supply also has Over  
Temperature Protection (OTP). This is activated when the  
overload condition persists for an extended duration and the  
output current is below the overload trigger point but > 100% load.  
In the event of a higher operating condition at 100% load, the  
power supply will run into OTP when the surrounding air  
temperature is > 75°C. When activated, the output voltage will go  
into bouncing mode until the operating surrounding temperature  
drops to 50°C or output capacity is reduced as recommended in  
the deꢀrating graph.  
Overvoltage Protection  
Short Circuit Protection  
The power supply’s overvoltage circuit will be activated when its  
internal feedback circuit fails. The output voltage shall not exceed  
its specifications defined on Page 3 under “Protections”.  
The power supply’s output OLP/OCP function also provides  
protection against short circuits. When a short circuit is applied,  
the output current will operate in “Hiccup mode”, as shown in the  
illustration in the OLP/OCP section on this page. The power  
supply will return to normal operation after the short circuit is  
removed.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
9
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Operating Mode  
Redundancy Operation  
In order to ensure proper redundancy operation for the  
power supply unit (PSU), ensure that the output voltage  
difference between the two units is kept at 0.45~0.50V  
for 24V supplies. Follow simple steps given below to  
verify:  
Step 1.  
Measure output voltage of PSU 1 and PSU 2. If PSU 1  
is the master unit, then VO of PSU 1 must be higher than  
PSU 2.  
In order to set the output voltage, connect the power  
supply to 50% load and set the PSU 1 and PSU 2  
output voltage.  
Step 2.  
Connect the right DRR module, 20A as per the system  
requirement to the power supply units PSU 1 and PSU 2  
at Vin 1 & Vin 2 respectively.  
Fig. 3 Redundancy / Parallel Operation Connection Diagram  
Step 3.  
Connect the system load from Vout. Please note that  
output voltage Vout from DRR module will be = VO  
(output voltage of power supply) – Vdrop* (in DRR  
module).  
Parallel Operation  
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A  
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the PMCꢀ24V150W1AX  
is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as  
below (Refer to Fig. 3 for the Connection Diagram).  
Step 1.  
Step 3.  
Set output load condition for both supplies at 50% and measure  
the output voltages.  
Connect PSU 1 and PSU 2 with the DRRꢀ20A module and  
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure  
the voltages are within ±25mV.  
Step 2.  
Step 4.  
Adjust output voltages to the same level or within ±25mV  
difference.  
Output voltage from DRR module Vout will be = VO (output  
voltage of power supply) – Vdrop* (in DRR module).  
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
10  
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
24V 150W 1 Phase / PMCꢀ24V150W1AX  
Others  
Delta RoHS Compliant  
Restriction of the usage of hazardous substances  
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,  
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and  
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in  
electrical and electronic equipment”.  
This product conforms to this standard.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (March 2013, Rev. 00)  
11  
Mouser Electronics  
Authorized Distributor  
Click to View Pricing, Inventory, Delivery & Lifecycle Information:  
Delta:  
PMC-24V150W1AA  

相关型号:

PMC-24V150W1AX

PMC Panel Mount Power Supply
DELTA

PMC-24V300W1BA

24V 300W 1 Phase
DELTA

PMC-48V150W1BA

PMC Panel Mount Power Supply
DELTA

PMC-48V150W1BH

PMC Panel Mount Power Supply
DELTA

PMC-48V150W1BJ

PMC Panel Mount Power Supply
DELTA

PMC-48V150W1BL

PMC Panel Mount Power Supply
DELTA

PMC-5001

High Power Reed Switch
PIC

PMC-5002

High Power Reed Switch
PIC

PMC-5025

Power Form C Switch
PIC

PMC-5025E

Latching Reed Switch
PIC

PMC-DSPV100W1A

Dual 24V/5V 100W 1 Phase
DELTA

PMC-GPIB

GPIB Interface for PCI Mezzanine Bus
NI