LPS100-M_10 [EMERSON-NETWORKPOWER]
150 Watts; 150瓦型号: | LPS100-M_10 |
厂家: | EMERSON NETWORK POWER |
描述: | 150 Watts |
文件: | 总3页 (文件大小:419K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Embedded Power for
Business-Critical Continuity
Rev. 03.30.10_29
LPS100-M Series
1 of 3
LPS100-M Series
150 Watts
Total Power:
Input Voltage: 90 - 264 Vac
# of Outputs: Single
80 - 150 Watts
Electrical Specifications
Special Features
• Medical and ITE safeties
• Active power factor correction
• 2” x 4” footprint
• Less than 1U high
• EN61000-3-2 compliant
• Remote sense
Input
Input range:
Frequency:
90 - 264 Vac; 120 - 300 Vdc
47-63 Hz
Inrush current:
50 A max., cold start @ 25 °C
Efficiency:
EMI/RFI:
88% typical at full load
• Power fail
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
275 µA @ 50/60 Hz, 264 Vac input
• Adjustable main output
• Built-in Class B EMI filter
• Overvoltage protection
• Overload protection
• Thermal overload protection
• Isolated12 V Fan output
• LPX50 Enclosure kit available
Safety ground
leakage current:
Output
100 W for convection (80 W for LPS102-M);
150 W with 30 CFM forced air (120 W for LPS102-M)
± 10% minimum on the main outputs
Maximum power:
Adjustment range:
Fan output:
12 V @ 1 A isolated, ± 10%
Hold-up time:
10 ms @ 150 W load, 120 Vac input
Overload protection:
Short circuit protection on all outputs. Case overload
protected @ 110-160% above rating
Overvoltage protection:
15-35% above nominal output
Logical Control
Power failure:
Open collector logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Remote sense:
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.
Safety
• TUV
• UL
60950, 60601-1
60950, 60601-1
60950, 60601-1
Certificate & report
Mark (LVD)
• cULus
• CB
• CE
• CQC
Mark
Embedded Power for
Business-Critical Continuity
Rev. 03.30.10_29
LPS100-M Series
2 of 3
Environmental Specifications
Operating temperature:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up
Storage temperature:
Electromagnetic
susceptibility:
-40 °C to +85 °C
Designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Humidity:
Vibration:
Operating; non-condensing 10% to 95% RH
IEC68-2-6 to the levels of IEC721-3-2
MTBF calculated:
534,000 hours at full load and 25 °C ambient conditions, 230 V input, Bellcore
Mechanical Drawing
VR1
Output Voltage
Adjust Pot
SK203
SK2
M1
M2
1
4
8
GND
1
4
SK5
1
SK1
1
3
3.73"
(94.7)
Mounting Hole
Ø0.16"[4.0] 4 Places
Max. Screw Head
Diameter .22”(5.6)
4.00"
(101.6)
0.197”(5.0) Minimum
Standoff height
Embedded Power for
Business-Critical Continuity
Rev. 03.30.10_29
LPS100-M Series
3 of 3
Americas
Ordering Information
5810 Van Allen Way
Carlsbad, CA 92008
USA
Maximum Load
with Convection
Cooling
Maximum Load
with 30CFM
Forced Air
Model
Output
Voltage
Minimum
Load
Ripple
P/P (PARD)
2
Peak Load Regulation
3
Number
Telephone: +1 760 930 4600
Facsimile: +1 760 930 0698
LPS102-M
LPS103-M
LPS104-M
LPS105-M
LPS108-M
5 V
0 A
0 A
0 A
0 A
0 A
16 A
8.3 A
6.7 A
4.2 A
2.1 A
24 A
12.5 A
10 A
30 A
14 A
11 A
7 A
± 2%
± 2%
± 2%
± 2%
± 2%
50 mV
120 mV
150 mV
240 mV
480 mV
12 V
15 V
24 V
48 V
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone: +44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
6.3 A
3.1 A
3.5 A
1. Peak current lasting < 30 seconds with a maximum 10% duty cycle.
2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage
and load ranges.
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone: +852 2176 3333
Facsimile: +852 2176 3888
Mating Connectors
Pin Assignments
AC Input (SK1): Molex P/N: 09-50-3031, Pins: 08-52-0072
Connector LPS100-M
or
SK1
Pin 1
Pin 3
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 1
Pin 2
Pin 3
Pin 4
Pin 1
Pin 2
Pin 3
Pin 4
Neutral
Line
Common
Common
Common
Common
+Vout
+Vout
+Vout
+Vout
Common
Power Fail
- Remote Sense
+ Remote Sense
+12 V Fan
+12 V Fan
Fan Return (Isolated)
Fan Return (Isolated)
Landwin P/N: 3060S0302, Pins: 3360T011P
AC Ground
DC Output
(SK2):
Molex: 01-90020001
Molex P/N: 09-50-3081, Pins: 08-52-0072
or
SK2
For global contact, visit:
www.Emerson.com/EmbeddedPower
Landwin P/N: 3060S0802, Pins: 3360T011P
Remote Sense Molex P/N: 35155-0400, Pins: 08-70-0057
techsupport.embeddedpower
@emerson.com
(SK203):
or
Landwin P/N: 2640S04A0, Pins: 2543T011P
Molex P/N: 22-01-1042, Pins: 08-70-0049
or
Fan: (SK5):
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Landwin: P/N: 2510S04A0, Pins: 2543T011P
Emerson Network Power Connector Kit #70-841-025, includes all of the
above
SK203
SK5
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Notes:
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±.02”.
3. mounting holes MH1, MH2 should be grounded for EMI
purpose
Outside Plant
4. Mounting MH1 is safety ground connection
5. Specifications are for convection rating at factory settings
at 115 Vac input 25 °C unless otherwise stated.
6. This power supply requires mounting on metal standoffs
0.20” (5 m) in height.
7. For DC input an external DC safety rated fuse must be used.
8. Warranty: 2 year
9. Weight: 0.44 lb. / 0.20 kg
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co.
©2010 Emerson Electric Co.
相关型号:
©2020 ICPDF网 联系我们和版权申明