B84299-D1320-B1 [EPCOS]
250V, 50/60Hz, SINGLE PHASE EMI FILTER;型号: | B84299-D1320-B1 |
厂家: | EPCOS |
描述: | 250V, 50/60Hz, SINGLE PHASE EMI FILTER LTE |
文件: | 总8页 (文件大小:205K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
Filter für:Netzleitungen
Two- and four-line filters
16 to 100 A
Single-stage
Stopband attenuation up to 40 GHz
Features
ꢀ General-purpose use through design with separate lines without intercoupling
ꢀ Use of single chokes
ꢀ Insertion loss to CISPR 17
Design
The electrical components are incorporated in an RF-tight case of stainless steel. The cables enter
through glands. The RF-tight termination of the openings is produced by specially shaped lids.
The conductors and equipment grounding conductor are connected by threaded bolts. The space
around the fixing holes is left as bare metal (unpainted) to ensure good RF contact with metal sur-
faces (chassis, ground).
Protective measures (grounding)
The high capacitances between the lines and ground require special protective measures. If there
are no product-specific requirements, protection with a secondary ground wire (diameter min.
10 mm2) in accordance with EN 50178 is necessary. For this purpose the filter case have connect-
ing bolts at each end.
Resistors are incorporated in the filter to discharge capacitors after turn-off.
Installation
Filters are supplied complete with all parts required for RF-tight installation (fixing screws, flanges,
RF gaskets, cable glands) and installation instructions.
No welding is needed on the shielding wall, so any subsequent installation is quite simple. And the
uniform template of the attachment points allows straightforward replacement of a two-line filter by
a four-line filter for example.
Accessories and special versions
RF-tight flexible connector fittings in widths of 25 and 40 mm are available for installation spaced
away from the shielding wall.
Filters with an EMP protection add-on for surge currents up to 100 kA per line are available on
request.
To match requirements, filters can be supplied with different kinds of EMC or shielding cable glands.
Tests
All filters are 100 % tested and the results are archived under a filter’s serial number. If required, a
test report can be generated for the serial number.
15 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
Circuit diagrams
Two-line filters B84299-+1***-B1
1‘
2‘
1
2
SSB1691-Q-E
Four-line filters B84299-+1***-E1
1
2
3
4
1‘
2‘
3‘
4‘
SSB1692-Y-E
Insertion loss αe (typical values at Z = 50 Ω)
SSB1694-F-E
120
dB
Measurement circuit
Measurement limit
α
50
Ω
e 100
up to 40 GHz
50
Ω
Filter
80
~
V0
V2
~
~
60
V0
40
= 20 lg
[dB]
α e
.
2 V2
SSB1693-7-E
20
0
104
105
106
107
108 Hz 109
f
16 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
General technical data
Rated voltage VR
250 V
line/line
for two-line filters
line/case
Rated voltage VR
for four-line filters
440 V
250 V
line/line
line/case
Rated current IR
see characteristics referred to + 40°C ambient temperature
(next page)
.
.
.
.
Max. admissible overcurrent Iover
75 IR for 50 ms
10 IR for 1 s
2
IR for 1 min
1,4 IR for 15 min
Rated frequency fR
Test voltages VT
50/60 Hz
1200 Vdc, 2 s
1200 Vdc, 2 s
line/line
line/case
Voltage drop/phase ∆V
DC resistance Rmax
< 1 %
of VR at 50 Hz and IR
see characteristics per line
(next page)
Power dissipation PD
see characteristics at IR
(next page)
Capacitive reactive
1 A
at 400/230V and 50 Hz (typical value)
current/line Ireactive
Climatic category
25/085/56
(−25 °C/+85 °C/56 days damp heat test)
to EN 60068-1
Mechanical version
C
D
cable glands at both ends
or flexible connector fitting
direct connection to shielding wall
Weight (approx.)
18 kg
20 kg
two-line filters
four-line filters
17 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
Characteristics and ordering codes
IR
Mechanical Rmax
PD
Ordering code
version
A
mΩ
W
Two-line filters
2 × 16
2 × 16
2 × 32
2 × 32
2 × 63
2 × 63
2 × 100
2 × 100
C
< 14
< 14
<
<
8
8
B84299-C1160-B1
B84299-D1160-B1
B84299-C1320-B1
B84299-D1320-B1
B84299-C1630-B1
B84299-D1630-B1
B84299-C1101-B1
B84299-D1101-B1
D
C
D
C
D
C
D
<
<
<
<
<
<
3,5
< 11
< 11
< 25
< 25
< 30
< 30
3,5
3,0
3,0
1,5
1,5
Four-line filters
4 × 16
4 × 16
4 × 32
4 × 32
4 × 63
4 × 63
4 × 100
4 × 100
C
< 14
< 14
< 20
< 20
< 20
< 20
< 35
< 35
< 45
< 45
B84299-C1160-E1
B84299-D1160-E1
B84299-C1320-E1
B84299-D1320-E1
B84299-C1630-E1
B84299-D1630-E1
B84299-C1101-E1
B84299-D1101-E1
D
C
D
C
D
C
D
<
<
<
<
<
<
3,5
3,5
3,0
3,0
1,5
1,5
18 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
Dimensional drawings
Mechanical version C (cable glands at both ends)
Shielded end
<155
Cable gland
288
10
268
Input end
RAL 7035 color
(light gray, semigloss)
SSB1695-N-E
IR
A
Fittings
Suitable for cable
outer diameter
Package
Suitable for cable
outer diameter
16
32
Cable gland PG 29
with cutout
sealing ring
17 to 19 mm
20 to 22 mm
23 to 25 mm
26 to 28 mm
Cable gland PG 21
and reducer rings
9 to 11 mm
12 to 14 mm
15 to 17 mm
18 to 20 mm
63
—
—
100
Cable gland PG 42
with cutout
sealing ring
29 to 31 mm
32 to 34 mm
35 to 37 mm
38 to 40 mm
Cable gland PG 29
and reducer rings
RF-tight connection to shielding wall, see page 21.
19 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
Mechanical version D (direct connection to shielding wall)
Hole PG 29 ( 37)
for 100 A: PG 42 ( 54)
Shielded end
<155
Connecting bolt M8
(at each end)
288
268
10
Input end
RAL 7035 color
(light gray, semigloss)
SSB1696-W-E
IR
A
Fittings
Suitable for cable
outer diameter
Package
Suitable for cable
outer diameter
16
32
Cable gland PG 29
with cutout
sealing ring
17 to 19 mm
20 to 22 mm
23 to 25 mm
26 to 28 mm
Cable gland PG 21
and reducer rings
9 to 11 mm
12 to 14 mm
15 to 17 mm
18 to 20 mm
63
—
—
100
Cable gland PG 42
with cutout
sealing ring
29 to 31 mm
32 to 34 mm
35 to 37 mm
38 to 40 mm
Cable gland PG 29
and reducer rings
RF-tight connection to shielding wall, see page 21.
20 12/01
Filters for Power Lines
B84299-+1***-B1
B84299-+1***-E1
16 to 100 A, 100 dB from 150 kHz
RF-tight connection to shielding wall with flexible connector fitting (mechanical version C)
Flexible connector fitting
Shielded end
Shielding wall
RF gasket
SSB1960-E-E
IR
Flexible connector fitting
Ordering code
A
(must be ordered separately)
B84298-A42-L** 1)
B84298-A44-L** 1)
16 ... 63 Width 25 mm
100 Width 40 mm
RF-tight connection to shielding wall (mechanical version D)
Cable gland
Shielding wall
RF gasket
– Self-locking screw M8 × 20
– Self-locking nut M8 (in package)
SSB1697-5
IR
A
Cable gland
Hole in shielding wall
37 + 0,5 mm
Bare metal area
on shielding wall
16
PG 29 with long thread and
55 +5 mm
32
63
RF gasket; check nut in package
100
PG 42
54 + 0,5 mm
70 +5 mm
1) ** add required length in cm (see also page 107 ff)
21 12/01
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
EPCOS AG 2002. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgele-
genen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsge-
sellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
EPCOS AG 2002. All Rights Reserved. Reproduction, publication and dissemination of this bro-
chure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be con-
sidered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY