Electronic circuit protector REX12  
Description  
The new electronic overcurrent protection REX12 consists of the  
supply module EM12-T and the single or double channel electronic  
circuit protector REX12-T which allows modular side-by-side mounting.  
The modules with a width of only 12.5 mm feature push-in  
technology including press release buttons and allow time-saving and  
maintenance-free wiring without tools. The supply module is designed  
for DC 24 V and 40 A and accommodates max. 10 mm² with wire  
end ferrule as a plus (+) supply. On the load output side the circuit  
protector can be wired with 2.5 mm².  
The new generation of electronic overcurrent protection REX12  
combines flexibility with a compact design. It is exactly tailored to the  
needs of machine and panel builders. And what is more: no additional  
accessories are required when connecting the individual components  
electrically and mechanically. This helps save time and money!  
Features  
Technical data (T  
= +23 °C, U = DC 24 V)  
amb B  
REX12-TAx-xxx circuit protectors  
REX12-TA1-107-DC24V-xA  
lꢀ  
Combination of supply module and electronic circuit protector  
Single and double channel selective load protection by means of  
electronic trip curve  
1-channel  
2-channel  
lꢀ  
REX12-TA2-107-DC24V-xA/xA  
lꢀ  
lꢀ  
Operating voltage UB  
DC 24 V (18...30 V)  
No accessories required for connecting the components  
Width per channel only 12.5 mm (1-channel) or  
Closed-circuit current I0  
REX12-TA1 1-channel  
REX12-TA2 2-channel  
6.25 mm (2-channel)  
Fixed current ratings from 1 A to 10 A  
in ON condition  
in ON condition  
typically 5 mA  
typically 8 mA  
lꢀ  
lꢀ  
lꢀ  
lꢀ  
lꢀ  
lꢀ  
Integral fail-safe element, adjusted to current rating  
Switching capacitive loads up to 20,000 µF  
Manual ON/OFF/reset momentary switch  
Clear status indication by means of LED and signal contact Si  
Reverse polarity  
protection  
yes  
Power failure  
buffering time  
up to 10 ms  
fixed ratings:  
1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A  
2 A / 2 A, 4 A / 4 A, 6 A / 6 A  
Connection via push-in terminals including orange press release  
Current ratings IN  
REX12-TA1  
REX12-TA2  
buttons  
Visual status indication  
green:  
load circuit connected  
Benefits  
by LED  
green/orange blinking:  
4
lꢀ  
load current warning limit reached 80 %  
Saves cost – no further accessories required  
Saves time through innovative and flexible mounting and  
connection technology  
Saves space – with a width of only 12.5 mm for two channels  
Provides flexibility through ease of mounting, disassembly and  
modular design  
lꢀꢀ ꢀ  
orange: overload or short circuit until  
disconnection  
lꢀ  
lꢀꢀ ꢀ  
red:  
- after disconnection due to  
overload or short circuit  
- after undervoltage release  
of operating voltage in ON  
condition with autoreset  
Device switched off by means  
of ON/OFF momentary switch  
or no operating voltage  
Approvals and standards  
OFF:  
Approval  
authority  
Standard  
Rated  
Current  
voltage  
rating range  
Load circuit  
UL  
UL  
UL 2367  
DC 24 V  
1 A…10 A  
1 A…10 A  
Load output  
power MOSFET switching output  
(plus switching)  
UL60947 / cULus508listed DC 24 V  
under preparation  
Load current  
typically 0.8 x IN  
warning limit (IWLimit  
hysteresis  
)
typically 5 %  
Overview of ordering number codes  
Overload current  
disconnection (IOL  
with trip times (tOL  
typically IOL: IN x 1.05  
typically IOL: IN x 1.35  
typically IOL: IN x 2.00  
typically IOL: IN x 2.50  
tOL: 3s  
)
)
tOL: 0,5 s  
tOL: 0.1 s  
tOL: 0.012 s  
Supply module  
EM12-T01-001-DC24V-40A  
REX12-TA1-107-DC24V-1A  
REX12-TA1-107-DC24V-2A  
REX12-TA1-107-DC24V-3A  
REX12-TA1-107-DC24V-4A  
REX12-TA1-107-DC24V-6A  
REX12-TA1-107-DC24V-8A  
REX12-TA1-107-DC24V-10A  
circuit protectors:  
1-channel  
Short circuit  
typically at short circuti (ISC) tSC: 0,002 s1)  
(see time/current characteristic)  
1) depends on the power suplly  
trip time (tSC  
)
Influence of ambient  
temperature on  
overload disconnection  
see temperature factor table  
and load current warning limit  
circuit protectors:  
2-channel  
REX12-TA2-107-DC24V-2A/2A  
REX12-TA2-107-DC24V-4A/4A  
REX12-TA2-107-DC24V-6A/6A  
1646  
www.e-t-a.de  
1
Electronic circuit protector REX12  
Technical data (T  
= +23 °C, U = DC 24 V)  
Technical data (T  
= +23 °C, U = DC 24 V)  
amb  
B
amb B  
General data  
Fail-safe element  
integral  
blade fuse  
adjusted to  
related current rating IN  
IN: 1 A  
IN: 2 A  
IN: 3 A  
IN: 4 A  
IN: 6 A  
fail-safe IN: 1 A  
fail-safe IN: 2 A  
fail-safe IN: 3.15 A  
fail-safe IN: 4 A  
fail-safe IN: 6.3 A  
fail-safe IN: 8 A  
Housing material  
Mounting  
moulded  
symmetrical rail to EN 60715-35x7.5  
Ambient temperature  
-25 °C...+60 °C  
(without condensation, cf. EN 60204-1)  
IN: 8 A  
IN: 10 A  
fail-safe IN: 10 A  
fail-safe IN: 2 A / 2 A  
fail-safe IN: 4 A / 4 A  
fail-safe IN: 6.3 A / 6.3 A  
Storage temperature  
Mounting temperature  
Humidity  
-40 °C...+70 °C  
+5 °C…+60 °C  
IN: 2 A / 2 A  
IN: 4 A / 4 A  
IN: 6 A / 6 A  
96 hrs / 95% RH 40 °C to IEC 60068-2-  
78-Cab, climate class 3K3 to EN 60721  
Voltage drop in load circuit at IN and at IN 70% between LINE+ and  
LOAD+  
Vibration  
3g test to IEC 60068-2-6, test Fc  
(IEC 60529, DIN VDE 0470) IP30  
IN: 1 A  
IN: 2 A  
IN: 3 A  
IN: 4 A  
IN: 6 A  
IN: 8 A  
IN: 10 A  
typically 180 mV  
typically 110 mV  
typically 120 mV  
typically 115 mV  
typically 170 mV  
typically 160 mV  
typically 180 mV  
IN: 70%  
IN: 70%  
IN: 70%  
IN: 70%  
IN: 70%  
IN: 70%  
IN: 70%  
typically 125 mV  
typically 80 mV  
typically 85 mV  
typically 80 mV  
typically 110 mV  
typically 105 mV  
typically 120 mV  
Degree of protection  
EMC requirements  
(EMC directive, CE logo) susceptibility:  
noise emission  
EN 61000-6-3  
EN 61000-6-2  
Insulation co-ordination  
(IEC 60934)  
0.5 kV / pollution degree 2  
max. DC 30 V (load circuit)  
Dielectric strength  
Operating voltage  
monitoring  
with regard to low voltage with automatic ON and  
OFF switching  
OFF at typically UB < 16.0 V  
ON at typically UB > 17.5 V  
Insulation resistance  
(OFF condition)  
n/a, only electronic disconnection  
Approvals  
CE logo,  
UL 2367, File # E306740,  
(UL60947 / UL 508, File # E...)  
under preparation  
Switch-on delay  
- with power ON  
channel 1:  
channel 2:  
typically 100 ms  
typically 200 ms  
- when switching on via channel 1:  
typically 5 ms  
typically 100 ms  
Ordering number code - REX12-T  
ON/OFF momentary  
switch or  
- after undervoltage  
channel 2:  
Type  
channel 1:  
channel 2:  
typically 5 ms  
typically 5 ms  
REX12 Electronic circuit protector with PT connection technology  
Mounting method  
Disconnection of  
load circuit  
- manually on the device with the  
ON/OFF momentary switch  
- after an overload / short circuit  
disconnection with storage  
(no automatic reset)  
T
rail mounting  
Design  
A
1 load output terminal per channel, fixed current ratings xA  
or xA/xA  
Number of channels  
- temporarily at undervoltage  
- at no operating voltage  
1
2
1 channel  
2 channels  
Version  
4
Switch-on of load circuit  
- momentary switch  
ON/OFF  
1
without physical isolation  
Signal input  
without signal input  
Signal output:  
device can only be switched on  
when operating voltage is applied  
0
- applying  
operating voltage  
the device starts up with the condition  
last stored  
7
status output  
Operating voltage  
Reset function  
a blocked load output (blocked by  
overload / short circuit) can externally be  
reset by the ON/OFF momentary switch  
DC 24 V  
voltage rating DC 24 V  
Current ratings  
1 A  
(only 1-channel)  
Leakage current in load typically < 1 mA  
circuit in OFF condition  
2 A  
3 A  
4 A  
6 A  
(only 1-channel)  
(only 1-channel)  
(only 1-channel)  
(only 1-channel)  
(only 1-channel)  
(only 1-channel)  
(only 2-channel)  
(only 2-channel)  
(only 2-channel)  
Capacitive loads  
up to 20,000 µF  
Free-wheeling diode  
external free-wheeling circuit at inductive  
load (rating according to load)  
8 A  
10 A  
2 A/2 A  
4 A/4 A  
6 A/6 A  
Parallel connection of  
several load outputs  
not allowed  
Status output  
REX12 - T  
REX12 - T  
A
A
1 - 1  
2 - 1  
0
0
7 - DC24V - 10 A  
7 - DC24V - 6 A / 6 A example of 2-channel  
example of 1-channel  
Status indication REX12-T minus switching signal output  
group signalling is implemented in  
connection with EM12-T supply module  
Screw terminals  
LOAD+  
0.14 mm2...2.5 mm2, flexible  
8 mm...10 mm  
Preferred types  
Push-in terminal PT 2.5  
Stripping length  
Preferred types  
REX12-TA1  
Standard current ratings (A)  
Dimensions (w x h x d)  
12.5 x 98,5 x 80 mm  
2
4
6
10 2/2 4/4 6/6  
Mass  
REX12-TA1-xxx 1-channel approx. 57 g  
REX12-TA2-xxx 2-channel approx. 58 g  
x
x
x
x
REX12-TA1-107-DC24V-  
REX12-TA2  
2
4
6
10 2/2 4/4 6/6  
x
x
x
REX12-TA2-107-DC24V-  
2
www.e-t-a.de  
1646  
Electronic circuit protector REX12  
Dimensions with connection diagram: REX12-TA1-xxx and REX12-TA2-xxx circuit protectors  
ꢇꢈꢉꢊ  
ꢇꢋ  
ꢒꢑꢍꢕꢎꢒꢕ ꢎꢗꢞ  
1ꢋꢉꢊ  
ꢂꢁꢠ1ꢋꢐ  
ꢂꢁꢠ1ꢋꢐ  
ꢡꢄ1ꢐ1ꢝꢝ  
ꢡꢄꢋꢐ1ꢝꢝ  
ꢭꢎꢮꢔꢙ ꢔꢯꢟꢯ ꢖꢗꢑꢞ  
ꢰꢥꢑꢔꢍꢘꢝ  
ꢢꢣꢋ4ꢤ  
ꢢꢣꢋ4ꢤ  
ꢣꢑꢍꢕꢎꢒꢕ ꢱꢲꢪꢐ1ꢋ  
ꢛꢉꢊ  
ꢝꢄ  
ꢃꢑꢞꢔꢍꢕꢎꢗꢦ ꢌꢧꢘꢕꢒꢥ  
ꢖꢑꢗ ꢨꢅꢩꢨꢪꢪ ꢎꢍꢫ  
ꢗꢔꢌꢔꢕ ꢧꢘꢕꢥ ꢘꢍꢕꢔꢟꢗꢎꢙ  
ꢌꢕꢎꢕꢬꢌ ꢘꢍꢫꢘꢒꢎꢕꢘꢑꢍ  
ꢝꢄ  
ꢝꢄ  
ꢋꢯ1  
ꢋꢯ1 ꢋꢯꢋ  
ꢭꢨꢄꢢ ꢳ  
ꢭꢨꢄꢢ ꢳ  
ꢘꢍꢌꢕꢎꢙꢙꢎꢕꢘꢑꢍ  
ꢎꢗꢔꢎ  
ꢑꢏꢔꢗꢎꢕꢘꢍꢟ  
ꢎꢗꢔꢎ  
1ꢐꢒꢥꢎꢍꢍꢔꢙ  
ꢋꢐꢒꢥꢎꢍꢍꢔꢙꢌ  
ꢌꢍꢎꢏꢐꢑꢍ ꢌꢑꢒꢓꢔꢕ ꢖꢑꢗ  
ꢗꢎꢘꢙ ꢁꢅ 6ꢚꢛ1ꢊꢐꢜꢊꢝꢛꢉꢊ  
Time/current characteristic (Tamb = +23 °C, UB = DC – 24 V)  
Preferred mounting postion REX12: horizontal  
1ꢀꢀꢀ  
1ꢀꢀ  
1ꢀ  
4
1
ꢀꢌ1  
ꢀꢌꢀ1  
ꢀꢌꢀꢀ1  
ꢀꢌꢏ  
1
1ꢌꢐ 1ꢌ4 1ꢌ6 1ꢌꢏ  
ꢐꢌꢐ ꢐꢌ4 ꢐꢌ6 ꢐꢌꢏ  
ꢓꢔ  
ꢌꢌꢌꢁꢃꢅꢆꢈ ꢂꢍꢁꢆꢋ ꢉꢎꢂꢂꢆꢇꢁ  
Temperature factor / continuous duty  
The time/current characteristic depends on the ambient temperature.  
In order to avoid premature trip, the rating of the circuit protector has  
to be multiplied with a temperature factor and has to be accounted  
for when mounted side-by-side (see chapter Technical Information).  
Temperature factor table:  
ambient temperature [°C]  
temperature factor  
0
1
10  
1
23  
1
40  
50  
60  
0,95  
0,90  
0,85  
Note: When mounted side-by-side, the devices can carry max. 80 %  
of their rated load or a different rating has to be selected (see chapter  
Technical Information).  
Note:  
With high temperatures, the load current warning threshold “warn limit  
typically 0.8 x IN” will be reduced in accordance with the temperature  
factor.  
1646  
www.e-t-a.de  
3
Electronic circuit protector REX12  
Description – EM12-T supply module  
Dimensions EM12-Txx supply module  
The EM12-T supply module receives the DC 24 V supply voltage, e.g.  
from a switched mode power supply, and distributes it to the mounted  
circuit protectors via the integral connector arm of the REX12-T.  
The potential-free auxiliary contact in the EM12-T indicates  
any detected failures through the circuit protector, e.g. to the  
superordinate control unit (CPU).  
ꢀꢁ  
ꢀ1ꢂꢃ  
1ꢣꢂ4  
ꢒꢤ1ꢣꢈ  
ꢥꢔ1ꢈꢔꢔ1  
ꢦꢟꢣ4ꢧ  
4ꢔ ꢨ  
Technical data (T  
= +23 °C, U = DC 24 V)  
B
amb  
Operating voltage UB  
Operating current IB  
DC 24 V (18...30 V)  
max. 40 A  
1ꢖ 14  
Reverse polarity protection yes  
Quiescent current I0  
typically 10 mA  
ꢩꢧ  
Potential-free auxiliary  
change-over contact  
max. DC 30 V / 0.5 A  
min. 10 V / 1 mA  
Group signalling Si  
Contact: Si (13) / Si (14)  
auxiliary contact, make contact  
ꢘꢪꢓꢒ ꢫ1  
ꢄꢅꢆꢇꢈꢉꢅ ꢄꢉꢊꢋꢌꢍ ꢎꢉꢏ  
ꢏꢆꢐꢑ ꢒꢓ 6ꢔꢕ1ꢃꢈꢖꢃꢗꢕꢂꢃ  
normal condition:  
auxiliary contact closed  
- when ON, load output connected  
- when OFF, load output disconnected  
ꢘꢆꢙꢌꢑ ꢌꢚꢛꢚ ꢎꢏꢉꢜ  
ꢝꢞꢉꢌꢅꢐꢗ ꢟꢉꢅꢍꢆꢊꢍ ꢠꢡꢢꢈ1ꢣ  
fault condition:  
auxiliary contact open  
- after an overload or short circuit  
disconnection  
- after undervoltage release of operating  
voltage in ON condition with autoreset  
- at no operating voltage UB in supply  
module  
Schematic diagram EM12-Txx with REX12-xx  
ꢎꢏꢐꢑ 16 ꢒꢓꢔ  
Insulation co-ordination 0.5 kV / pollution degree 2  
Power failure  
ꢊꢋ1ꢅꢌꢍ  
ꢕꢊꢖ1ꢅꢌꢍ  
14  
1ꢙ  
buffering time  
up to 10 ms  
Screw terminals  
LINE+  
Push-in terminal PT 10  
Stripping length  
0.5 mm2...10 mm2, flexible  
18 mm...10 mm  
4
ꢗ ꢘ  
Screw terminals  
0 V / Si 13 / Si 14  
Push-in terminal PT 2.5  
Stripping length  
0.14 mm2...2.5 mm2, flexible  
8 mm...10 mm  
ꢀꢈꢉꢊꢄ1  
Dimensions (w x h x d)  
Mass  
12.5 x 98 x 80 mm  
approx. 52 g  
ꢀꢁꢂꢃꢄ ꢅ1 ꢆꢅꢅꢇ  
Number of circuit  
protectors to be mounted  
side-by-side to EM12  
REX12-TA1-x or  
REX12-TA2-x  
max. 16 pcs  
Ordering number code – EM12  
Type  
EM12  
supply module for REX, with PT connection technology  
Mounting method  
T
rail mounting  
Version: communication, interface  
01 analog signal  
Additional functionality  
0 without  
Signal input:  
0 without signal input  
Signal output:  
1
signal make contact  
Operating voltage  
DC 24 V voltage rating DC 24 V  
Current ratings  
40 A  
EM12 -  
T
01 - 0  
0
1 - DC 24 V  
-
40 A  
ordering example  
4
www.e-t-a.de  
1646  
Electronic circuit protector REX12  
Application example: REX… mounting on or removing from symmetrical rail  
ꢀꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈ  
ꢄꢇꢂ ꢉꢃ ꢄꢊꢁꢋꢃꢌ  
ꢐꢃꢈꢁꢗꢃ ꢐꢑꢒꢝꢝꢝ ꢠꢆꢁꢈ ꢆꢇꢔꢊ  
ꢍꢎꢋꢏ ꢐꢑꢒ  
ꢅꢁꢓꢇꢆꢌꢋ ꢆꢇꢔꢊ  
ꢜꢁꢎꢂꢅ ꢐꢑꢒꢝꢝꢝ  
ꢋꢔꢌꢃꢞꢉꢟꢞꢋꢔꢌꢃ ꢓꢔꢅꢏ ꢑꢜꢝꢝꢝ  
ꢖꢂꢊꢇꢅꢄꢏ ꢓꢔꢅꢏ ꢋꢆꢃꢓꢌꢆꢔꢗꢃꢆꢘ  
ꢅꢔꢊꢅ ꢎꢙꢓꢇꢆꢌꢋ ꢇꢂꢌ ꢆꢃꢈꢁꢗꢃ  
ꢚꢄꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈ ꢄꢇꢂ ꢉꢃ ꢄꢊꢁꢋꢃꢌꢛ  
ꢕꢇꢅꢄꢏ ꢁꢂ ꢃꢂꢄꢊꢁꢋꢎꢆꢃ  
ꢌꢁꢓꢂꢓꢇꢆꢌꢋ  
Application example: REX... replacement or disassembly  
ꢒꢓꢋꢁ ꢅꢐꢁꢁꢋꢅꢄꢐꢊ  
ꢃꢊꢔ  
ꢒꢓꢋꢁ ꢅꢐꢁꢁꢋꢅꢄꢐꢊ  
ꢃꢊꢔ  
4
ꢎꢏꢂꢂ ꢐꢏꢄ ꢃꢄ ꢊꢈꢑꢆꢄ  
ꢃꢁꢑꢂꢋꢉ ꢄꢐ ꢄꢆꢋ ꢊꢃꢈꢂ  
ꢀꢁꢂꢃꢄꢅꢆ ꢇꢈꢄꢆ ꢉꢅꢊꢋꢇꢌꢊꢈꢍꢋꢊ  
Instructions for installation  
Mounting or actuation of the REX connector arm must only be effected  
at dead-voltage. For start-up the REX connector arm must be closed.  
1646  
www.e-t-a.de  
5
Electronic circuit protector REX12  
Application example: EM12-T with REX12-TA1… and REX12-TA2…  
Application example: REX... Locked connector arms  
Application example: REX12(D)-T... distance  
between cable duct and connector arm  
6ꢈ  
4
ꢀꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈꢉ ꢄꢇꢂ  
ꢊꢃ ꢋꢁꢄꢌꢃꢍ ꢎꢏꢅꢐ  
ꢃꢂꢄꢋꢁꢉꢑꢆꢃ  
All dimensions without tolerances are for reference only. E-T-A reserves the right change  
specifications at any time in the interest of improved design, performance and cost effective-  
ness, the right to make changes in these specifications without notice is reserved. Product  
markings may not be exactly as the ordering codes. Errors and omissions excepted.  
6
www.e-t-a.de  
1646  

相关型号:

REX12-TA2-107-DC24V-2A/2A

Combination of supply module and electronic circuit protector
ETAL

REX12-TA2-107-DC24V-4A/4A

Combination of supply module and electronic circuit protector
ETAL

REX12-TA2-107-DC24V-6A/6A

Combination of supply module and electronic circuit protector
ETAL

REX12D

Control, diagnosis and monitoring via IO link
ETAL

REX12D-TA1-100-DC24V-10A

Control, diagnosis and monitoring via IO link
ETAL

REX12D-TA1-100-DC24V-8A

Control, diagnosis and monitoring via IO link
ETAL

REX12D-TA2-100-DC24V-2A

Control, diagnosis and monitoring via IO link
ETAL

REX12D-TA2-100-DC24V-4A

Control, diagnosis and monitoring via IO link
ETAL

REX12D-TA2-100-DC24V-6A

Control, diagnosis and monitoring via IO link
ETAL

REYFA

VIDEO OVERSAMPLING SMD FILTERS
FARADAY

REYSA

VIDEO OVERSAMPLING SMD FILTERS
FARADAY

REZ

ECONOLINE - DC/DC CONVERTER
RECOM