Bus s m a nn  
®
Fus e tron®  
FRN-R  
7 0 -6 0 0 A  
Dua l-Ele m e nt, Tim e -De la y Fus e s  
Cla s s RK5 – 2 5 0 Volt  
Dim e ns iona l Da ta  
5.88"  
(± 0.062)  
1.06" (± 0.008)  
70A to 100A  
7.13"  
(± 0.062)  
1.56" (± 0.008)  
110A to 200A  
8.63"  
(± 0.094)  
2.06" (± 0.008)  
225A to 400A  
10.38"  
(± 0.094)  
2.59" (± 0.008)  
450A to 600A  
Ca ta log Sym bol: FRN-R  
Current-Limiting  
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%  
rated current  
Am pe re Ra ting: 70 to 600 Amperes  
Volta ge Ra ting: 250 Volts AC (or less)  
Inte rrupting Ra ting: 200,000A RMS Sym.  
DC Ratings: 20,000 AIC @ 125 VDC 70-400 Amperes  
20,000 AIC @250 VDC 401-600 Amperes  
Age nc y Approva ls :  
Ge ne ra l Inform a tion:  
• Provides motor overload, ground fault and short-circuit  
protection.  
• Helps protect motors against burnout from overloads and  
single phasing when sized properly.  
• Simplifies and improves blackout prevention (selective  
coordination).  
• Dual-element fuses can be applied in circuits subject to  
temporary motor overloads and surge currents to provide  
both high performance short-circuit and overload  
protection.  
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273  
CSA Certified, C22.2 No. 248.12, Class 1422-01, File 53787  
• The overload element provides protection against low level  
overcurrent of overloads and will hold on inrush current  
which is five times greater than the ampere rating of the  
fuse for a minimum of ten seconds.  
Ca ta log Num be rs  
FRN-R-70  
FRN-R-75  
FRN-R-80  
FRN-R-85  
FRN-R-90  
FRN-R-100  
FRN-R-110  
FRN-R-125  
FRN-R-150  
FRN-R-175  
FRN-R-200  
FRN-R-225  
FRN-R-250  
FRN-R-300  
FRN-R-350  
FRN-R-400  
FRN-R-450  
FRN-R-500  
FRN-R-600  
Fus e Re duc e rs For Cla s s R Fus e s  
Equipment  
Fuse Clips  
Desired Fuse  
(Case) Size  
Catalog Number  
(Pairs) 250V  
Ca rton Qua ntity a nd We ight  
Weight*  
200A  
100A  
100A  
200A  
100A  
200A  
400A  
No. 2621-R  
No. 2641-R  
No. 242-R  
Ampere  
Ratings  
Carton  
Qty.  
Lbs.  
1.5  
Kg.  
400A  
70–100  
5
1
1
1
0.680  
0.349  
0.689  
1.4  
101–200  
0.77  
1.52  
3.0  
No. 2661-R  
No. 2662-R  
No. 2664-R*  
201–400  
600A  
401–600  
*Single reducer only (pair not required).  
*Weight per carton.  
To obtain information for 0-60 Amps, access BIF # 1019  
CE logo denotes compliance with European Union Low Voltage Directive  
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact  
Bussmann Application Engineering at 636-527-1270 for more information.  
Form No. FRN-R 70-600  
Page 1 of 3  
11-1-00  
A00115  
BIF Doc #1020  
Bus s m a nn  
®
Fus e tron®  
FRN-R  
7 0 -6 0 0 A  
Dua l-Ele m e nt, Tim e -De la y Fus e s  
Cla s s RK5 – 2 5 0 Volt  
Fus e bloc ks for Cla s s R Fus e s  
(Clip Re ta ining Spring Sta nda rd, Suffix “R”)  
Terminal Type (Suffix No.)  
Tim e -Curre nt Cha ra c te ris tic Curve s Ave ra ge Me lt  
AMPERE  
RATING  
Basic  
Box Lug w/  
300  
100  
Catalog  
Number  
R25100-1  
Clip  
CU only  
COR  
Amps  
70  
Poles  
1
CR  
CR  
CR  
CR  
CR  
CR  
to  
2
3
1
1
1
R25100-2  
R25100-3  
R25200-1  
R25400-1  
R25600-1  
COR  
COR  
100  
to 200  
to 400  
to 600  
10  
1
.1  
.01  
CURRENT IN AMPERES  
Form No. FRN-R 70-600  
Page 2 of 3  
11-1-00  
A00115  
BIF Doc #1020  
®
Bu s s m a n n  
Fus e tron®  
FRN-R  
7 0 -6 0 0 A  
Dua l-Ele m e nt, Tim e -De la y Fus e s  
Cla s s RK5 – 2 5 0 Volt  
Curre nt-Lim ita tion Curve s  
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin  
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change  
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information  
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.  
Form No. FRN-R 70-600  
Page 3 of 3  
BIF Doc #1020  
11-1-00  
A00115  

相关型号:

FRN-R-60ID

Electric Fuse, Time Delay Blow, 60A, 250VAC, 125VDC, 200000A (IR), Inline/holder
COOPER

FRN-R-7

Electric Fuse, Time Delay Blow, 7A, 250VAC, 125VDC, 200000A (IR), Inline/holder
COOPER

FRN-R-7

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
EATON

FRN-R-7-1/2

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
COOPER

FRN-R-7-1/2

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
EATON
ETC
ETC
ETC

FRN-R-8

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
EATON

FRN-R-8*

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
COOPER

FRN-R-8/10

Electric Fuse, Time Delay Blow, 0.8A, 250VAC, 125VDC, 200000A (IR), Inline/holder
COOPER

FRN-R-8/10

Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses