Monitoring Relays
1-Phase True RMS AC/DC Over or Under Current
Types DIB01, PIB01
• TRMS AC/DC over or under current
monitoring relay
• Current measuring through internal shunt
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 mA to 10 A AC/DC
• Adjustable current on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DIB01) or plug-in module (PIB01)
• 22.5 mm Euronorm housing (DIB01)
DIB01
PIB01
or 36 mm plug-in module (PIB01)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
Product Description
DIB01 and PIB01 are precise can be used to avoid relay Housing
TRMS AC/DC over or under operation when not desired Function
current (selectable by DIP- (maintenance, transitions).
Ordering Key
DIB 01 C B23 5A
Type
switch) monitoring relays. The LED's indicate the state Item number
Direct measuring or through of the alarm and the output Output
current transformer.
relay. Through the built-in Power supply
Owing to the built-in latch shunt it is possible to moni- Measuring range
function, the ON-position of tor loads up to 10 A AC/DC.
the relay output can be
maintained. Inhibit function
Type Selection
Mounting
Output
Measuring range
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DIN-rail
SPDT
0.1 to 5 mA AC/DC
1 to 50 mA AC/DC
10 to 500 mA AC/DC
0.1 to 5 A AC/DC
1 to 10 A AC/DC
DIB 01 C 724 5mA
DIB 01 C 724 50mA
DIB 01 C 724 500mA
DIB 01 C 724 5A
DIB 01 C B48 5mA
DIB 01 C B48 50mA
DIB 01 C B48 500mA
DIB 01 C B48 5A
DIB 01 C B23 5mA
DIB 01 C B23 50mA
DIB 01 C B23 500mA
DIB 01 C B23 5A
DIB 01 C 724 10A
DIB 01 C B48 10A
DIB 01 C B23 10A
Plug-in
SPDT
0.1 to 5 mA AC/DC
1 to 50 mA AC/DC
10 to 500 mA AC/DC
0.1 to 5 A AC/DC
1 to 10 A AC/DC
PIB 01 C 724 5mA
PIB 01 C 724 50mA
PIB 01 C 724 500mA
PIB 01 C 724 5A
PIB 01 C B48 5mA
PIB 01 C B48 50mA
PIB 01 C B48 500mA
PIB 01 C B48 5A
PIB 01 C B23 5mA
PIB 01 C B23 50mA
PIB 01 C B23 500mA
PIB 01 C B23 5A
PIB 01 C 724 10A
PIB 01 C B48 10A
PIB 01 C B23 10A
Input Specifications
Input
Measuring ranges (cont.)
Current level
DIB01: Terminals Y1, Y2
PIB01: Terminals 5, 7
Internal resist.
Max. curr.
700 mA
700 mA
700 mA
1.4 A
..500MA: 10 to 100 mA AC/DC
20 to 200 mA AC/DC
0.5 Ω
0.5 Ω
0.5 Ω
Measuring ranges
50 to 500 mA AC/DC
Max. current for 1 s
Internal resist.
Max. curr.
..5MA: 0.1 to 1 mA AC/DC
0.2 to 2 mA AC/DC
50 Ω
50 Ω
50 Ω
50 mA
50 mA
50 mA
100 mA
..5A:
0.1 to 1 A AC/DC 0.05 Ω
0.2 to 2 A AC/DC 0.05 Ω
0.5 to 5 A AC/DC 0.05 Ω
Max. current for 1 s
6 A
6 A
6 A
15 A
0.5 to 5 mA AC/DC
Max. current for 1 s
..50MA: 1 to 10 mA AC/DC
2 to 20 mA AC/DC
5 Ω
5 Ω
5 Ω
150 mA
150 mA
150 mA
500 mA
..10A:
1 to 10 A AC/DC
Max. current for 1 s
3 mΩ
11 A
15 A
5 to 50 mA AC/DC
Max. current for 1 s
Specifications are subject to change without notice (21.10.00)
1
DIB01, PIB01
Input Specifications (cont.)
Output Specifications
Measuring ranges (cont.)
Output
Rated insulation voltage
SPDT relay
250 VAC
Standard CT (examples)
AACrms
Max. curr.
60 A
180 A
480 A
1200 A
7200 A
Contact ratings (AgSnO2)
µ
TADK2
TAD2
TAD6
TAD12
TACO200
50 A/5 A
5 to 50 A
Resistive loads
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
150 A/5 A
400 A/5 A
1000 A/5 A
6000 A/5 A
15 to 150 A
40 to 400 A
100 to 1000 A
600 to 6000 A
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Note:
The input voltage cannot
(at 8 A, 250 V, cos ϕ = 1)
raise over 300 VAC/DC with
respect to ground (PIB01 only)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Contact input
DIB01
PIB01
Disabled
Enabled
Dielectric voltage
≥ 2 kVAC (rms)
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
Rated impulse withstand volt. 4 kV (1.2/50 µs)
< 500 Ω
Latch disable
> 500 ms
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 100 ms
A1, A2 or A3, A2 (DIB01)
2, 10 or 11, 10
(PIB01)
724:
B48:
Alarm ON delay
Alarm OFF delay
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
< 100 ms
Accuracy
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
Temperature drift
Delay ON alarm
Repeatability
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
DC supply
2 kV
4 kV
AC supply
4 kV
4 kV
Indication for
Power supply ON
Alarm ON
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
4 kV
4 kV
Rated operational power
AC
DC
Output relay ON
4 VA
3 W
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
(EN 60529)
IP 20
3 (DIB01), 2 (PIB01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
Housing dimensions
DIn-rail version
Plug-in version
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Weight
Approx. 150 g
Screw terminals
Tightening torque
Max. 0.5 Nm
acc. to IEC 60947
CE-Marking
Yes
2
Specifications are subject to change without notice (21.10.00)
DIB01, PIB01
Mode of Operation
DIB01 and PIB01 monitor Example 1
Example 2 (Stardard CT)
Note
both AC and DC over or (connection between termi- (no connection between ter- When the inhibit contact is
under current through an nals Z1, Y1 or 8, 9 - latching minals Z1, Y1 or 8, 9 - latch opened, if the input signal is
internal shunt.
function enabled)
function disabled)
already in alarm position, the
delay time needs to elapse
The relay operates and latch- The relay operates when the before relay activation.
es in operating position measured value exceeds (or
when the measured value drops below) the set level for
exceeds (or drops below) the more than the set delay time.
set level for more than the It releases when the current
set delay time. Provided that drops below (or exceeds) the
the current has dropped set level (see hysteresis set-
below (or has exceeded) the ting) or when power supply
set point (see hysteresis set- is interrupted.
ting), the relay releases when
the interconnection between
terminals Z1, Y1 or 8, 9 is
interrupted or the power
supply is interrupted as well.
The red LED flashes until the
delay time has expired or the
measured value comes back
to a non-alarm value (see
hysteresis setting).
Function/Range/Level and Time Delay Setting
Selection of measuring range: Selection of function:
Selection of function:
DIP-switch selector (6)
Selection of level and time
delay:
DIP-switch selector (1 to 2)
DIP-switch selector (3 to 5)
..5MA
1 2
Input range:
0.1 - 1 mA
0.2 - 2 mA
0.5 - 5 mA
3
6
Upper knob:
ON
Relay de-energized in
normal condition.
Over current monitoring Setting of hysteresis on rela-
relay. The alarm condition tive scale: 0 to 30% on set
occurs when the current input value.
is over the set point value.
Relay energized in normal
condition.
..50MA
1 2
Centre knob:
Input range:
1 - 10 mA
2 - 20 mA
5 - 50 mA
Under current monitoring Current level setting on rela-
relay. The alarm condition tive scale: 10 to 110% on full
occurs when the current input scale.
is under the set point value.
ON
4
Power ON delay 6 ± 0.5 s
Lower knob:
..500MA
Power ON delay 1 ± 0.5 s
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
1 2
Input range:
10 - 100 mA
20 - 200 mA
50 - 500 mA
ON
5
Contact input as latch func-
tion enable. When the contact
is closed, the latch function is
activated. Reset of the latch
condition occurs when the con-
tact is open or by power down.
..5A
1 2
ON
Input range:
0.1 - 1 A
0.2 - 2 A
0.5 - 5 A
Contact input as inhibit of
alarm enable. When the con-
tact is closed the relay remains
in normal position even if the
alarm condition occurs.
Specifications are subject to change without notice (21.10.00)
3
DIB01, PIB01
Wiring Diagrams
Example 1
Example 1
24 VDC (+)
48/230 VAC 24/115 VAC
Latch/Inhibit 24 VDC (+)
enable
48/230 VAC 24/115 VAC
Latch/Inhibit
enable
L
L
µ
µ
9
8
2
11
4
3
Z1
A1
A3
16
18
I
I
PE
PE
Y1
7
5
10
1
Y2
A2
15
N (-)
N (-)
Example 2
Example 2
24 VDC (+)
48/230 VAC 24/115 VAC
24 VDC (+)
48/230 VAC 24/115 VAC
L
L
µ
µ
2
11
9
8
4
3
Z1
A1
A3
16
18
I
I
7
Y1
5
10
1
Y2
A2
15
N (-)
N (-)
PIB01
DIB01
Operation Diagrams
Over current
Under current - Latch function
Power supply
Power supply
Latch ON
Set Level
Hysteresis
Hysteresis
Set Level
1 or 6 s
Relay ON
1 or 6 s
Red LED ON
Relay ON
Red LED ON
Under current
Over current - Inhibit function
Power supply
Power supply
Inhibit ON
Hysteresis
Set Level
Set Level
Hysteresis
1 or 6 s
Relay ON
1 or 6 s
Red LED ON
Relay ON
Red LED ON
4
Specifications are subject to change without notice (21.10.00)