BB-17F [GAMEWELL-FCI]

Four-Zone Fire Alarm Control Panel; 四区火灾报警控制面板
BB-17F
型号: BB-17F
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

Four-Zone Fire Alarm Control Panel
四区火灾报警控制面板

文件: 总2页 (文件大小:76K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Features  
Four Style B (Class B) Initiating Device Circuits  
(IDCs); two Style Y (Class B) Notification  
Appliance Circuits (NACs); optional module (P/  
N CAC-4) converts 4 IDCs and two NACs to  
Class A. 24 VDC.  
Flex 404  
Four-Zone Fire Alarm Control Panel  
NAC synchronization features:  
– Provides synchronization of standardANSI  
audible signals as required by NFPA 72  
(3-8.4.1.2.3).  
– Provides synchronization of ADAcompliant  
strobes per NFPA72 (4-4.4.1).  
Description  
The Gamewell Flex 404 Fire Alarm  
– Selectable for System Sensor, Cooper-  
Wheelock,& Gentex protocols.  
– Selective Silence feature allows manual  
silencing of horns while strobes continue to  
flash on the same NAC.  
Control Panel brings the latest in mi-  
croprocessor technology to conven-  
tional fire controls. The Flex 404 is  
compatible with the new i³  
smoke  
detectors from System Sensor, and  
provides advanced features including  
drift compensation, maintenance alert,  
and freeze warning. Automatic syn-  
chronization of audio/visual devices is  
provided, selectable for three manufac-  
turers’ protocols. The NAC protocol in-  
cludes the ability, using a single pair  
of wires, to silence audible devices  
Silent orAudible WalkTest operation mode  
commanded from the front keypad, with  
automatic return to normal after one hour of  
inactivity.  
Alarm verification selectable per zone.  
Each zone may be programmed for supervisory  
or fire; each zone has separate red and yellow  
LEDs.  
Disable switches provided for each zone.  
NACs programmable for: Silence Inhibit,Auto  
Silence, Strobe Synchronization, Selective  
Silence (horn/strobe mute), Temporal or  
Steady signal, Silenceable or Nonsilenceable.  
Form-CAlarm, Trouble, and Supervisory  
relays.  
3.0A(6.0Awith optional second transformer)  
total usable current.  
Piezo sounder for alarm, trouble, supervisory,  
and maintenance.  
Control buttons:ACK (Acknowledge),Alarm  
Silence, Reset, Walktest, Zone Enable/Disable  
(one per zone).  
LED indicators: FireAlarm (one per zone),  
Supervisory (one per zone), Trouble (one per  
zone), Maintenance (one per zone),AC  
Power, NAC Disable, Zone Disable, NAC  
Fault, System Trouble, Power Trouble,  
Walktest,Alarm Silence, Earth Fault (on circuit  
board), Battery Fault (on circuit board),  
Charger Fault (on circuit board).  
while strobes continue to flash.  
The Flex 404 is also compatible with conventional input devices such as two-  
and four-wire smoke detectors, pull stations, waterflow devices, tamper switches  
and other normally-open contact devices.  
Operation  
The activation of a compatible smoke detector or any normally-open fire alarm  
initiating device will: activate audible and visual signaling devices, illuminate an  
indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm  
relay, and operate an optional module which notifies a remote station or initiates  
an auxiliary control function.  
Technology Features  
• Drift compensation automatically adjusts detector sensitivity and increases  
resistance to false alarms caused by dust accumulation.  
• The maintenance alert LEDs (per zone) warn of excessive dirt accumulation,  
preventing false alarms.  
Optional dress panel (P/N DP-FLEX).  
Optional modules: plug-in transmitter module  
(P/N 4XTMF); plug-in zone relay module  
(P/N 4XZMF); transmitter module (P/N  
4XLMF) for SAN-404 remote LED annuncia-  
tor.  
• Detector sensitivity is automatically measured. The twice-yearly test require-  
ments of NFPA72 (7-3.2.1) are met without using a ladder or test meter.  
• The wireless handheld sensitivity meter eliminates the need for voltmeters,  
magnets, or a physical connection to the detector. The reader displays sensi-  
tivity in terms of percent-per-foot obscuration and provides text status indica-  
tion.  
Listings  
Listings and approvals below apply to the  
basic Flex 404 panel. In some cases, certain  
modules may not be listed by certain approval  
agencies, or listing may be in process.  
Consult factory for latest listing status.  
• The supervisory LED (per zone) provides a warning if a detector senses tem-  
peratures approaching freezing.  
UL Listed: file S521.  
CSFM approved: file 7165-1288:180.  
MEA approved: file 366-04-E.  
• Special test protocol and LED indication allow a quick test of all detectors —  
without a ladder.  
• Electronic heat-sensing element provides thermal detection in addition to pho-  
toelectronic smoke detection.  
Flex 404 Four-Zone FACP CS-2404 09/01/06  
Page 1 of 2  
Specifications  
AC power, TB8  
Backbox Mounting  
The cabinet can be surface-mounted. The door is removable during installation  
by opening and lifting it off the hinges. The cabinet mounts using two key slots at  
the top of the backbox and two additional 0.250" diameter holes at the bottom.  
120 VAC, 50/60 Hz, 2.3 A.  
Wire size: minimum 14 AWG (2.0 mm²) with  
600 V insulation.  
Battery (sealed lead-acid only), J8  
Maximum charging circuit: normal flat charge  
27.6 VDC @ 0.8 A.  
Ordering Information  
Maximum battery charger capacity:  
18 AH battery. Two 7 AH batteries can be  
housed in the FACPcabinet.Larger batteries  
require a separate battery box i.e. BB-17F.  
F404  
Four-zone conventional FACP.  
XRM-24  
120 VAC, 100 VA transformer, expands NAC power from 3.0  
to 5.0 Amps.  
Initiating device circuits, TB3  
CAC-4  
Class A converter module. Used to convert Style B (Class  
B) IDC to Style D (Class A) and Style Y (Class B) NAC to  
Style Z (Class A). The module connects to J1 on the Flex  
404 circuit board.  
Alarm zones 1 – 4. Power-limited circuitry.  
Operation: all zones Style B (Class B).  
Normal operating voltage: nominal 22 VDC.  
Alarm current: 15 mA minimum.  
Standby current: 4 mA.  
Short circuit current: 40 mA maximum.  
Maximum loop resistance: 100 ohms. End-  
of-line resistor: 4.7K ohm, 1/2 watt (P/N  
71252).  
4XTMF  
4XLMF  
4XZMF  
411UD  
Transmitter module.  
LED interface module, supports SAN-404.  
Zone relay module.  
Notification appliance circuits, TB2  
Four-input (channel) 411UD dual-line Digital Alarm Commu-  
nicator/Transmitters, which can be used as slave communi-  
cators with Flex 404.  
Two NACs on Flex 404. Power-limited  
circuitry.  
Normal operating voltage: nominal 24 VDC.  
Maximum signaling current: 2.5 Atotal with  
standard transformer; 5.0 Atotal (2.5  
maximum per NAC) with optional trans-  
former.  
PRO-411  
SAN-404  
Programmer used with 411UD.  
Remote annunciator (RZA-4XF), mounts in a single-gang  
box.  
End-of-line resistor: 4.7K ohm, 1/2 watt  
BB-17F  
Battery box, required to house two batteries greater than 7  
AH, to a maximum of 18 AH.  
(P/N 71252).  
Form-C relays  
DP-FLEX  
TR-1-R  
52194  
Dress panel.  
Trouble relay TB5 (fail-safe).Alarm relayTB6.  
Contact ratings: 2.0 A @ 30 VAC (resistive).  
Trim ring for semi-flush mounting.  
Flex 404 Installation and Maintenance Manual.  
Auxiliary outputs  
Resettable power, TB1  
Power-limiting circuitry.  
Operating voltage: nominal 24 VDC.  
Maximum available current: 500 mA,  
appropriate for powering four-wire smoke  
detectors. See note under nonresettable.  
i³™ is a trademark and Gamewell® is a registered trademark of Honeywell International Inc.  
Nonresettable power, TB1  
Power-limiting circuitry.  
Operating voltage: nominal 24 VDC.  
Maximum available current: 500 mA,  
appropriate for powering four-wire smoke  
detectors. Note:Total current for nonre-settable  
power, resettable power and two NACs must  
not exceed 6Afor the Flex 404.  
Cabinet dimensions  
Door: 15.342" (38.97 cm) high x 14.677"  
(37.28 cm) wide x 0.375" (0.95 cm) deep.  
Backbox: 15.0" (38.10 cm) high x 14.5"  
(36.83 cm) wide x 3.0" (7.62 cm) deep.  
Gamewell-FCI  
12 Clintonville Road  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
Specifications and wiring information are provided for information only and are  
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring  
instructions shipped with the product shall always be used for actual installation. For  
more information, contact Gamewell-FCI.  
www.gamewell-fci.com  
A Honeywell Company  
© 2006 Gamewell-FCI  
Page 2 of 2  
Flex 404 Four-Zone FACP CS-2404 09/01/06  

相关型号:

BB-183-10

Wire Terminal, 2mm2,
MOLEX

BB-183-10T

Wire Terminal, 2mm2,
MOLEX

BB-2

Dual action fire alarm station
GAMEWELL-FCI

BB-200.000MBE-T

OSC XO 200.000MHZ LVPECL SMD
ETC

BB-201-76HDX

Wire Terminal
MOLEX

BB-201-76HDXT

Wire Terminal
MOLEX

BB-207-04X

Wire Terminal, 2mm2,
MOLEX

BB-207-04XT

Wire Terminal, 2mm2,
MOLEX

BB-207-06X

InsulKrimp™ Spade Tongue Terminal for 14-16 AWG Wire
MOLEX

BB-207-06XT

Wire Terminal, 2mm2,
MOLEX

BB-213-04X

Wire Terminal, 2mm2,
MOLEX

BB-213-04XT

Wire Terminal, 2mm2,
MOLEX