Flex Series
GF505 and GF510
5 and 10 Zone Conventional
Fire Alarm Control Panels
Description
The Flex 505 is a five zone fire alarm control panel (FACP)
and the Flex 510 is a ten zone FACP. These combination
control and digital communicator panels provide reliable
fire signaling protection for medium sized commercial,
industrial and institutional buildings.
Initiating device circuits (IDCs) for Flex Series panels are
programmable and operate in Class B (Style B). Each
panel is compatible with conventional input devices such
as two-wire smoke detectors, four-wire smoke detectors,
pull stations, water flow devices, tamper switches and
other normally-open contact devices. This includes System
GF510
Sensor i3™ Series microprocessor-based detectors with
advanced features like drift compensation, maintenance
alert and freeze warning. (See the Gamewell-FCI Device
Compatibility Document, P/N 52195, for a listing of com-
patible devices).
Features
•
IBC Seismic Certified.
•
Class B (Style B) initiating device circuits (IDCs):
- Flex 505 - five programmable IDCs
- Flex 510 - ten programmable IDCs
Built-in digital alarm communicator/transmitter (DACT).
Four Class B (Style Y) notification appliance circuits
(NACs) programmable for the following:
- ADA compliant strobe synchronization
- Selective silence (horn/strobe mute)
- Temporal or steady signal
•
•
Outputs include four notification appliance circuits (NACs),
three programmable Form-C relays (factory pre-set for
Alarm, Trouble and Supervisory), and resettable and non
resettable power (24 VDC) for special applications. NACs
are power limited and operate in Class B (Style Y). The
FACP supervises wiring, AC voltage and battery level.
- Silenceable or non-silenceable
- Auto-silence and silence inhibit
Three programmable Form-C relays.
24 VDC special application power outputs (resettable
and non-resettable).
A variety of optional devices can be connected to the built-
in ANN-BUS 4-conductor communication circuit. These
include: remote annunciators, a printer interface module,
LED driver module, and relay module.
•
•
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and
visual signaling devices, illuminate an indicating LED, dis-
play message on LCD display, sound the piezo sounder at
the FACP, activate the FACP alarm relay and operate and
optional modules used to notify a remote station or initiate
an auxiliary control function.
•
•
•
Optional Class A converter module for NACs and IDCs
(model CAC-5X).
Optional transmitter module for municipal box service
and reverse polarity (model 4XTMF).
Completely field programmable at keypad
- does not require special software or extra equipment
- two password protected programming levels
80-character, backlit, high-angle, LCD display.
continued on next page
Both the Flex 505 and Flex 510 fire alarm control panel are
listed to UL® Standard 864, 9th Edition.
•
SIGNALING
FM
MEA
Reference Certificate
of Compliance
3™
i
is a trademark of Honeywell International Inc.
Approved
APPROVED
®
S1869
UL is a registered trademark of Underwriter’s Laboratories Inc.
7165-1703:0166
VMA-45894-02C
(Revision 1)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60293 Rev. C page 1 of 2
Options:
GFANN-80
Features (Continued)
Remote annunciator with 80 charac-
ter, backlit LCD which mimics the
FACP display. Also provides status
indicators for AC Power, Alarm, Trou-
ble, Supervisory and Alarm Silenced
conditions. Packed in its own enclosure.
•
Panel LED annunciating indicators (visible to public)
- Fire Alarm (red)
- AC Power (green)
- Supervisory (yellow)
- Trouble (yellow)
- Alarm Silenced (yellow)
GFANN-RLY
CAC-5X
Relay module provides 10 Form-C
relays. Mounts in FACP.
Class A conversion module used to
convert Class B (Style B) IDCs to
Class A (Style D) and Class B (Style
Y) NACs to Class A (Style Z). Mounts
in FACP. Two required for GF510.
Transmitter module provides output
for the local energy municipal box
transmitter and the alarm and trouble
reverse polarity. Mounts in FACP.
•
•
Local FACP piezo sounder differentiates Alarm,
Trouble, Maintenance, and Supervisory.
Membrane key panel (visible when panel door open):
- 25 keys, including a 16 alpha-numeric keypad.
- Function: ACK/STEP, SILENCE, DRILL, RESET.
- Service/programming: phone keys, cursor, enter, etc.
256 Event History Log.
24 volt operation with low AC voltage sense.
Automatic battery charger with supervision.
Built-in FLPS-7 power supply (7.0 A total current).
Silent or audible walk test capabilities.
Alarm verification and positive alarm sequence (PAS).
Piezo sounder for Alarm, Trouble, and Supervisory.
Built-in 4-conductor communication bus (ANN-BUS) to
connect remote annunciators, and printer, LED, and
relay modules.
4XTMF
•
•
•
•
•
•
•
•
Specifications
AC Power:
120 VAC, 60Hz, 3.8 A
Supervised, non power-limited
Max. charging circuit:
27.6 VDC@ 1.4A
Battery:
Max. Charger
Capacity:
26 Ah
(two 18 Ah batteries fit inside FACP)
Initiating Device: Alarm zones 1 - 5 (Flex 505/Flex 510)
•
Optional trim ring.
Circuits (IDC):
Alarm zones 6 - 10 (Flex 510 only)
All zones Class B (Style B)
Ordering Information
Supervised, Class 2 Power-Limited
circuitry
GF505
Flex 505 conventional FACP, 5 zones,
120 VAC, w/ FLPS-7 power supply, red
Operating Voltage: nominal 20 VDC
GF510
Flex 510 conventional FACP, 10 zones,
120 VAC, w/ FLPS-7 power supply, red
EOL resistor, 4.7K ohm, ½ watt
Alarm Current:
15 mA minimum
71252
53164
Short Circuit
Current:
40 mA maximum
GF505 & GF510 Series I/O Manual
Standby Current: 2 mA
Maximum Loop
Options:
Resistance:
100 ohms
Four NACs, Class B (Style Y)
Supervised, Class 2, Power-Limited
circuitry
GFANN-80
GFANN-80W
GFANN-LED
Remote annunciator, LCD, red
Remote annunciator, LCD, white
Notification:
Circuits (NAC):
LED annunciator module;
yellow and red LEDs
Relay module, 10 Form-C relays
Class A converter for IDCs & NACs
(2 for Flex 510)
Transmitter module for remote station
output or municipal box connection
Operating Voltage: nominal 24 VDC
GFANN-RLY
CAC-5X
Maximum
Signaling Current: 7.0 A (3.0 A maximum per NAC)
Maximum Wiring
Voltage Drop:
4XTMF
2 VDC
Form-C Relays:
Programmable (factory setting:
Trouble, Alarm, Supervisory)
TR-CE
Trim ring for semi-flush mount, red
ANN-SB80KIT-R Backbox kit, surface mount used with
Contact Ratings: 2 A @ 30 VDC (resistive)
ANN-80, red
0.5 A @ 30 VAC (resistive)
ANN-SB80KIT-W Backbox kit, angled for better viewing,
surface mount used with the N-ANN-80
(-W), white
Resettable
Operating Voltage: nominal 24 VDC
Power:
Maximum
Available Current: 500 mA
Non-Resettable
Class 2 Power-Limited circuitry
ANN-MBRLY
Optional mounting bracket (ANN-RLY)
Operating Voltage: nominal 24 VDC
Power:
Class 2 Power-Limited circuitry
Maximum
Available Current:
500 mA
Remote Sync:
Cabinet-Door:
Backbox:
24 VDC nominal, max. current: 40 mA
19.3" x 16.8" x 0.3" (49 x 43 x 1 cm)
19" x 16.6" x 5.2"(48 x 42 x13 cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60293 Rev. C page 2 of 2
www.gamewell-fci.com
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明