GFANN-80 [GAMEWELL-FCI]

5 and 10 Zone Conventional Fire Alarm Control Panels;
GFANN-80
型号: GFANN-80
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

5 and 10 Zone Conventional Fire Alarm Control Panels

文件: 总2页 (文件大小:61K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Flex Series  
GF505 and GF510  
5 and 10 Zone Conventional  
Fire Alarm Control Panels  
Description  
The Flex 505 is a five zone fire alarm control panel (FACP)  
and the Flex 510 is a ten zone FACP. These combination  
control and digital communicator panels provide reliable  
fire signaling protection for medium sized commercial,  
industrial and institutional buildings.  
Initiating device circuits (IDCs) for Flex Series panels are  
programmable and operate in Class B (Style B). Each  
panel is compatible with conventional input devices such  
as two-wire smoke detectors, four-wire smoke detectors,  
pull stations, water flow devices, tamper switches and  
other normally-open contact devices. This includes System  
GF510  
Sensor i3™ Series microprocessor-based detectors with  
advanced features like drift compensation, maintenance  
alert and freeze warning. (See the Gamewell-FCI Device  
Compatibility Document, P/N 52195, for a listing of com-  
patible devices).  
Features  
IBC Seismic Certified.  
Class B (Style B) initiating device circuits (IDCs):  
- Flex 505 - five programmable IDCs  
- Flex 510 - ten programmable IDCs  
Built-in digital alarm communicator/transmitter (DACT).  
Four Class B (Style Y) notification appliance circuits  
(NACs) programmable for the following:  
- ADA compliant strobe synchronization  
- Selective silence (horn/strobe mute)  
- Temporal or steady signal  
Outputs include four notification appliance circuits (NACs),  
three programmable Form-C relays (factory pre-set for  
Alarm, Trouble and Supervisory), and resettable and non  
resettable power (24 VDC) for special applications. NACs  
are power limited and operate in Class B (Style Y). The  
FACP supervises wiring, AC voltage and battery level.  
- Silenceable or non-silenceable  
- Auto-silence and silence inhibit  
Three programmable Form-C relays.  
24 VDC special application power outputs (resettable  
and non-resettable).  
A variety of optional devices can be connected to the built-  
in ANN-BUS 4-conductor communication circuit. These  
include: remote annunciators, a printer interface module,  
LED driver module, and relay module.  
Activation of a compatible smoke detector or any normally-  
open fire alarm initiating device will activate audible and  
visual signaling devices, illuminate an indicating LED, dis-  
play message on LCD display, sound the piezo sounder at  
the FACP, activate the FACP alarm relay and operate and  
optional modules used to notify a remote station or initiate  
an auxiliary control function.  
Optional Class A converter module for NACs and IDCs  
(model CAC-5X).  
Optional transmitter module for municipal box service  
and reverse polarity (model 4XTMF).  
Completely field programmable at keypad  
- does not require special software or extra equipment  
- two password protected programming levels  
80-character, backlit, high-angle, LCD display.  
continued on next page  
Both the Flex 505 and Flex 510 fire alarm control panel are  
listed to UL® Standard 864, 9th Edition.  
SIGNALING  
FM  
MEA  
Reference Certificate  
of Compliance  
3™  
i
is a trademark of Honeywell International Inc.  
Approved  
APPROVED  
®
S1869  
UL is a registered trademark of Underwriter’s Laboratories Inc.  
7165-1703:0166  
VMA-45894-02C  
(Revision 1)  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2013 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
9021-60293 Rev. C page 1 of 2  
Options:  
GFANN-80  
Features (Continued)  
Remote annunciator with 80 charac-  
ter, backlit LCD which mimics the  
FACP display. Also provides status  
indicators for AC Power, Alarm, Trou-  
ble, Supervisory and Alarm Silenced  
conditions. Packed in its own enclosure.  
Panel LED annunciating indicators (visible to public)  
- Fire Alarm (red)  
- AC Power (green)  
- Supervisory (yellow)  
- Trouble (yellow)  
- Alarm Silenced (yellow)  
GFANN-RLY  
CAC-5X  
Relay module provides 10 Form-C  
relays. Mounts in FACP.  
Class A conversion module used to  
convert Class B (Style B) IDCs to  
Class A (Style D) and Class B (Style  
Y) NACs to Class A (Style Z). Mounts  
in FACP. Two required for GF510.  
Transmitter module provides output  
for the local energy municipal box  
transmitter and the alarm and trouble  
reverse polarity. Mounts in FACP.  
Local FACP piezo sounder differentiates Alarm,  
Trouble, Maintenance, and Supervisory.  
Membrane key panel (visible when panel door open):  
- 25 keys, including a 16 alpha-numeric keypad.  
- Function: ACK/STEP, SILENCE, DRILL, RESET.  
- Service/programming: phone keys, cursor, enter, etc.  
256 Event History Log.  
24 volt operation with low AC voltage sense.  
Automatic battery charger with supervision.  
Built-in FLPS-7 power supply (7.0 A total current).  
Silent or audible walk test capabilities.  
Alarm verification and positive alarm sequence (PAS).  
Piezo sounder for Alarm, Trouble, and Supervisory.  
Built-in 4-conductor communication bus (ANN-BUS) to  
connect remote annunciators, and printer, LED, and  
relay modules.  
4XTMF  
Specifications  
AC Power:  
120 VAC, 60Hz, 3.8 A  
Supervised, non power-limited  
Max. charging circuit:  
27.6 VDC@ 1.4A  
Battery:  
Max. Charger  
Capacity:  
26 Ah  
(two 18 Ah batteries fit inside FACP)  
Initiating Device: Alarm zones 1 - 5 (Flex 505/Flex 510)  
Optional trim ring.  
Circuits (IDC):  
Alarm zones 6 - 10 (Flex 510 only)  
All zones Class B (Style B)  
Ordering Information  
Supervised, Class 2 Power-Limited  
circuitry  
GF505  
Flex 505 conventional FACP, 5 zones,  
120 VAC, w/ FLPS-7 power supply, red  
Operating Voltage: nominal 20 VDC  
GF510  
Flex 510 conventional FACP, 10 zones,  
120 VAC, w/ FLPS-7 power supply, red  
EOL resistor, 4.7K ohm, ½ watt  
Alarm Current:  
15 mA minimum  
71252  
53164  
Short Circuit  
Current:  
40 mA maximum  
GF505 & GF510 Series I/O Manual  
Standby Current: 2 mA  
Maximum Loop  
Options:  
Resistance:  
100 ohms  
Four NACs, Class B (Style Y)  
Supervised, Class 2, Power-Limited  
circuitry  
GFANN-80  
GFANN-80W  
GFANN-LED  
Remote annunciator, LCD, red  
Remote annunciator, LCD, white  
Notification:  
Circuits (NAC):  
LED annunciator module;  
yellow and red LEDs  
Relay module, 10 Form-C relays  
Class A converter for IDCs & NACs  
(2 for Flex 510)  
Transmitter module for remote station  
output or municipal box connection  
Operating Voltage: nominal 24 VDC  
GFANN-RLY  
CAC-5X  
Maximum  
Signaling Current: 7.0 A (3.0 A maximum per NAC)  
Maximum Wiring  
Voltage Drop:  
4XTMF  
2 VDC  
Form-C Relays:  
Programmable (factory setting:  
Trouble, Alarm, Supervisory)  
TR-CE  
Trim ring for semi-flush mount, red  
ANN-SB80KIT-R Backbox kit, surface mount used with  
Contact Ratings: 2 A @ 30 VDC (resistive)  
ANN-80, red  
0.5 A @ 30 VAC (resistive)  
ANN-SB80KIT-W Backbox kit, angled for better viewing,  
surface mount used with the N-ANN-80  
(-W), white  
Resettable  
Operating Voltage: nominal 24 VDC  
Power:  
Maximum  
Available Current: 500 mA  
Non-Resettable  
Class 2 Power-Limited circuitry  
ANN-MBRLY  
Optional mounting bracket (ANN-RLY)  
Operating Voltage: nominal 24 VDC  
Power:  
Class 2 Power-Limited circuitry  
Maximum  
Available Current:  
500 mA  
Remote Sync:  
Cabinet-Door:  
Backbox:  
24 VDC nominal, max. current: 40 mA  
19.3" x 16.8" x 0.3" (49 x 43 x 1 cm)  
19" x 16.6" x 5.2"(48 x 42 x13 cm)  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
9021-60293 Rev. C page 2 of 2  
www.gamewell-fci.com  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY