Three-Fold  
Fire Alarm Boxes  
and Transmitters  
Three-Fold Fire Alarm Boxes  
and Transmitters  
Description  
Gamewell-FCI coded fire alarm boxes and industrial trans-  
mitters provide large industries, institutions and communi-  
ties with the surest and safest means of prompt, effective  
fire alarm reporting. They are positive and bring help  
directly to the exact location from which the alarm was  
sent. They minimize human error in fire reporting. There is  
no confusion on the part of either sender or receiver; no  
hazardous, time-consuming confusion between streets,  
roads and avenues with the same or similar names.  
The three-fold fire alarm boxes and transmitters are  
designed for coded alarm reporting into a normally closed  
series metallic signaling circuit having a normal DC flow of  
0.100 amp. They transmit signals over this circuit in accor-  
dance with their respective code numbers.  
These three-fold assemblies are available in numerous  
variations which can be classified into three major catego-  
ries as follows:  
Three-Fold Fire Alarm Box  
Features  
Three-Fold Manual Fire Alarm Box  
Strictly manually operated by moving the pull guard forward  
which exposes the operating lever. Downward pressure on  
this lever actuates the code signal mechanism.  
Manual activation.  
Remote electrical activation.  
Manual or remote activation.  
Positive non-interfering movement.  
Automatic grounding.  
Three-Fold Master Fire Alarm Box  
Red or blue.  
Master fire alarm boxes have provisions for electrical actu-  
ation in addition to the manual operation. They are  
designed to provide the connecting link between a principal  
municipal or industrial fire alarm system and auxiliary type  
fire alarm systems installed for protection of public build-  
ings, schools, industrial plants etc. With such provisions,  
any alarm originating from heat detectors, smoke detec-  
tors, sprinkler heads, etc. are automatically transmitted  
through the Three-Fold Master Fire Alarm Box to the cen-  
tral headquarters.  
Local energy transmission.  
Surface or semi-flush mount.  
An ISO 9000-2000 Company  
SIGNALING  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
©2007 Honeywell International Inc. All rights reserved.  
Specifications are for information only, are not intended for installation pwurpwoswes,.ganadmareeswubejecllt-tofcchia.cngoemwithout notice. No responsibility is assumed by Gamewell-FCI for their use.  
CS-2261 Rev. A1 page 1 of 4  
sion of a fragment of a signal or stopping of the mechanism  
in a position which might hold the circuit open.  
Industrial Three-Fold Master Transmitter  
Master transmitters have provisions for electrical actuation  
but do not have any means for manual operation. They  
would be used when manual operation is not required such  
as an un-manned warehouse.  
If the main spring is run-down, the circuit will be grounded.  
Thus, by the testing means provided at headquarters, the  
location of the faulty box may be determined.  
Operation  
Manual Pull  
Three-Fold Features  
All fire alarm boxes and transmitters incorporate the  
unequaled Gamewell-FCI Three-Fold spring-driven move-  
ment. This movement operates on positive non-interfering,  
quick succession and also features the unique three-fold  
automatic grounding capability.  
The manual Three-Fold Boxes and Three-Fold Master  
Boxes are provided with means for manual actuation.  
These boxes are of the quick action type and require only  
the opening of the quick action pull down guard and the  
depressing of the lever to trip the mechanism. Once  
tripped, no further manipulation of the lever has any effect  
on the mechanism. When the box is operated in a normal  
metallic circuit, four (4) rounds of the box number will be  
transmitted to headquarters. If another box has control of  
the line, the box operated will wait until the line is clear and  
then transmit its signal to headquarters.  
The movement is designed so that should two (2) boxes on  
a normal line be operated simultaneously, one will be auto-  
matically selected to transmit a correct signal for four com-  
plete rounds. If a box is operated while another box is in  
operation, it will not interfere in any way with the transmis-  
sion of the signal of the first box. The second box will take  
control of the circuit and transmit its complete four (4)  
rounds of signal upon the beginning of its next round fol-  
lowing the completion of the signal of the first box. This  
operation, without loss of alarm or interference between  
simultaneously actuated movements, is possible because  
of the positive non-interference and quick succession fea-  
tures.  
Test Features  
In addition to transmitting emergency signals for fire alarm  
purposes, the fire box is equipped with a telegraph key so  
that authorized persons may transmit manually formulated  
code signals and receive audible indication, via tap bell, of  
the transmission of all code signals on the circuit.  
The test block is provided so that all functions of the box  
can be tested without the transmission of any signal over  
the circuit and without impairing the transmission over the  
circuit of signals from other sources. Means for cutting the  
box out of service or grounding either side of the circuit as  
required are also provided.  
The self-grounding mode of operation is accomplished  
automatically whenever a three-fold movement is actuated  
on a circuit which has developed an open. In this mode of  
operation, signals may be received from transmitters and  
boxes by properly conditioned receiving circuits at head-  
quarters.  
Frequently, the many advantages of the Three-Fold opera-  
tion are desired without all of the other features of a stan-  
dard Gamewell-FCI Fire Alarm Box. Accordingly, we offer  
the MODIFIED version of the standard units. It is basically  
the same as the popular Three-Fold Box which has had an  
excellent service record for decades. The difference is that  
the MODIFIED Three-Fold Boxes do not have the inner  
case, tap bell, telegraph key and test block.  
The Gamewell-FCI Three-Fold Boxes and Transmitters are  
capable of making approximately 26 attempts to command  
a circuit. If, at the end of that time an actuated unit is still  
unable to get a clear line, it will automatically “take over”  
(bulldog) the circuit to transmit four (4) rounds of its signal  
before it is wound down. The mechanism is capable of  
transmitting signals at varying rates of speed ranging from  
electrical impulses at 3.25 second intervals to .25 second  
intervals and has provisions for adjusting speeds within this  
range.  
Construction  
Signaling Mechanism  
When the main spring is run-down so there is insufficient  
capacity left for transmission of four (4) complete rounds of  
the signal, the mechanism is locked to prevent further  
operation until the spring is rewound, to prevent transmis-  
The signaling mechanism is carefully assembled with all  
parts precision-manufactured. All parts are plated or  
treated to resist rust and corrosion, and the mechanism is  
completely enclosed in a dust tight transparent plastic  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2261 Rev. A1 page 2 of 4  
www.gamewell-fci.com  
cover, fastened to the mechanism mounting panel of heavy  
duty molded plastic.  
arranged to perform this function if specifically designed to  
operate the local energy type Master Box.  
1. All wires shall be installed in accordance with the National Electrical Code.  
2. Auxiliary circuit wires must be installed in rigid conduit.  
Three-Fold Fire Alarm Boxes  
All of the working parts are mounted in an *inner case  
which is installed in the familiar “Signal Red” weatherproof  
cottage shell. Both the inner and outer cases are con-  
structed of aluminum, suitably treated and finished, the  
outer case is painted red and the inner case is white. A  
white guard panel is installed on the outer door to protect  
and highlight the starting lever. Both narrow sides of the  
box have a Scotchlite™ reflective “FIRE” sign that appears  
in red letters with a white background. The outer case is  
provided with a threaded 1/2”, (typical 2 places) conduit  
connection at the top and a clearance hole for 1/2”, (typical  
2 places) conduit at the bottom.  
LIGHTNING  
ARRESTER  
(IF USED)  
FIRE  
ALARM  
BOX  
1
2
3
4
5
6
7
8 10  
9
FOR CONNECTION DETAILS  
SEE SYSTEM DIAGRAM  
N/C  
COM  
N/O  
TO FIRE  
ALARM  
CIRCUIT  
IN SERIES  
CONNECT TO REMOTE  
SUPERVISORY PANEL  
(IF USED)  
Figure 1 Typical Wiring Connections - Gamewell-FCI Master Fire Alarm Box  
For Shunt Type Master Box  
*The inner case is not included with Modified Boxes.  
Scotchlite™ is a trademark of 3M™.  
1. Connect initiating devices in series with auxiliary circuit.  
Devices must be normally closed and must open on  
alarm.  
2. Auxiliary circuit loop resistance must not exceed  
30 ohms.  
Industrial Master Transmitter  
This transmitter utilizes the standard Three-Fold Mecha-  
nism and auxiliary tripping attachment mounted in a sheet  
metal enclosure with a locked, hinged door. The box code  
number plate is mounted on the outside of the door. The  
transmitter dimensions are: 12” high x 12” wide x 6” deep  
(30.48 H x 30.48 W x 15.2 D cm). This unit is designed for sur-  
face mounting.  
3. Supply voltage of the circuit in which the Master Box  
is connected should not be less than 30 volts.  
For Local Energy Type Master Box  
1. Auxiliary circuit normal operating (alarm) current should  
be.250 amperes DC or .380 ampere 60 Hz AC.  
2. Auxiliary circuit supervisory current should be not more  
than .050 ampere DC or .070 ampere 60 Hz AC.  
3. Nominal volts across coil = 3.65 VDC or 50 VAC 60 Hz.  
Use series resistor for higher voltages.  
4. Maximum safe current in trip coil 125% of nominal  
values given.  
5. Coil, wiring, and terminals insulated for 125 VAC  
(1250 VAC breakdown test).  
Installation Information  
Although the Gamewell-FCI Master Fire Alarm Box is  
designed for connection to auxiliary systems inside the  
buildings, the National Fire Protection Association recom-  
mends that the Master Box be placed outside of, but con-  
venient to, the building protected. Installation on a pole or  
wall nearby, preferable using a mounting bracket, reduces  
the fire hazard to the circuit wires of the main fire alarm  
system. It is recommended that the lead-in wires from the  
main circuit to the Master Box be placed underground, but  
if aerial wire construction is used, adequate lightning pro-  
tection should be provided at the Master Box. A Gamewell-  
FCI, GW 44551-01 lightning arrester is suitable for this pur-  
pose. Three (3) conductors, of #14 or #16 AWG wire, are  
recommended for connection between the Master Box and  
the Reset Supervisory Panel. This panel may be installed  
inside the building, preferably in some location where it will  
be visible a major portion of the time to certain of the build-  
ing personnel. This applies to the shunt trip type Master  
Box. Where the local energy type is used, requiring local  
power source for auxiliary operation, the supervisory panel  
may not be necessary as interior system control panels are  
Figure 2 Dimension Data for Master Boxes  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2261 Rev. A1 page 3 of 4  
www.gamewell-fci.com  
Ordering Information  
Ordering Information (Continued)  
Three-Fold Manual Boxes  
(For interior or exterior use)  
Part Number Description  
Accessories  
Part Number Description  
M34-52  
Surface mounting, cottage shell  
47375G  
Indicating light, plain red globe for pedestal  
mounting, 120 VAC. Order 40067 1/2"  
nipple separately.  
Master Box - Shunt Type  
M34-53  
Shunt Trip, surface mounting, cottage shell  
40067  
47374  
1/2" nipple for use with 47375G Light  
Plain red globe, pole or wall mounting,  
120 VAC  
M34-104  
Same as M34-53 with plain door painted  
red  
M34-71  
Shunt Trip, sheet metal housing, plain door  
(less test block, tap key and bell)  
28295  
28268  
28296  
28297  
27853  
28298  
EZYMOUNT cross brackets  
EZYMOUNT loose parts  
EZYMOUNT side brackets (2 required)  
Flexmount horizontal bracket  
Flexmount loose parts  
Local Energy Type  
M34-56  
M34-110  
M34-111  
M34-92  
Local Energy Trip, surface mount,  
cottage shell  
Same as M34-56 with plain door  
painted blue  
Same as M34-56 with plain door  
painted red  
Local energy trip, flush mounting,  
gasket cast frame for interior or exterior  
use.  
Flexmount vertical bracket  
M34-113  
M34-114  
M34-75  
Same as M34-92 with plain door  
painted blue  
Same as M34-92 with plain door  
painted red  
Local Energy Trip, surface mount cottage  
shell (less inner case test block, tap key  
and bell)  
M34-72  
Local Energy Trip Transmitter, sheet metal  
housing (less test block, tap key & bell)  
plain door.  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2261 Rev. A1 page 4 of 4  
www.gamewell-fci.com  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY