Intelligent Low-Flow Photoelectric
Duct Smoke Detectors
Features
• Air velocity rating from 100 to
4,000 feet per minute (0.5 to
20.32 m/sec.).
• Patented telescopic sampling
tube.
SS-PD
• Easily accessible code wheels
for addressing detector.
Description
The Gamewell SS-PD and SS-PDR
• Outside mounting tabs.
Intelligent Low-Flow Photoelectric
Smoke Duct Detectors provide low-
flow technology that enables duct
smoke detection throughout a broad
range of airflow environments in HVAC
applications. The low-flow technology
can detect smoke at air speed veloci-
ties of 100 feet per minute (0.5 m/sec.)
or greater, while continuing the same
reliable performance to 4,000 feet per
minute (20.32 m/sec.). The intelligent
low-flow duct detectors sample air cur-
rents passing through a duct and gives
dependable performance for shutdown
• Mounts to round or rectangular
ducts from 1’ to 12’ (0.3 to 3.7
meters) wide.
• Transparent cover for conve-
nient visual inspection.
SS-PDR
Listings
Listings and approvals below
apply to the SS-PD and SS-
PDR Intelligent Low-Flow
Photoelectric Duct Smoke
Detectors. In some cases,
certain modules may not be
listed by certain approval
agencies, or listing may be in
process. Consult factory for
of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke
an fire gases through the protected area.
The SS-PD and SS-PDR provide a remote alarm output for use with auxiliary
devices such as the RA400 remote LED annunciator, as well as remote test capa-
bility with the RTS451 or RTS451KEY Remote Test Stations.
The SS-PD is a photoelectric duct detector with SmartScanTM protocol. The SS-
latest listing status.
PDR additionally incorporates a relay.
• UL Listed: file S1115.
Applications
• CSFM approved:
file 3240-1288:167.
Duct smoke detectors have specific limitations, they are:
• NOT a substitute for open area smoke detectors.
• NOT a substitute for early warning detection.
• MEA approved: file 384-02-E
Vol. III.
• NOT a replacement for a building’s regular fire detection system.
Please call Gamewell for a copy of System Sensor’s application guide, Proper Use
of Smoke Detectors in Duct Applications, (A05-1004-00).
Installation
Wiring: For signal wiring (the wiring between detectors or from detectors to auxil-
iary devices), it is recommended that single conductor wire be no smaller than 18
AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up
to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48
cm) of conduit; solid conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for Signal-
ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring
requirements before wiring the detector loop. The SS-PD and SS-PDR detectors
are designed for ease of wiring; their housing provides a terminal strip with clamp-
ing plates.
LED Features: If programmed with the system control panel, two LEDs on each
duct smoke detector light to provide local visible indication.
Page 1 of 4
SS-PD and SS-PDR CS-2463 10/21/04
Programming
SS-PD: Current Requirements (using no accessories)
Specifications
specifications
requirements for
intelligent system
control panels:
The number of devices that can
have their LEDs programmed to
illuminate is limited by the fea-
tures of the panel and the indi-
vidual devices. The actual num-
ber of devices is determined by
the control panel and its
ability to supply LED cur-
rent. Refer to the control
panel installation manual
for details.
Power
24VAC, 120VAC, 220/240 VAC,
Supply
Voltage
Max.
Standby
Current
Max Alarm
Current
Alarm
30-30VDC
50/60 Hz 50/60 Hz
50/60 Hz
25 mA RMS
30 mA RMS
3 to 17 Sec.
2 Sec.
SS-PD
Operating voltage range
15 to 32 VDC.
Standby current
65 mA
RMS
44 mA
RMS
26 Ma
87 mA
182 mA
RMS
52 mA
RMS
300 µA @ 24 VDC (one communi-
cation every 5 seconds with LED
blink enabled).
Operating temperature range
32° to 131°F (0° to 55°C).
Relative Humidity range
10% to 93% (non-condensing).
Duct air velocity
100 to 4,000 feet/min (0.5 to 20.32
m/s).
Dimensions
14.750" (37 cm) length x 5.500" (14
cm) width x 2.750" (7 cm) deep.
3 to 17
Sec.
3 to 17
Sec.
3 to 17
Sec.
Response
Time
Power Up
Time
2 Sec.
2 Sec.
2 Sec.
SS-PDR: Relay Contact Ratings
10 Amp @ 30 VDC
Alarm
Auxiliary
Contacts *
(DPDT)
10 Amp @ 277 VAC (0.75 Pow er Factor)
240 VAC @ 249 VAC (0.4 Pow er Factor)
1/8 HP@ 120 VAC
1/4 HP@ 240 VAC
Options
Supervisory
Contact
2.0 Amp @ 30 VDC (resistive)
1. RTS-451, RTS-451KEY, RA400Z.
2. PA400 (Review installation instruc-
tions on power requirements).
(SPST)
Minimum sw itching current of 100 mA @ 5 VDC.
SS-PDR
Product Line
Information
Operating voltage range
20 to 30 VDC, 24 VAC/VDC, 120/
240 VAC auxiliary power (requires
a separate auxiliary source).
Model
Description
SS-PD
Duct detector housing with SmartScan™
Standby current
photoelectric smoke detector.
300 µA @ 24 VDC (one communi-
cation every 5 seconds with LED
blink enabled).
Operating temperature range
32° to 131°F (0° to 55°C).
Relative Humidity range
10% to 93% (non-condensing).
Duct air velocity
100 to 4,000 feet/min (0.5 to
20.32 m/s).
Dimensions
14.750" (37 cm) length x 5.500" (14
cm) width x 2.750" (7 cm) deep.
SS-PDR
Duct detector housing with SmartScan™
photoelectric smoke detector, DPDT relay.
A5053GM
A5067
Replacement photoelectric sensor board.
Replacement power board (without relay).
Replacement power board (with relay).
The RA400Z
A5060
ST-1.5
Metal sampling tube, duct widths 1' to 2'
(see table at left for metric lengths).
ST-3
Metal sampling tube, duct widths 2' to 4'.
Metal sampling tube, duct widths 4' to 8'.
Metal sampling tube, duct widths 8' to 12'.
Remote annunciator alarm LED.
ST-5
ST-10
RA400Z
RTS451
Options
Remote test station. Mounts in single-gang
box. Includes red alarm LED and magnet
test switch.
The RTS451
1. RTS-451, RTS-451KEY, RA400Z.
2. PA400 (Review installation instruc-
tions on power requirements).
RTS451KEY Key-activated remote test station.
F36-09-11
M02-04-00
S08-39-01
Replacement filters.
Replacement test magnet.
Replacement photo insect screen.
The RTS451KEY
Page 2 of 4
SS-PD and SS-PDR
CS-2463 10/21/04
Sample Wiring Diagrams
SS-PD Duct
Smoke Detector
using a UL Listed
control panel
On to other
Detectors on
the Loop
6821wir1.wmf
SS-PD Duct
6821wir2.wmf
Smoke Detector
with optional
RA400Z
SS-PD Detector
Terminals
SS-PD Detector Terminals
SS-PD Duct
Smoke Detector
with RTS451/
RTS451KEY
SS-PD
Please refer to manual
I56-1978-002R for
installation instructions.
NOTE: For RTS451,
Terminal 3 is not
used. RTS451 does
not have a Terminal
6.
SS-PDR
For RTS451KEY,
Terminals 3 and 6
are not used.
Please refer to manual
I56-1979-003R for
installation instructions.
Outside Duct Width
Inlet Tube*
Up to 2 feet (0.6096 m)
ST-1.5
ST-3
2 to 4 feet (0.6096 to 1.2192 m)
4 to 8 feet (1.2192 to 2.4384 m)
8 to 12 feet (2.4384 to 3.6576 m)
ST-5
ST-10
*NOTE: Inlet tube is required and must be purchased separately.
Order one inlet tube for each duct smoke detector ordered.
SS-PD and SS-PDR CS-2463 10/21/04
Page 3 of 4
The Gamewell Company
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell.
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
Page 4 of 4
SS-PD and SS-PDR CS-2463 10/21/04
SS-PDR 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
SS-P_1110 | OMRON | SS Series Compatible Mounting | 获取价格 | |
SS-T | GAMEWELL-FCI | Intelligent Addressable Plug-In Thermal (Heat) Detectors | 获取价格 | |
SS-TH | GAMEWELL-FCI | Intelligent Addressable Plug-In Thermal (Heat) Detectors | 获取价格 | |
SS-TR | GAMEWELL-FCI | Intelligent Addressable Plug-In Thermal (Heat) Detectors | 获取价格 | |
SS/SK1010 | HC | SMC | 获取价格 | |
SS/SK102 | HC | SMC | 获取价格 | |
SS/SK103 | HC | SMC | 获取价格 | |
SS/SK104 | HC | SMC | 获取价格 | |
SS/SK1045 | HC | SMC | 获取价格 | |
SS/SK106 | HC | SMC | 获取价格 |
SS-PDR 相关文章
- 2024-09-20
- 6
- 2024-09-20
- 9
- 2024-09-20
- 8
- 2024-09-20
- 6