Current Transducer HX 02..06-P
IPN = 2 .. 6 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primarynominal Primary current
Primary Conductor
Diameter x Turns
(mm)
Type
Features
r.m.s. current
measuring range
IPN (A)
IP (A)
· Galvanicisolationbetweenprimary
andsecondarycircuit
· Halleffectmeasuringprinciple
· Isolationvoltage 3000V
2
3
4
6
±6
±9
±12
±18
0.5d x 30T
0.6d x 20T
0.7d x 15T
1.0d x 10T
HX 02-P
HX 03-P
HX 04-P
HX 06-P
· Low power consumption
VOUT
ROUT
RL
VC
IC
Vd
Output voltage @ ± IPN, RL = 10 kW, TA = 25°C
Output impedance
Load resistance
Supply voltage (± 5 %)1)
Current consumption
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn > 3
R.m.s. voltage for partial discharge extinction
± 4
V
W
kW
V
mA
kV
· Extended measuring range(3x IPN
· Power supply from ±12V to ±15V
· Material according to UL94-V0
)
< 50
³ 10
± 15
< ± 15
Advantages
Ve
at 10pC
³ 1
³ 6
kV
kV
· Low insertion losses
· Easy to mount with automatic
handlingsystem
Impulse withstand voltage, 1.2/50µs
Accuracy-Dynamic performance data
· Small size and space saving
· Only one design for wide current
ratingsrange
· Highimmunitytoexternal
interference.
X
e
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error (0 .. ± IPN)
< ± 1 % of IPN
< ± 1 % of IPN
L
VOE
VOH
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 3 x IPN
< ± 40
mV
< ± 15
max. ± 1.5
± 0.1
mV
mV/K
%/K
µs
VOT
TCe
tr
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Applications
G
£ 3
· Switched Mode Power Supplies
(SMPS)
2)
f
Frequency bandwidth (-3 dB)
50
kHz
· ACvariablespeeddrives
· UninterruptiblePowerSupplies
(UPS)
· Electricalappliances
· Batterysuppliedapplications
· DC motor drives
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Min. internal creepage distance/clearance
Isolation material group
Standards
- 25 .. + 85 °C
- 25 .. + 85 °C
8
g
³ 5.5
m m
I
EN50178
ApplicationDomain
· Industrial
Notes : 1) Also operate at ±12V power supplies, measuring range reduced to ±2.5x IPN
2)
Small signal only to avoid excessive heating of the magnetic cores
Page 1/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
060920/1
www.lem.com
Dimensions HX 02..06-P (in mm. 1 mm = 0.0394 inch)
HX 02..06-P
Terminal Pin Identification
Max.
19
1 ..... -15 V
2 ..... 0 V
3 ..... +15 V
4 ..... Output
5 ..... Primary input Current (+)
6 ..... Primary input Current (-)
Primary conductor diameter
10.85
3
HX
d
02-P
0.5
03-P
0.6
04-P
0.7
06-P
1.0
d
6
5
4 OUT
3 +V
Secondary pins dimension
0.5 x 0.25
0
2
1
-V or 0
3
10.85
Top view
HX 02-P
41123
Lot No.
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/2