LTS15-NP [LEM]
Current Transducer; 电流传感器型号: | LTS15-NP |
厂家: | LEM |
描述: | Current Transducer |
文件: | 总3页 (文件大小:61K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
IPN = 15 At
Current Transducer LTS 15-NP
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electricaldata
Features
IPN
IP
Primary nominal r.m.s. current
Primary current, measuring range
15
0 .. ± 48
At
At
· Closed loop (compensated) multi-
range current transducer using the
Hall effect
ÎPDC
Overload capability
250
At
VOUT Analog output voltage @ IP
IP = 0
Number of secondary turns (± 0.1 %)
2.5 ± (0.625·IP/IPN)V
· Unipolar voltage supply
2.5 1)
2000
³ 2
V
· Compact design for PCB mounting
· Insulated plastic case recognized
according to UL 94-V0
· Incorporated measuring resistance
· Extended measuring range.
NS
RL
Load resistance
kW
W
ppm/K
V
R IM
Internal measuring resistance (± 0.5 %)
83.33
< 50
5
TCRIM Thermal drift of RIM
VC
IC
Supply voltage (± 5 %)
Current consumption @ VC = 5 V
Typ
28+IS2) +(VOUT/RL)mA
Advantages
· Excellent accuracy
Accuracy - Dynamic performance data
· Very good linearity
· Very low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
X
Accuracy @ IPN , TA = 25°C
Accuracy with R IM @ IPN , TA = 25°C
Linearity error
± 0.2
± 0.7
< 0.1
%
%
%
e
L
Typ Max
65
TCVOUT Thermal drift of VOUT @ IP = 0
- 10°C .. + 85°C
- 40°C .. - 10°C
- 40°C .. + 85°C
120 ppm/K
170 ppm/K
50 3)ppm/K
· Current overload capability.
TCe Thermal drift of the gain
G
VOM
Residual voltage@ IP = 0,after an overload of 3 x IPN
± 0.5
± 2.0
± 2.0
mV
mV
mV
Applications
5 x IPN
10 x IPN
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
tr a
tr
Reaction time @ 10 % of IPN
Response time @ 90 % of IPN
< 100
< 400
> 35
DC .. 100
DC .. 200
ns
ns
A/µs
kHz
kHz
di/dt di/dt accurately followed
f
Frequency bandwidth (0 .. - 0.5 dB)
(- 0.5 .. 1 dB)
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 40 .. + 85
- 40 .. + 100
10
EN 50178 : 1997
IEC 60950-1 : 2001
°C
°C
g
Applicationdomain
Standards
· Industrial.
1)
Notes :
Absolute value @ TA = 25°C, 2.475 < VOUT < 2.525
Please see the operation principle on the other side
Only due toTCRIM.
Copyrightprotected.
2)
3)
050713/15
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 1/3
LEM Components
www.lem.com
Tope Co., Ltd.
Tel: (02) 8228-0658
Fax: (02) 8228-0659
http://www.sensor.com.tw
e-mail: tope@ms1.hinet.net
Current Transducer LTS 15-NP
Isolationcharacteristics
Vd
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Impulse withstand voltage 1.2/50 µs
3
>8
kV
kV
V
w
Min
Ve
R.m.s. voltage for partial discharge extinction @ 10pC >1.5
kV
Min
4)
dCp
dCl
CTI
Creepage distance
Clearance distance
15.5
6.35
175
mm
mm
5)
Comparative Tracking Index (Group III a)
Applicationexamples
According to EN 50178 and IEC 61010-1 standardsand following conditions :
· Over voltage category OV 3
· Pollution degree PD2
· Non-uniform field
EN 50178
Rated isolation voltage
600 V
IEC 61010-1
Nominal voltage
600 V
V
dCp, dCI,
W
Single isolation
Reinforced isolation
300 V
300 V
4)
Notes :
On housing
On PCB with soldering pattern UTEC93-703.
5)
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
050713/15
Page 2/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Components
www.lem.com
Dimensions LTS 15-NP (in mm. 1 mm = 0.0394 inch)
Operation principle
Bottom view
Front view
Back view
Right view
Number
of primary
turns
Primary nominal
r.m.s. current
Nominal
output voltage
VOUT [ V ]
Primary
resistance
RP [ mW ]
Primary
insertion inductance
L P [ µH ]
Recommended
connections
IPN [ A ]
6
5
4
OUT
OUT
OUT
1
2
3
± 15
± 7.5
± 5
2.5 ± 0.625
2.5 ± 0.625
2.5 ± 0.625
0.18
0.81
1.62
0.013
0.05
0.12
IN
IN
IN
1
6
2
5
3
4
1
6
2
5
3
4
1
2
3
Mechanicalcharacteristics
Output Voltage - Primary Current
VOUT [V]
· General tolerance
± 0.2 mm
· Fastening & connection of primary
Recommended PCB hole
6 pins 0.8 x 0.8 mm
1.3 mm
5
4.5
· Fastening & connection of secondary 3 pins 0.5 x 0.35 mm
3.125
2.5
Recommended PCB hole
0.8 mm
· Additional primary through-hole
Æ 3.2 mm
1.875
Remarks
0.5
· VOUT is positive when IP flows from terminals 1, 2, 3 to
terminals 6, 5, 4.
· Temperature of the primary jumper should not exceed 100°C.
IP [At]
- IP
- IPN
0
IPN
IP
050713/15
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 3/3
LEM Components
www.lem.com
相关型号: