LV100-100 [LEM]

Voltage Transducer LV 100-100; 电压互感器低压100-100
LV100-100
型号: LV100-100
厂家: LEM    LEM
描述:

Voltage Transducer LV 100-100
电压互感器低压100-100

文件: 总2页 (文件大小:69K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Voltage Transducer LV 100-100  
VPN = 100 V  
For the electronic measurement of voltages : DC, AC, pulsed...,  
with a galvanic isolation between the primary circuit (high voltage)  
and the secondary circuit (electronic circuit).  
Electrical data  
VPN  
VP  
IPN  
Primary nominal r.m.s. voltage  
Primary voltage, measuring range  
Primary nominal r.m.s. current  
Measuring resistance  
100  
0 .. ± 150  
100  
V
V
mA  
Features  
· Closed loop (compensated) voltage  
transducer using the Hall effect  
· Insulated plastic case recognized  
according to UL 94-V0  
· Primary resistor R 1 incorporated into  
the housing.  
RM  
RM min  
RMmax  
with ± 15 V  
@ ± 100 V max  
@ ± 150 V max  
0
0
170  
90  
W
W
ISN  
KN  
VC  
IC  
Secondary nominal r.m.s. current  
Conversion ratio  
Supply voltage (± 5 %)  
Current consumption  
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn  
50  
mA  
100 V / 50 mA  
± 15  
10 + IS  
6
V
mA  
kV  
Advantages  
Vd  
· Excellent accuracy  
· Very good linearity  
· Low thermal drift  
· High immunity to external  
interference.  
Accuracy - Dynamic performance data  
XG  
Overall Accuracy @ VPN , TA = 25°C  
Linearity  
± 0.7  
< 0.1  
%
%
e
L
Applications  
Typ  
Max  
± 0.2 mA  
± 0.2 ± 0.3 mA  
IO  
IOT  
Offset current @ IP = 0, TA = 25°C  
Thermal drift of IO  
· AC variable speed drives and servo  
motor drives  
0°C .. + 70°C  
tr  
Response time @ 90 % of VP max  
50  
µs  
· Static converters for DC motor drives  
· Battery supplied applications  
· Uninterruptible Power Supplies  
(UPS)  
General data  
· Power supplies for welding  
applications.  
TA  
TS  
N
Ambient operating temperature  
Ambient storage temperature  
Turns ratio  
0 .. + 70  
- 25 .. + 85  
1000 : 2000  
10  
1
60  
°C  
°C  
P
Total primary power loss  
Primary resistance @ TA = 25°C  
Secondary coil resistance @ TA = 70°C  
Mass  
W
kW  
W
R1  
RS  
m
850  
EN 50178  
g
1)  
Standards  
1)  
Note :  
A list of corresponding tests is available  
980709/1  
LEM Components  
www.lem.com  
Dimensions LV 100-100 (in mm. 1 mm = 0.0394 inch)  
Front view  
Left view  
Secondary terminals  
Terminal + : supply voltage + 15 V  
Terminal M : measure  
Terminal  
Terminal  
-
: supply voltage - 15 V  
: ground or earth  
Connection  
Top view  
Mechanical characteristics  
Remarks  
· General tolerance  
· Fastening  
· Connection of primary  
· Connection of secondary  
· Connection to the ground  
· Fastening torque  
± 0.3 mm  
· IS is positive when VP is applied on terminal +HT.  
· The primary circuit of the transducer must be linked to the  
connections where the voltage has to be measured.  
· This is a standard model. For different versions (supply  
voltages, turns ratios, unidirectional measurements...),  
please contact us.  
2 holes Æ 6.5 mm  
M5 threaded studs  
Faston 6.3 x 0.8 mm  
M5 threaded stud  
2.2 Nm or 1.62 Lb. -Ft.  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  

相关型号:

LV100-1000

Voltage Transducer LV 100-1000
LEM

LV100-1000_03

Voltage Transducer
LEM

LV100-100_03

Voltage Transducer
LEM

LV100-1200

Voltage Transducer LV 100-1200
LEM

LV100-1200_03

Voltage Transducer
LEM

LV100-150

Voltage Transducer LV 100-150
LEM

LV100-1500

Voltage Transducer LV 100-1500
LEM

LV100-1500_03

Voltage Transducer
LEM

LV100-150_03

Voltage Transducer
LEM

LV100-1600

Voltage Transducer LV 100-1600
LEM

LV100-1600_03

Voltage Transducer
LEM

LV100-200

Voltage Transducer LV 100-200
LEM