SE-330-20-11 [LITTELFUSE]
NGR MONITOR 48VDC NC CE/C-T;型号: | SE-330-20-11 |
厂家: | LITTELFUSE |
描述: | NGR MONITOR 48VDC NC CE/C-T 监视器 |
文件: | 总44页 (文件大小:2152K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Tel: (800) 832-3873
Email: relays@littelfuse.com
www.littelfuse.com/SE-330
SE-330 MANUAL
NEUTRAL-GROUNDING-RESISTOR MONITOR
REVISION 11-A-063018
Copyright © 2018 by Littelfuse
All rights reserved.
Document Number: PM-1200-EN
Page i
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
This page intentionally left blank.
Page ii
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
7 ORDERING INFORMATION.................................................. 34
8 WARRANTY .......................................................................... 35
TABLE OF CONTENTS
1 GENERAL............................................................................1
1.1 Modern Resistance-Grounded Systems.....................1
1.2 SE-330 NGR Monitoring.............................................1
1.3 NGR Short Detection..................................................2
9 TEST PROCEDURES............................................................ 35
9.1 Resistor-Fault Tests...................................................... 35
9.1.1 Calibration and Open Test......................................... 35
9.1.2 Voltage Test............................................................... 35
9.2 Sensing-Resistor Test................................................... 35
9.3 Analog-Output Test ...................................................... 36
9.4 Ground-Fault Performance Test.................................... 36
2 OPERATION........................................................................2
2.1 Settings......................................................................2
2.1.1 GF Trip Time ............................................................2
2.1.2 GF Trip Level............................................................2
2.1.3 VN Trip Level............................................................2
2.1.4 Pulse-Period Adjustment ........................................3
2.1.5 Configuration Settings............................................4
2.1.5.1 Relay K1 Function (S1).........................................4
2.1.5.2 Trip-Relay Mode and
APPENDIX A SE-330 REVISION HISTORY.......................... 37
LIST OF FIGURES
Trip-Memory Mode (S2)...................................................4
2.1.5.3 Ground-Fault-Trip Latch (S3)................................4
2.1.5.4 Resistor-Fault-Trip Latch (S4)...............................4
2.1.5.5 Sensing-Resistor Selection (S5) ..........................4
2.1.5.6 Frequency (S6) .....................................................4
2.1.5.7 Upgrade Mode (S8) .............................................4
2.1.6 Resistor-Fault Trip Time ..........................................4
2.1.7 Resistor-Fault Trip Level ........................................4
2.1.8 Geo-Magnetic Filter................................................4
2.2 Calibration .................................................................5
2.3 Pulsing Operation ......................................................5
2.4 Trip Indication and Reset...........................................5
2.5 Remote Operation......................................................5
2.6 Relay K1 LED..............................................................6
2.7 Unit Healthy Output...................................................6
2.8 Diagnostic LED...........................................................6
2.9 Enhanced Health Status ............................................6
2.10 Analog Output..........................................................6
1
2
3
4
5
6
7
8
9
Configuration switches......................................................... 4
Analog-output connections.................................................. 6
SE-330 connection diagram ................................................. 7
SE-330 outline and panel-mounting details......................... 8
SE-330 outline and surface-mounting details...................... 9
SE-IP65CVR-G weatherproof cover outline........................ 10
SE-IP65CVR-G weatherproof cover installation................. 11
ER-600VC sensing resistor................................................. 12
SE-MRE-600 moisture-resistant enclosure outline ........... 13
10 ER-600VC installed in SE-MRE-600 ................................... 14
11 ER-5KV sensing resistor..................................................... 15
12 ER-5WP sensing resistor.................................................... 16
13 ER-15KV sensing resistor................................................... 17
14 ER-25KV sensing resistor................................................... 18
15 ER-35KV sensing resistor................................................... 19
16 ELCT5-88 and ELCT30-88 ground-fault current sensors .... 21
17 ELCT5-31 and ELCT30-31 ground-fault current sensors .... 22
18 RK-332 remote indication and reset .................................. 23
19 PGA-0520 analog percent current meter ........................... 23
20 Simplified isolated-ground connection .............................. 24
21 Simplified pulsing connection............................................ 24
22 Ground-fault test circuits ................................................... 36
3 INSTALLATION ..................................................................6
3.1 SE-330........................................................................6
3.2 Sensing Resistor......................................................12
3.3 Ground-Fault CT.......................................................20
3.4 Isolated Ground Connection ....................................24
3.5 Pulsing Connection ..................................................24
LIST OF TABLES
4 DATA INTERFACES..........................................................25
4.1 SD Card....................................................................25
4.1.1 Datalogging ..........................................................25
4.1.2 Firmware Upgrade ................................................25
4.2 USB Interface...........................................................25
4.3 Network Communications .......................................26
1
2
3
Typical tripping system values............................................. 3
Ground-fault trip levels for selected CTs ............................. 3
Ground-fault-test record..................................................... 36
DISCLAIMER
5 TROUBLESHOOTING.......................................................27
Specifications are subject to change without notice. Littelfuse,
Inc. is not liable for contingent or consequential damages or for
expenses sustained as result of incorrect application, incorrect
adjustment, or malfunction.
6 TECHNICAL SPECIFICATIONS .......................................29
6.1 SE-330......................................................................29
6.2 Sensing Resistors ....................................................31
6.3 Current Sensors .......................................................32
Page iii
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
This page intentionally left blank.
Page 1
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
•
A transformer can provide the inductance necessary to cause
ferroresonance if the NGR opens.
1. GENERAL
1.1 Modern Resistance-Grounded Systems
Following these guidelines will reduce the flash hazard, reduce
point-of-fault damage, achieve reliable ground-fault protection, and
ensure a stable system not subject to ferroresonance.
A high-resistance-grounded system uses a neutral-grounding
resistor (NGR) with a low let-through current to limit the ground-
fault current. This is an improvement from low-resistance and
solidly grounded systems, which do not use NGRs and therefore
have a ground-fault flash hazard that can cause substantial point-
of-fault damage. High-resistance grounding eliminates these
problems. Modern ground-fault protection reliably operates at low
current levels. Furthermore, the probability of an arc-flash incident
is significantly reduced in high-resistance-grounded systems.
1.2 SE-330 NGR Monitoring
The SE-330 is a microprocessor-based NGR monitor that detects
NGR failures and ground faults in resistance-grounded systems and
is compliant with the 2018 CE Code. The SE-330 measures NGR
resistance, NGR current, and transformer or generator neutral-to-
ground voltage. The components required to monitor an NGR are
an SE-330, a 20- or 100-kΩ ER-series sensing resistor, and a current
transformer (CT).
NGR selection depends on system charging current and whether
the system is an alarm-only or a tripping system. Alarm-only
systems are usually restricted to system voltages up to 5 kV with
NGR let-through currents of 5 A or less. Occasionally, alarm-only
systems up to 15 kV and 10 A are used, however, these systems
are not common because a ground fault on such a system tends
to escalate to a phase-to-phase fault before the ground fault can
be located and cleared. Consult Canadian Electrical (CE) Code rule
10-302, National Electric Code (NEC)* 250.36, and NEC 250.186 for
application details.
Power-circuit elements (other than neutral-connected NGRs)
that purposefully connect the power system to ground are often
not compatible with SE-330 NGR monitoring. These elements
include single-phase grounding transformers, grounded-wye-
primary potential transformers, and grounded-wye-primary power
transformers.
The SE-330 continuously measures NGR resistance in an
unfaulted system. It will trip on resistor fault if the NGR resistance
varies from its calibrated value. When a ground fault occurs, voltage
is present on the neutral. NGR current will flow if the NGR is healthy.
The SE-330 will trip on ground fault if fault current exceeds the GF
TRIP LEVEL setting for an interval equal to the GF TRIP TIME setting.
However, if the NGR fails open during a ground fault, it is possible
for fault resistance to satisfy the NGR resistance measurement. To
detect this double-fault condition, the SE-330 measures neutral
voltage. If neutral voltage exceeds the VN TRIP LEVEL setting and if
NGR current is less than 5% of the CT rating, the SE-330 will trip on
resistor fault. If the resistor-fault circuit is tripped and the neutral
voltage exceeds the VN TRIP LEVEL setting for an interval greater
than the GF TRIP TIME setting, the ground-fault circuit will also trip.
System charging current is the capacitive current that flows
to ground when a bolted ground fault occurs. This current can
be calculated or measured. For small systems, the magnitude of
charging current may be conservatively estimated as ½ A per 1,000
kVA in low-voltage systems and 1 A per 1,000 kVA in medium-
voltage systems.
In an alarm-only system or in a tripping system without selective
coordination, use an NGR with a let-through current larger than the
system charging current. Set the pick-up current of ground-fault
devices at or below 50% of the NGR let-through current.
In a tripping system with selective coordination, use ground-fault
devices that have a definite-time characteristic to achieve time
coordination. Use the same pick-up current for all ground-fault
devices, which must be a larger value than the charging current
of the largest feeder. Select an NGR with a let-through current
between five and 10 times the pick-up current of the ground-fault
devices.
Ground-fault current is sensed by a CT with a 1- or 5-A secondary,
or by a CT (ELCT5-x or ELCT30-x) with a 50-mA secondary. The trip
level of the ground-fault circuit is adjustable from 2 to 100% of the
CT rating. The trip time is adjustable from 0.1 to 10.0 seconds.
The SE-330 has four output relays. With firmware version 3.00 or
higher, relays K1, K2, and K3 can be assigned to one of the following
functions (using SE-MON330 version 4.0 or higher):
Do not use a grounding transformer with a low-voltage resistor:
•
The combined cost of a transformer and a low-voltage resistor
is more than the cost of a resistor that is rated for line-to-
neutral voltage.
•
•
•
•
•
•
Ground Fault (GF);
Resistor Fault (RF);
Enhanced Health Status (HEALTH);
GF + RF;
•
•
•
A transformer saturated by a ground fault through a rectifier
can make ground-fault protection inoperative.
Transformer inrush current up to 12 times the rated current can
cause a voltage that is larger than expected.
GF + RF + HEALTH; or
DISABLED.
A parallel transformer winding makes it difficult to monitor
NGR continuity.
Page 2
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
In addition to the selected function, K1 is also assigned a trip or
pulsing function. When the pulsing function is selected, relay K1
is used to control a contactor to assist in locating faults. Relays
K1, K2, and K3 can be set to operate in the fail-safe or non-fail-
safe mode for undervoltage or shunt-trip applications. Relay K4 is a
solid-state relay that provides basic UNIT HEALTH indication.
is not detected. A trip will eventually occur when the time for fault
current above the trip level is greater than the time for fault current
below the trip level.
A non-accumulating mode can also be selected. In this mode, a
trip occurs if the fault current remains higher than the ground-fault
trip level for the duration of the ground-fault trip time.
Additional features include LED trip indication, trip memory,
front-panel and remote reset, 4-20-mA analog output, trip event
recorder, USB local communications, microSD* data logging, and
optional network communications.
2.1.2 GF Trip Level
The SE-330 uses a Discrete-Fourier Transform (DFT) algorithm to
measure the fundamental component of NGR current.
The SE-330 provides additional features over the SE-330 legacy
model (revision 04 or less):
Choose an NGR let-through current and a ground-fault trip
level using the guidelines in Section 1.1. Set the ground-fault
trip level between 2 and 100% of the CT-primary rating. When
the ground-fault trip level is set to MEM, the ground-fault setting
that is stored in non-volatile memory is used. This parameter
must be set using a PC running the SE-MON330 software and
connected to the USB interface. The setting range is 2 to 100%
of CT primary rating in 1% increments. The default value is 15%.
Inputs are provided for 5-, 1-, and 0.05-A secondary CTs. Typical
values for 5-, 15-, and 25-A tripping systems are shown in Table 1.
Ground-fault trip levels for the selected CTs are shown in Table 2.
For other systems, refer to the NGR Monitor Set-Point Assistant
at www.littelfuse.com/relayscontrols. The Set-Point Assistant is
included with the SE-MON330 software.
•
•
NGR short detection capability.
Configurable output relay function and operating mode (K1,
K2, and K3).
•
When the trip level is set to MEM, the ground-fault trip setting
is defined by an internal non-volatile memory variable. The
range is 2 to 100% in 1% increments of the CT-primary rating.
•
•
The number of trip records has been increased to 100 and
includes date and time stamping.
A microSD card interface can be used for short-term data
logging and firmware updates. A microSD card is included.
See Section 4.1.
•
•
•
For ease of connection to new devices, the RS-232 interface
has been replaced by a Mini-B USB port.
2.1.3 VN Trip Level
The SE-330 uses a DFT algorithm to measure the fundamental
component of neutral voltage (VN).
Dual Ethernet ports are available with support for fiber-optic
and RJ45 interfaces.
The SE-330 will trip and indicate a resistor fault if neutral voltage
is greater than the VN TRIP LEVEL setting for the duration of the
resistor-fault trip time, and ground-fault current is less than 5% of
the CT rating. If the resistor-fault circuit is tripped and the neutral
voltage exceeds the VN TRIP LEVEL setting for an interval greater
than the GF TRIP TIME setting then the ground-fault circuit will
also trip.
An added IEC61850 protocol.
1.3 NGR Short Detection (firmware version 3.00 and higher)
The SE-330 can be configured to monitor and trip if the NGR
resistance decreases to a value less than 10 to 70% of the Nominal
NGR Resistance value. The Nominal NGR Resistance, NGR Short
Trip Level, and several other values can be configured using SE-
MON330 (version 4.0 or higher). Refer to the SE-MON330 manual
for further details.
The VN TRIP LEVEL range is 20 to 2,000 V when switch S5 is in the
20-kΩ (Vx1) position, and the range is 100 to 10,000 V when switch
S5 is in the 100-kΩ (Vx5) position. Calculate the voltage across the
NGR when the NGR current is equal to the pick-up current of the
ground-fault circuit. Set the VN TRIP LEVEL to the next largest value.
See Fig. 1 and Section 2.1.5.5.
2. OPERATION
2.1 Settings
2.1.1 GF Trip Time
Typical values for 5- 15-, and 25-A tripping systems are shown
in Table 1. For an NGR resistance greater than 2 kΩ, use a 100-kΩ
sensing resistor. For other systems, refer to the NGR Monitor Set-
Point Assistant at www.littelfuse.com/relayscontrols.
GF TRIP TIME (definite time) is adjustable from 0.1 to 10.0
seconds. Time-coordinated ground-fault protection requires this
setting to be longer than the trip times of downstream ground-fault
devices.
NOTE: A resistor-fault trip is inhibited if the ground-fault current is
above 5% of the CT rating.
A trip-time accumulator provides a ground-fault memory function
for detection of intermittent faults. The accumulated time increases
when a ground fault is detected and decreases when a ground fault
Page 3
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
TABLE 1. Typical tripping system values
SYSTEM
VOLTAGE
NEUTRAL-GROUNDING
RESISTOR
GROUND-FAULT
SENSING RESISTOR
VN TRIP LEVEL
(VOLTS)
TRIP LEVEL
(LINE-TO-LINE)
RESISTANCE
CURRENT
RESISTANCE
(OHMS)
(VOLTS)
MODEL
(SWITCH S5
SETTING)
(AMPERES)
(AMPERES)
480
600
5
55
69
ER-600VC
ER-600VC
ER-5KV
20 kΩ
20 kΩ
20 kΩ
20 kΩ
20 kΩ
20 kΩ
20 kΩ
20 kΩ
100 kΩ
100 kΩ
20 kΩ
100 kΩ
100 kΩ
100 kΩ
100 kΩ
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
5.0
5.0
5.0
60
100
5
2,400
4,160
480
5
277
480
18
340
5
ER-5KV
800
15
15
15
15
15
15
25
25
25
25
25
ER-600VC
ER-600VC
ER-5KV
60
600
23
100
2,400
4,160
7,200
14,400
4,160
7,200
14,400
25,000
35,000
92
340
160
277
554
96
ER-5KV
800
ER-15KV
ER-15KV
ER-5KV
170x5 = 850
340x5 = 1,700
800
166
332
577
808
ER-15KV
ER-15KV
ER-25KV
ER-35KV
170x5 = 850
340x5 = 1,700
800x5 = 4,000
1,200x5 = 6,000
TABLE 2. Ground-fault trip levels for selected CTs
ELCT5-x
EFCT-x
ELCT30-x
50:1
50:5
(AMPERES)
100:1
100:5
(AMPERES)
200:1
200:5
(AMPERES)
400:1
400:5
(AMPERES)
GF TRIP
SE-CS30-x
30:0.05
LEVEL(%)(1)
5:0.05
(AMPERES)
(AMPERES)
2
4
0.10
0.20
0.30
0.40
0.50
1.00
2.00
3.00
4.00
5.00
0.60
1.20
*
*
*
*
*
*
*
16
6
1.80
*
*
12
16
20
40
80
120
160
200
24
8
2.40
*
8
36
10
20
40
60
80
100
3.00
5
10
20
40
60
80
100
40
6.00
10
20
30
40
50
80
12.00
18.00
24.00
30.00
160
240
320
400
(1) When set to MEM, range is 2 to 100% in 1% increments.
* Setting not recommended.
See Section 2.3 for detailed pulsing operation information.
2.1.4 Pulse-Period Adjustment
NOTE: For pulsing configuration, set switch S1 to K1 = PULSING
and install an external pulse-enable switch.
Pulse period is the cycle time of relay K1 when the SE-330 is
configured for pulsing operation. Pulse period is adjustable from 1.0
to 3.0 seconds with a fixed duty cycle of 50 percent. For example,
with the 1.0-s setting, relay K1 will be energized for 0.5 seconds
and de-energized for 0.5 seconds when pulsing is enabled.
Page 4
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
2.1.5 Configuration Settings
2.1.5.3 Ground-Fault-Trip Latch (S3)
Eight configuration switches (S1 to S8) and a calibration button
are located behind the access cover on the front panel. See Fig. 1.
Set switch S3 to select latching or non-latching ground-fault-
circuit operation. Non-latching operation overrides ground-fault-trip
memory. See Sections 2.1.5.2 and 2.4.
CALIBRATION BUTTON
2.1.5.4 Resistor-Fault-Trip Latch (S4)
Set switch S4 to select latching or non-latching resistor-fault-
circuit operation. Non-latching operation overrides resistor-fault-
trip memory. See Sections 2.1.5.2 and 2.4.
K1 =TRIP
K1 = PULSING
S1
S2
S3
S4
S5
S6
S7
S8
K1 NON-FAIL-SAFE
NON-LATCHING GF TRIP
K1 FAIL-SAFE
LATCHING GF TRIP
LATCHING RF TRIP
20 kΩ
2.1.5.5 Sensing-Resistor Selection (S5)
NON-LATCHING RF TRIP
100 kΩ
Set switch S5 to the resistance of the sensing resistor. For the
ER-600VC, ER-5KV, and ER-5WP, select 20 kΩ. For the ER-15KV, ER-
25KV, and ER-35KV, select 100 kΩ. Switch S5 sets the resistor-fault
trip value and the VN TRIP LEVEL range. See Section 2.1.3.
60 Hz
50 Hz
NOT USED
RUN
UPGRADE
2.1.5.6 Frequency (S6)
Set switch S6 to 50 or 60 Hz to tune the digital filter to the line
frequency of the monitored system.
NOTE:
1. DEFAULT SETTINGS SHOWN.
2.1.5.7 Upgrade Mode (S8)
FIG. 1. Configuration switches.
The microSD card is used for firmware upgrades. See Section
4.1.2 for upgrade instructions.
2.1.5.1 Relay K1 Function (S1)
NOTE: An upgrade causes an SE-330 restart and this may cycle the
output relays.
Set switch S1 to K1 = TRIP to assign the trip function to relay K1
and to activate switch S2. With the default setting, relay K1 will
change state when a resistor-fault or ground-fault trip occurs. Other
trip functions can be assigned to K1 using SE-MON330 software or
via network communications.
2.1.6 Resistor-Fault Trip Time
The resistor-fault trip time can be adjusted from from 12 seconds
(the default) to as much as 60 seconds using the SE-MON330
software or via network communications.
Set switch S1 to K1 = PULSING to configure relay K1 for pulsing
operation. See Section 2.3.
2.1.7 Resistor-Fault Trip Level
2.1.5.2 Trip-Relay Mode And Trip-Memory Mode (S2)
The resistor-fault trip level can be adjusted using the SE-MON330
software or via network communications. See Section 6.1.
Set switch S2 to select the operating mode of trip relay K1. In the
non-fail-safe mode, relay K1 energizes and its contact closes when
a trip occurs. The non-fail-safe mode can be used to trip shunt-trip
circuit breakers. In the non-fail-safe mode, SE-330 trips are reset
when supply voltage is cycled.
2.1.8 Geo-Magnetic Filter
A low-frequency ground current can be caused by the Earth’s
magnetic field and from charged clouds passing overhead during
a thunderstorm. In some conditions, this can cause a false resistor-
fault trip. Enabling the geo-magnetic filter and increasing the
resistor-fault trip time can help counteract these effects.
In the fail-safe mode, relay K1 energizes and its contact will
close if there are no trips. The contact will open in the event of a
trip, a loss of supply voltage, or a processor failure. In the fail-safe
mode, SE-330 trips are not reset when the supply voltage is cycled.
A trip time of 30 seconds is recommended when the
geo-magnetic filter is enabled.
NOTE: Switch S2 does not affect the operating modes of relays
K2, K3, and K4.
The geo-magnetic filter is disabled by default but can be enabled
using the SE-MON330 software or via network communications.
NOTE: Switch S2 only affects relay K1 operating mode when K1 is
assigned the trip function (switch S1 set to K1 = TRIP). Trip memory
is enabled when K1 is set to the fail-safe mode, regardless of the
switch S1 setting.
Page 5
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
2.2 Calibration
2.4 Trip Indication And Reset
The SE-330 measures the resistance change of the NGR
relative to the NGR-resistance value that was determined at the
time of calibration. When the resistance change is greater than
the threshold amount (500 Ω for 20-kΩ systems and 2,500 Ω for
100-kΩ systems), a resistor-fault trip will occur. The SE-330 should
be calibrated for new installations, or if the NGR or the sensing
resistor is changed.
Red LEDs and indication relays indicate ground-fault and
resistor-fault trips. The indication relays K2 (default is GF) and K3
(default is RF) operate in either fail-safe or non-fail-safe mode. The
default is non-fail-safe mode. In this mode, the relays are energized
when a fault occurs. The relay mode setting is stored in non-volatile
memory and can be set using the SE-MON330 software or network
communications.
NOTE: If the SE-330 is not calibrated and is supplied from the load
side of the breaker (non-fail-safe mode), calibrate it within the
resistor-fault trip time after power-up or it may trip and interrupt its
supply. See Section 2.1.6.
When a trip occurs with latching operation selected, the
SE-330 remains tripped until the unit is reset with the front-panel
RESET button or the remote-reset input. See Sections 2.1.5.3 and
2.1.5.4. Terminals 15 and 16 are provided for remote reset as
shown in Fig. 3. The reset circuit responds only to a momentary
closure so that a jammed or shorted button does not prevent a trip.
The front-panel RESET button is inoperative when terminal 15 is
connected to terminal 16. If non-latching operation is selected, trips
and corresponding indication will automatically reset when the
fault clears. In addition, the power-up trip memory will be ignored
even when configuration switch S2 is set to fail-safe. The maximum
automatic reset time is 2.8 s.
The CALIBRATION button is located behind the access cover on
the front panel, and is recessed to prevent inadvertent activation.
NOTE: Calibration must be performed with the SE-330 connected
to the sensing resistor and NGR of the installed system.
To calibrate the SE-330, press and hold the CALIBRATION
button until the green CALIBRATED LED turns off and then turns
on (if the LED is already off, press and hold down the button until
the LED turns on). Calibration takes approximately two seconds.
If calibration is not successful a resistor-fault trip occurs, the
RESISTOR FAULT TRIP LED will be on, the CALIBRATED LED will be
off, and the DIAGNOSTIC LED will flash the calibration-error code.
See Section 2.8.
The red DIAGNOSTIC LED annunciates latched calibration-error
and remote trips. See Section 2.8.
When supply voltage is applied with switch S2 set to
FAIL-SAFE, then the SE-330 returns to its state prior to loss of
supply voltage unless switch S3 or S4 is set to non-latching. SE-330
trips reset when the supply voltage is applied with switch S2 set to
NON-FAIL-SAFE. When a local, remote, or network reset is issued,
both trip LEDs will flash if they are off.
The SE-330 may be calibrated remotely using the SE-MON330
software with the USB interface or the communications options.
If the resistor fault (switch S4) is selected, the calibration-error
code flashes until RESET is pressed even if the CALIBRATED LED is
on.
Resistor-fault-trip reset can take up to one second.
Resistor-fault trip-memory trip can take up to three seconds once
the relay powers up.
The calibration value is stored in non-volatile memory.
2.5 Remote Operation
2.3 Pulsing Operation
Relays K2 and K3 can be used for remote indication, and terminals
15 and 16 are provided for remote reset. RK-332 Remote Indication
and Reset components are shown in Fig. 18. Connect them as
shown in Fig. 3. RK-332 components are not polarity sensitive.
If switch S1 is set to K1 = PULSING, pulsing occurs when terminal
16 is connected to terminal 17. Relay K1 operates at a 50% duty
cycle. The duration of each cycle can be adjusted from 1.0 to 3.0
seconds. When terminals 16 and 17 are not connected, K1 is not
energized and its contact is open.
Indication relays can be set to fail-safe or non-fail-safe operation
using the SE-MON330 software or network communications. The
default mode is non-fail-safe. In non-fail-safe mode, relays energize
on fault.
Relay K1 can be used to control a contactor that is rated for use
at the line-to-neutral voltage. The contactor causes changes in
neutral-to-ground resistance by adding or shorting portions of the
NGR. See Section 3.5. Pulsing ground-fault current appears as zero-
sequence current upstream from the fault.
Network-enabled SE-330s can be remotely tripped and reset by
the network master. The red DIAGNOSTIC LED indicates a network-
initiated trip. See Section 2.8. Refer to the appropriate SE-330
communications manual.
Pulsing ground-fault current is distinguishable from charging
current and noise, and it can be traced with a clip-on ammeter or
current probe. If a pulsing current is detected on a cable or conduit,
then the fault is downstream. Systematic testing allows faults to be
located without isolating feeders or interrupting loads.
Stop pulsing when a fault is located.
Page 6
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
2.6 Relay K1 LED
The yellow RELAY K1 LED follows the state of relay K1 and is on
when K1 is energized (contact closed).
2.7 Unit Healthy Output
The UNIT HEALTHY relay K4 provides a basic status of processor
health, which is energized when the processor is operating. It can
be ordered with N.O. or N.C. contacts. See section 7.
An ENHANCED HEALTH status can be assigned to relays K1, K2,
and K3. See Section 2.9.
UNIT HEALTHY relay K4 is energized when the processor is
operating. It can be ordered with N.O. or N.C. contacts. See Section 7.
NOTE: The K4 output changes state momentarily during a
processor reset.
FIG. 2. Analog-output connections.
3. INSTALLATION
3.1 SE-330
NOTE: K4-contact rating is 100 mA maximum.
2.8 Diagnostic LED
Outline and panel-cutout dimensions for the SE-330 are shown
in Fig. 4. To panel mount the SE-330, insert it through the panel
cutout and secure it with the fourincluded 8-32 locknuts and flat
washers.
The DIAGNOSTIC LED is used to annunciate trips without
individual LED indication. The number of short LED pulses between
pauses indicates the cause of the trip.
If an optional SE-IP65CVR-G hinged cover is used, follow the
included installation instructions. See Figs. 6 and 7.
By default, only critical diagnostic flash codes are shown. Non-
critical diagnostic codes include SD Card status and USB Error
status. All other diagnostic codes are considered critical.
All connections to the SE-330 are made with plug-in, wire-
clamping terminal blocks. Each plug-in terminal block can be secured
to the SE-330 by two captive screws for reliable connections.
Starting with SE-330 firmware version 2.60 and SE-MON330
software version 3.8, the SE-330 can be configured to show
only critical diagnostic codes. In this configuration, only critical
diagnostic codes will be indicated with the DIAGNOSTIC LED.
Diagnostic messages are always visible with the SE-MON330
software. See Sections 4.2 and 5.
Outline dimensions and mounting details for surface mounting
the SE-330 are shown in Fig. 5. Fasten the optional surface-mount
adapter to the mounting surface and make connections to the
adapter terminal blocks. Follow Fig. 5 instructions to mount or
remove the SE-330.
2.9 Enhanced Health Status
Ground terminal 7 (G) and connect terminal 6 (R) to the sensing-
resistor R terminal.
The Enhanced Health Status can be assigned to relays K1, K2,
and K3 (firmware version 3.00 and higher). The assigned relay(s)
will trip when a critical diagnostic code occurs. See Section 5 for a
list of critical diagnostic codes.
Use terminal 1 (L1) as the line terminal on ac systems, or the
positive terminal on dc systems. Use terminal 2 (L2/N) as the
neutral terminal on ac systems or the negative terminal on dc
systems. Connect terminal 3 ( ) to ground.
2.10 Analog Output
NOTE: Disconnect terminal 1 (L1) and terminal 2 (L2/N) before
performing dielectric strength testing of the control panel.
An isolated 4–20-mA output indicates NGR current with full-
scale output corresponding to the CT rating. An internal 24-VDC
supply allows the analog output to be connected as a self-powered
output. Power from an external supply is required for loop-powered
operation. See Fig. 2. A PGA-0520 analog meter can be panel-
mounted to display the NGR current. See Fig. 19 and Section 7.
NOTE: Connections to terminals 4 (SPG) and 5 (SPGA) are not
required when using the SE-330 hardware revision 10 and higher.
However, it is recommended to connect terminal 4 to terminal 5
to maintain backwards compatibility with the older SE-330 series
(hardware revision 04A and lower).
Page 7
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
TRANSFORMER
OR GENERATOR
NOTE 1
NEUTRAL
NOTE 16
NOTE 2
NOTE 12
NOTES 11 ꢁ 12
EFCT-ꢀꢁ
ELCTꢂ-ꢀꢁ
OR
C
XXX:1
OR XXX:5
ELCT30-ꢀ
NOTE ꢂ
N
ER SERIES
SENSING
RESISTOR
NOTE 1ꢄ
8
8
ꢀ
1
10 11
ꢀ
10 11
NGR
S
5
C
S
1
5
C
5 A
1 A
EFCT
NOTE 4
SE-330
G
R
6
ꢄ
R
ALTERNATE CT
CONNECTIONS
G
NOTE 5
N/- SUPPLY
L/ꢃ SUPPLY
NOTE 6
ꢅ1
1
2
L1
L2/N
NOTES:
1. USE SEPARATE LUG TO CONNECT
NOTE 1ꢂ ꢁ 14
22
2ꢂ
C
ꢅ2
GF
24
26
SENSING-RESISTORTERMINAL NTO NEUTRAL.
GROUND
FAULT
2. LOCATETHESE COMPONENTS NEAR
TRANSFORMER OR GENERATOR.
25
2ꢄ
ꢅꢂ
RF
2ꢀ
ꢂ. ALTERNATE SENSING-RESISTOR
TERMINAL-N CONNECTION.THE NEUTRAL
CONNECTION IS NOT MONITORED.
RESISTOR
FAULT
28
ꢅ4
12
14
1ꢂ
18
4. VOLTAGE BETWEEN SENSING-RESISTOR
TERMINALS R AND G IS LIMITEDTO 100 V BY
INTERNAL CLAMP.
UNIT HEALTHY
NOTE ꢄ
ꢃ24V
NO
NOTE 8
CONNECTION
1ꢀ
20
21
+
5. SEE SECTION ꢂ.4 FOR ISOLATED-GROUND
CONNECTION.
NOTE 14
ANALOG OUTPUT
15
-
REMOTE
RESET
NOTE 15
RESET
6. RELAY CONTACTS SHOWN WITH SE-ꢂꢂ0
DE-ENERGIꢆED.
16
1ꢄ
ꢂ
0V
PGA-0520
PULSE
ENABLE
PULSE ENABLE
ꢄ. OPTIONAL N.C. ꢅ4 AVAILABLE.
USB PORT
NOTE ꢀ
8. LOOP-POWERED CONNECTION USES
TERMINALS 1ꢀ AND 20 ONLY.
4
5
SPG
NOTE 18
SPGA
ꢀ. MINI-B USB DEVICE CONNECTOR.
MICRO SD
SLOT
OPTIONAL
NETWORꢅ COM
NOTE 10
SE-330
10. REFERTO APPROPRIATE SE-ꢂꢂ0
COMMUNICATIONS INTERFACE MANUAL.
11. TWO-CONDUCTORTWISTED CABLE
REꢇUIRED, SHIELDED RECOMMENDED.
INDICATION
GROUND-FAULT
TRIP
R
R
R
G
Y
G
12. CT CONNECTION IS NOT POLARITY-SENSITIVE.
RESIS-
TOR-FAULT TRIP
1ꢂ. CONNECT CONTACTS ꢅ1, ꢅ2, ꢅꢂ, AND ꢅ4
AS REꢇUIRED FOR PROTECTION,
INDICATION, AND CONTROL.
DIAGNOSTIC
CALIBRATED
RELAY ꢅ1
14. EXTERNAL LIGHTS AND SWITCHES NOT
INCLUDED WITH SE-ꢂꢂ0.
15. SELF-POWERED 4-20 mA OUTPUT.
16. TYPICALTRIPPING SYSTEM.
POWER
1ꢄ. GROUND CURRENT SENSOR ATTERMINAL 11
ONLY.
18. CONNECTION NOT REꢇUIRED. SEE SECTION ꢂ.1
FOR COMPATABILITY WITH OLDER SE-ꢂꢂ0
SERIES.
FIG. 3. SE-330 connection diagram.
Page 8
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
16.0
(0.6ꢁ)
1ꢁ2.0
(5.20)
ꢀ8.ꢁ
PANELTHICꢃNESS
1.6 (0.06)TO 4.8 (0.1ꢀ)
(ꢁ.8ꢂ)
LITTELFUSE STARTCO
NEUTRAL-GROUNDING-RESISTOR SE-330
MONITOR
GROUND
FAULT
RESISTOR
FAULT
12
K4
13
UNIT
HEALTHY
TRIP
DIAGNOSTIC
CALIBRATED
RELAꢌ ꢍꢁ
TRIP
NC - 14
-
-
-
-
-
15
RESET
16
1
L1
2
3
4
5
L2/N
PULSE ENABLE
17
24V - 18
-
SPG
+
SPGA
+
ANALOG OUTPUT
1 9
20
-
-
ꢄ0
ꢄ00
0V - 2 1
ꢁ0
ꢄ
ꢅ0
ꢁꢃ0
ꢁ30
ꢁ00
ꢇ0
ꢄ0
3ꢅ0
ꢆ00
ꢁꢄ00
ꢆ
ꢇ
ꢇ0
ꢆ0
ꢁ00
MEM
POWER
ATTENTION
ꢅ
ꢁꢃ00
ꢄ000
DISENGAGE CAPTIVE RETAINING
SCREWS BEFORE REMOVING
PLUG-IN TERMINAL BLOCKS
GF TRIP LEVEL
ꢈꢋ CT RATINGꢊ
V
N
TRIPΩ LEVELΩ
ꢄ0
ꢍ
ꢁ00 ꢍ
ꢊ
VN ꢎ ꢂ
ꢈ
Sꢂ
VN
ꢎ ꢁ
0ꢀꢃ
ꢄꢀ0
ꢄꢀꢄ
0ꢀꢂ
0ꢀꢅ
ꢁꢀ0
ꢄꢀ0
ꢁꢀꢆ
ꢁꢀꢇ
ꢁꢀꢅ
ꢁꢀꢄ
ꢁꢀ0
ꢄꢀꢅ
ꢄꢀꢇ
ꢄꢀꢆ
22
23
K1
0ꢀ3
0ꢀꢄ
0ꢀꢁ
3ꢀ0
ꢂꢀ0
ꢁ0ꢀ0
-
-
6
7
R
G
SENSING
RESISTOR
3ꢀ0
PULSE PERIODꢈꢉꢊ
GF TRIP TIME ꢈꢉꢊ
24
25
26
27
28
29
GROUND
FAULT
K2
-
8
S
1
-
-
-
E
F
C
T
9
RESISTOR
FAULT
K3
1
A
10
1 1
5
C
5
A
RESET
FRONT VIEW
SIDE VIEW
REAR VIEW
ꢀ2.ꢂ
(ꢁ.65)
ꢂ6.2
(ꢁ.00)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
8.2
(0.ꢁ2)
Rꢄ4.8 (0.1ꢀ)
MAXI
4.ꢂ5 (0.18ꢂ) DIA
4 LOCATIONS
PANEL-MOUNT CUTOUT
FIG. 4. SE-330 outline and panel-mounting details.
Page 9
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
114.ꢀ
(4.50)
8.0
(0.ꢀ1)
ꢁ8.ꢀ
(ꢀ.8ꢂ)
1ꢀ8.0
(5.4ꢀ)
RETAINER SCREW
RETAINER
LITTELFUSE STARTCO
NEUTRAL-GROUNDING-RESISTOR SE-330
MONITOR
GROUND
FAULT
RESISTOR
FAULT
12
UNIT
HEALTHY
K4
13
TRIP
DIAGNOSTIC
CALIBRATED
RELAꢌ ꢍꢁ
TRIP
14 - NC
15
-
-
-
-
-
L1
1
1
RESET
16
17
L2/N
2
3
4
5
2
3
4
5
PULSE ENABLE
18 - 24V
+
1 9
20
SPG
-
+
SPG A
ANALOG OUTPUT
-
-
ꢄ0
ꢄ00
2 1 - 0V
ꢁ0
ꢄ
ꢅ0
ꢁꢃ0
ꢁ30
ꢁ00
ꢇ0
ꢄ0
3ꢅ0
ꢆ00
ꢁꢄ00
ꢆ
ꢇ
ꢇ0
ꢆ0
ꢁ00
MEM
POWER
ꢅ
ꢁꢃ00
ꢄ000
GF TRIP LEVEL
ꢈꢋ CT RATINGꢊ
V
N
TRIPΩ LEVELΩ
ꢄ0
ꢍ
ꢎ
ꢁ00 ꢍ
ꢊ
VN ꢎ ꢂ
ꢈ
Sꢂ
V
N
ꢁ
0ꢀꢃ
ꢄꢀ0
ꢄꢀꢄ
0ꢀꢂ
0ꢀꢅ
ꢁꢀ0
ꢄꢀ0
ꢁꢀꢆ
ꢁꢀꢇ
ꢁꢀꢅ
ꢁꢀꢄ
ꢁꢀ0
ꢄꢀꢅ
ꢄꢀꢇ
ꢄꢀꢆ
22
23
K1
0ꢀ3
0ꢀꢄ
0ꢀꢁ
3ꢀ0
ꢂꢀ0
ꢁ0ꢀ0
-
R
6
7
6
7
SENSING
RESISTOR
-
G
3ꢀ0
PULSE PERIODꢈꢉꢊ
GF TRIP TIME ꢈꢉꢊ
24
25
26
27
28
29
GROUND
FAULT
K2
-
-
-
-
S
1
8
9
8
9
E
F
C
T
RESISTOR
FAULT
1
A
5
C
10
10
5
A
K3
RESET
1
1
1 1
FRONT VIEW
SE-ꢀꢀ0-SMA
FRONT VIEW
SIDE VIEW
6ꢀ.5
25.4
(2.50)
(1.00)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-ꢀ2 PANHEAD.
INSTALLATION
(NOTE 2)
1. LOOSEN RETAINER SCREWS, MOVE RETAINERS
OUTWARD AND TIGHTEN RETAINER SCREWS.
2. MATE MONITOR WITH ADAPTER PLUG-INTERMINALS.
LOOSEN RETAINER SCREWSTO LET RETAINERS
SNAP OVER MONITOR BACꢄPLATE.
ꢀ. ENSURETHAT RETAINERS ARE AGAINST MONITOR
BODY ANDTIGHTEN RETAINER SCREWS.
REMOVAL
1. LOOSEN RETAINER SCREWS, SLIDE RETAINERS AWAY
FROM MONITOR BODY ANDTIGHTEN RETAINER SCREWS.
BEꢃEL OUTLINE
2. PULL MONITOR FORWARD.
ADAPTER PANEL OUTLINE
MOUNTING DETAIL
FIG. 5. SE-330 outline and surface-mounting details.
Page 10
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
TO PREVENT UNAUTHORIꢃED ENTRY:
1. USE WIRE SEALTHROUGH HOLES IN
WEATHERPROOF COVER ASSEMBLY, OR
2. SECURE WITHTHE PLASTICTHREAD FORMING
SCREW SUPPLIED IN ꢄIT.
TOP VIEW
SHOWN
WITH
SEAL
HOLE FOR
SEAL WIRE
12ꢂ.0
(5.00)
FRONT VIEW
SIDE VIEW
NOTES:
1. DIMENSIONS SHOWN IN MILLIMETRES (INCHES).
2. SHOWN WITH WEATHERPROOF SNAPS CLOSED.
ꢀ. REFERTO PANEL MOUNTING CUTOUT (FIG. 4) FOR PANEL
MOUNTING DETAIL.
FIG. 6. SE-IP65CVR-G weatherproof cover outline.
Page 11
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
INSTALL O-RING INTO
GROOVE INTHE REAR
OF WEATHERPROOF
WINDOW
INSERTTHE SE-ꢀꢀ0 THROUGH OPENING
OF THE WEATHERPROOF WINDOW UNTIL IT
IS SECURELY NESTED TO THE BACꢁ OF THE
DARꢁ GREY PVC PANEL.
INSTALL O-RING INTOTHE GROOVE INTHE REAR
OF WEATHERPROOF WINDOW ASSEMBLY.
FRONT PANEL
DETAILS NOT SHOWN.
INSERT ASSEMBLY INTO PANEL AND FASTEN WITH
THE HARDWARE PROVIDED WITHTHE SE-ꢀꢀ0.
FIG. 7. SE-IP65CVR-G weatherproof cover installation.
Page 12
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
If a ground fault in the sensing-resistor conductor is unlikely
and it does not pass through the ground-fault-CT window, then
protection will be minimally lost. See Note 3 in Fig. 3.
3.2 Sensing Resistor
Outline and mounting details for the ER-600VC, ER-5KV, ER-
5WP, ER-15KV, ER-25KV, and ER-35KV sensing resistors are shown
in Figs. 8, 11, 12, 13, 14, and 15. Install the NGR and the sensing
resistor near the transformer or generator. When installed outdoors,
a sensing resistor must be installed in a suitable enclosure. An
optional SE-MRE-600 Moisture-Resistant Enclosure is available for
applications that may expose an ER-600VC to moisture. See Figs.
9 and 10. The weather-protected ER-5WP shown in Fig. 12 is an
ER-5KV with moisture-resistant terminal covers. Use an ER-5WP in
applications in which it might be exposed to moisture. The ER-15KV,
ER-25KV, and ER-35KV include moisture-resistant terminal covers.
Use suitable water-tight fittings. Ground sensing-resistor terminal
G. Pass the sensing-resistor-to-neutral conductor and the NGR-to-
neutral conductor through the ground-fault-CT window as shown
in Fig. 3. Separately connect sensing-resistor terminal N and the
NGR to the neutral to include neutral connections in the monitored
loop. Alternatively, if the NGR connection to system neutral does
not need to be monitored, connect terminal N to the NGR neutral
terminal.
NOTE: Voltage at terminal N rises to line-to-neutral voltage when
a ground fault occurs. The same clearances are required for sensing
resistors as for NGRs.
NOTE: A parallel ground path created by moisture can result in a
false resistor-fault trip. Moisture sources include wind-driven rain
or snow, and condensation. Sensing-resistor terminal R and its
connection to SE-330 terminal R, including interposing terminal
blocks, must remain dry.
NOTE: The neutral-to-sensing-resistor-terminal-N connection is
not a neutral conductor as defined in Canadian Electrical Code Rule
10-308 and National Electrical Code Section 250.36(B). It is not
required to be 8 AWG (8.36 mm2) or larger. Since current through
this conductor is always less than 250 mA, a 14 AWG (2.08 mm2)
conductor insulated to the system voltage is sufficient.
RATINGS:
MAXIMUM VOLTAGE
600 Vac
.
.
MAXIMUM CURRENT ꢀ0 mA
RESISTANCE
THERMAL:
20 ꢁΩ
. . . . . . .
600 Vac
6 MINUTES ON,
60 MINUTES OFF
CONTINUOUS
. . . . . . . . . .
41.5
40.0
(1.6ꢀ)
(1.5ꢂ)
420 Vac
. . . . . . . . . .
10.5
40.0
22.2
10.5
(0.41)
1ꢄ.0
(0.41)
(1.5ꢂ)
(0.8ꢂ)
(0.ꢂ5)
NOTE ꢀ
N
R
G
ER-600VC
SENSING RESISTOR
20 KΩ
600 VAC MAX
4.5 (0.18) DIA
CꢃBORE 10.0 (0.ꢀꢄ) DIA
ꢀ.2 (0.1ꢀ) DEEP
FRONT
SIDE
MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCꢅ SCREWS: 6-ꢀ2 ꢆ 0.25.
ꢀ. MOUNTING SCREWS: M4 OR 8-ꢀ2.
4. ON REVISION 2 UNITS ENCLOSURE IS ELECTRICALLY CONNECTEDTO
TERMINAL G THROUGH JUMPER FROMTERMINAL G TO SCREW.
THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH
TESTING. ENSURETHAT THE JUMPER IS INSTALLED AFTER TESTING.
5. ON REVISION 1 UNITS, SCREW IS NOT PRESENT AND ENCLOSURE IS
ELECTRICALLY CONNECTEDTOTERMINAL G.
6. NOT ALL CERTIFICATIONS SHOWN.
FIG. 8. ER-600VC sensing resistor.
Page 13
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
GASꢀET
120.4
(4.ꢁ4)
120.4
(4.ꢁ4)
ENCLOSURE - TOP VIEW
COVER - INSIDE VIEW
(COVER REMOVED)
ꢃ.5
82.5
(ꢂ.25)
(0.ꢂ8)
M6 OR 0.25-20
120.4
(4.ꢁ4)
ENCLOSURE - TOP VIEW
MOUNTING DETAIL
120.4
(4.ꢁ4)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M6 OR 0.25-20.
ENCLOSURE - SIDE VIEW
FIG. 9. SE-MRE-600 moisture-resistant enclosure outline.
Page 14
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
NOTE 2
MOUNTING
SCREWS
FOUR LOCATIONS
NOTE 4
N
R
G
NOTE ꢁ
ER-600VC
SENSING RESISTOR
20 KΩ
600 VAC MAX
NOTE 2
COVER - INSIDE VIEW
ENCLOSURE - TOP VIEW
(COVER REMOVED)
ASSEMBLY INSTRUCTIONS
1. DRILL HOLE FOR ENCLOSURE WIRE ENTRY. USE LIꢀUID-TIGHT FITTING.
2. REMOVE NYLON NUTS AND WASHERS. INSERT ER-600VC INTO ENCLOSURE. REPLACE NUTS AND WASHERS.
ꢁ. ATTACH GROUND WIRE FROM ENCLOSURETO COVER AND TO ER-600VC TERMINAL G.
4. MOUNT SE-MRE-600 IN PLACE USING M6 OR 0.25-20.
5. COMPLETE OTHER WIRING AND REPLACE COVER.
FIG. 10. ER-600VC installed in SE-MRE-600.
Page 15
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
RATINGS:
MAXIMUM VOLTAGE
2,500 Vac
.
.
MAXIMUM CURRENT 125 mA
RESISTANCE . . . . . . .
20 ꢀΩ
. . . . . . . . . . CONTINUOUS
THERMAL
TORꢈUE
TERMINAL N (ꢁ LOCATIONS)
10-ꢁ2 INSERT
(50 lbf•in.)
. . . . . 5.6 N-m (50 inlb)
OTHERS
. . . . . . . . . ꢃ.0 N-m ((880 ilnbfl•ibn).)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCꢅ SCREWS: 6-ꢁ2 ꢆ 0.25.
ꢁ. MOUNTING SCREWS: M6 OR 0.25-20.
4. THIS DEVICE CAN DISSIPATE
ꢁ00 WATTS.TO MINIMIꢇE SURFACE
TEMPERATURES FOR SYSTEMS
ALLOWEDTO OPERATE
CONTINUOUSLY WITH A GROUND
FAULT, MOUNT VERTICALLY WITH
R ꢄ GTERMINALS DOWN.
5. ON REVISION 2 UNITS BASE IS
ELECTRICALLY CONNECTEDTO
TERMINAL G THROUGH JUMPER
FROMTERMINAL G TO
SCREW.
THIS CONNECTION MAY BE
REMOVED FOR DIELECTRIC
STRENGTH TESTING. ENSURE
THAT THE JUMPER IS INSTALLED
AFTER TESTING.
6. ON REVISION 0 ꢄ 1 UNITS
IS NOT PRESENT AND BASE IS
ELECTRICALLY CONNECTED TO
TERMINAL G.
SCREW
ꢂ. CERTIFICATIONS NOT SHOWN.
FIG. 11. ER-5KV sensing resistor.
Page 16
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
RATINGS:
MAXIMUM VOLTAGE
2,500 Vac
.
.
MAXIMUM CURRENT 125 mA
RESISTANCE . . . . . . .
20 ꢈΩ
. . . . . . . . . . CONTINUOUS
THERMAL
TORꢅUE
TERMINAL N (ꢀ LOCATIONS)
10-ꢀ2 INSERT
(50 lbf•in.)
. . . . . 5.6 N-m (50 in-lb)
OTHERS
(80 lbf•in.)
. . . . . . . . . ꢂ.0 N-m (
MIN DISTANCE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCꢃ SCREWS: 6-ꢀ2 ꢄ 0.25
½ NPT
CABLE ACCESS OPENING IS 12 NPT.
USE A LIꢅUID-TIGHT FITTING FOR
CABLE ENTRY.
MIN CLEARANCE FROM BASE
ꢀ. MOUNTING SCREWS: M6 OR 0.25-20.
4. THIS DEVICE CAN DISSIPATE
ꢀ00 WATTS.TO MINIMIꢆE SURFACE
TEMPERATURES FOR SYSTEMS
ALLOWEDTO OPERATE
CONTINUOUSLY WITH A GROUND
FAULT, MOUNT VERTICALLY WITH
R ꢇ GTERMINALS DOWN.
5. BASE IS ELECTRICALLY CONNECTED
TOTERMINAL G THROUGH JUMPER
FROMTERMINAL GTO SCREW.
THIS CONNECTION MAY BE REMOVED FOR
DIELECTRIC STRENGTH TESTING.
ENSURETHATTHEJUMPERIS INSTALLED
AFTER TESTING.
6. CERTIFICATIONS NOT SHOWN.
FIG. 12. ER-5WP sensing resistor.
Page 17
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
FIG. 13. ER-15KV sensing resistor.
Page 18
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
RATINGS:
MMAAXIVOULMTAVGOEL. A. .G. .. ..14,400 Vac
14400 Vac
MAX CURRENT . . . . . . .144 mA
MAIUM CURRENT
RESISTANCE
THERMAL
144 m
100 ꢂΩ
. . . . . . .
. . . . . . . . . 11 MIINNUONE,
14,400 Vac
120 MIN
120 MINUT
OFF
CONTINUOUS
. . . . . . . . .
2,500 Vac
TORꢆUE
TERMINAL N
(80 lbf•in.)
. . . . . . .ꢃ.0 N-m (80 i-b)
NOTES:
1. DIMENSIONS IN
MILLIMETRES (INCHES).
2. TERMINAL-BLOCꢄ SCREWS:
6-ꢁ2 ꢅ 0.25.
ꢁ. MOUNTING SCREWS:
M6 OR 0.25-20
MIN CLEARANCE FROM BASE
4. USE LIꢆUID-TIGHT FITTING
FORTERMINAL-BLOCꢄ-
ENCLOSURE CABLE ENTRY.
MIN DISTANCE
5. MOUNT AS SHOWN
WITH BASE HORIꢇONTAL.
6. CERTIFICATIONS NOT SHOWN.
FIG. 14. ER-25KV sensing resistor.
Page 19
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
RATINGS:
MAX VOLTAGE . . . . . . . .2222,000000VVaac
MAIUM VOLAG
220 mA
MAX CURRENT . . . . . ... 220 mA
MXMUCURRN
. . . . . . .
RESISTANCE
THERMAL
100 ꢂΩ
1 MIN ON,
. . . . . . . . . 1 MINUTE ON,
22,000 Vac
120 MIN
1IE
OFF
CONTINUOUS
. . . . . . . . . .
ꢀ,000 Vac
TORꢆUE
TERMINAL N
. . . . . . . ꢁ.0 N-m ((8800 lnb-f•bin).)
MIN CLEARANCE FROM BASE
MIN DISTANCE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCꢄ SCREWS: 6-ꢀ2 ꢅ 0.25.
ꢀ. MOUNTING SCREWS: M6 OR 0.25-20.
4. USE LIꢆUID-TIGHT FITTING FOR
TERMINAL-BLOCꢄ-ENCLOSURE CABLE ENTRY.
5. MOUNT AS SHOWN WITH BASE HORIꢇONTAL.
6. CERTIFICATIONS NOT SHOWN.
FIG. 15. ER-35KV sensing resistor.
Page 20
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
3.3 Ground-Fault CT
Select and install a ground-fault CT that will provide the desired
trip level. Typically, the CT-primary rating should be approximately
equal to the NGR let-through-current rating. This provides an
appropriate GF TRIP LEVEL setting range and analog-output scaling.
See Sections 2.1.2 and 2.9.
The outline and mounting details for the ELCT5- and ELCT30-
series current sensors are shown in Fig. 16 and Fig. 17. Ground-
fault-CT connections and the typical ground-fault-CT location are
shown in Fig. 3.
For SE-325 replacement applications, the existing CT200
current sensor will typically have to be replaced. However, where
a replacement is not necessary or possible, the CT200 can be
connected to either the 1- or 5-A input. This CT has a 200:5 current
ratio. If connected to the 1-A input, the ground-fault trip level will
be a percentage of 40 A. See Section 2.1.2.
The accuracy of a typical current sensor, including the CT200, will
decrease when below 5% of its current rating. CT-primary current-
injection testing is recommended to verify trip levels below 5% of
the CT-primary rating. See Section 9.4. Littelfuse Startco current
sensors with a 50-mA-secondary rating, such as the ELCT5-x and
ELCT30-series, are designed for use at low levels and respond
linearly to 2% current rating.
NOTE: The current-sensor insulation class is of no consequence if
its secondary is grounded and the conductors through its window
are insulated for the system voltage. Medium-voltage systems may
require a bushing-type CT.
Page 21
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
137.69
[5.421]
87.73
[3.454]
115.59
[4.551]
TOPVIEW AND MOUNTING DETAIL
FRONTVIEW
7.62
[0.300]
NOTES:
1. DIMENSIONS IN MILLIMETERS [INCHES].
2. MOUNTING SCREWS: M6 OR 1/4”.
SIDEVIEW
FIG. 16. ELCT5-88 and ELCT30-88 ground-fault current sensors.
Page 22
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
72.64
[2.860]
31.56
[1.243]
55.97
[2.204)
TOPVIEW AND MOUNTING DETAIL
FRONTVIEW
7.62
[ 0.300]
NOTES:
1. DIMENSIONS IN MILLIMETERS [INCHES].
2. MOUNTING SCREWS: M5 OR #10.
SIDEVIEW
FIG. 17. ELCT5-31 and ELCT30-31 ground-fault current sensors.
Page 23
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
MILLIMETERS
FIG. 18. RK-332 remote indication and reset.
FIG. 19. PGA-0520 analog percent current meter.
Page 24
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
3.4 Isolated Ground Connection
An isolated ground bed can prevent a ground potential rise (GPR)
from being transferred to remote equipment. If the G terminals on
the sensing resistor and the SE-330 are connected to an isolated
ground, then the SE-330 will be exposed to the GPR. If the GPR
is greater than the terminal-block rating, then the SE-330 must be
isolated from station ground and precautions must be taken with
the power supply and the trip contacts. See Technical Note RG-1
“NGR Monitoring with Isolated Ground Beds” at
www.littelfuse.com/relayscontrols.
A configuration that allows an SE-330 to be connected to
station ground is shown in Fig. 20. The SE-330 monitors the
series combination of the NGR and the two ground beds. This
configuration is acceptable provided the series resistance of the
NGR and the ground beds is within the NGR calibration range
and groundbed-resistance changes remain within the trip range.
See Section 6.1.
FIG. 21. Simplified pulsing connection.
FIG. 20. Simplified isolated-ground connection.
3.5 Pulsing Connection
Set switch S1 to K1 = PULSING. Use an external switch to use
relay K1 to control a pulsing contactor (see Fig. 21). Relays K2 and
K3 can be used for tripping, and configured in the fail-safe or non-
fail-safe mode with the desired function using the SE-MON330
software.
Page 25
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
5. Set switch S8 back to RUN for normal operation. If a firmware
upgrade fails, then the existing firmware will not be overwritten.
4. DATA INTERFACES
4.1 SD Card
A record of the upgrade can be found in “upgrade_log_<SN>.txt”
on the microSD card. This file is updated each time an upgrade is
performed.
The SE-330 supports microSD data storage. The microSD card
port is located on the front panel just below the USB port. The
microSD card is used for short-term data logging of measured
values and for firmware upgrades.
NOTE: The maximum microSD card storage capacity is 32 GB for
SE-330 hardware revision 16 and higher. The maximum microSD
card storage capacity is 4 GB for SE-330 hardware revision 15 and
lower.
NOTE: SD card performance may vary by manufacturer, model,
and with varying environmental conditions. The included microSD
card has a temperature rating of -25 to 85°C (-13 to 140°F). For
applications colder than -25°C (-13°F), use an industrial-grade
microSD card.
4.2 USB Interface
Use the SE-MON330 software to access set-points, measured
values, and trip records through the Mini-B USB interface located
on the front panel. SE-MON330 version 4.0 or newer is required for
some set-points. The following information can be viewed:
NOTE: SD card usage is intended for use with the SE-330 only.
Do not store other data on the SD card because files may be
automatically deleted.
4.1.1 Datalogging
•
•
•
•
•
•
Front-panel and configuration-switch settings
Neutral voltage and neutral current
Resistance change from the calibrated value
Trip status
When a microSD card is installed, the SE-330 looks for a
directory called “Datalogging.” If this directory exists, data logging
will automatically start after the card is indexed (indexing may take
several minutes depending on the size of the card and the number
of files).
Trip records, 100 date and time stamped
Firmware version and serial number
The log is updated every two seconds and includes the measured
values, configuration parameters, and trip status. A new log file is
created at the start of each day. The most recent two months of log
files are retained.
The following values can be viewed and adjusted:
•
Ground-fault trip setting (when front-panel GF trip level is
set to MEM)
The red DIAGNOSTIC LED may indicate an SD Card error. See
Sections 2.8 and 5. Approximately 500 MB of data is generated per
month of logging.
•
•
•
•
•
•
•
•
•
•
•
K1, K2 and K3 relay assignement
K2 ground-fault relay output operating mode
K3 resistor-fault relay output operating mode
NGR Short Detection (multiple settings)
Clock settings
4.1.2 FIRMWARE UPGRADE
Firmware upgrades are performed using a microSD card in
conjunction with configuration switch S8. See Section 2.1.5.7. The
SE-Flash software is not required.
To upgrade the SE-330 firmware, insert a microSD card containing
the firmware upgrade file (.S19 format) in the root directory of the
SD card and set switch S8 to UPGRADE within 30 seconds of card
installation. If S8 is switched to UPGRADE after 30 seconds, the
upgrade process will not occur. If the microSD card is inserted after
S8 is switched to UPGRADE, switch S8 to RUN and then back to
UPGRADE. The SE-330 evaluates firmware upgrade files found in
the root directory of the microSD card and uses the first valid file.
Trip records can be cleared
Remote calibration
Resistor-fault trip time
Resistor-fault trip level
Geo-magnetic filter
Critical and non-critical diagnostic codes
Ensure that the DIAGNOSTIC LED is off before beginning the
firmware upgrade process.
Ensure the real-time clock is set to the correct time prior
to normal operation. Trip records and on-board datalogging
information include date and time readings from the clock. Refer to
the SE-MON330 software help file for further information.
The red DIAGNOSTIC LED blinks rapidly while the firmware
upgrade is running and the SE-330 may reset multiple times during
the upgrade process. Do not remove the SD card or power off the
SE-330 until the DIAGNOSTIC LED has stopped blinking rapidly
for at least 30 seconds. If the upgrade is not successful, then the
DIAGNOSTIC LED will indicate an SD upgrade error. See Section
Page 26
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
NOTE: SE-330 hardware revisions 10 and later include an internal
rechargeable battery that powers the real-time clock. Please
consult local regulations regarding the use of batteries in electrical
equipment. The SE-330 battery is not designed for user service or
removal; please contact Littelfuse with any questions regarding
battery removal.
4.3 Network Communications
The optional communications interfaces include a single CAN
port and dual Ethernet ports supporting cable, fiber(1), or both cable
and fiber. Protocols include:
•
•
•
•
DeviceNet over CAN (ordering option 1)
EtherNet/IP cable or fiber (ordering options 3, 4, and 5)
Modbus TCP over cable or fiber (ordering options 3, 4, and 5)
IEC 61850 over cable or fiber (ordering options 6, 7, and 8)
See Section 7 and refer to the appropriate SE-330 communications-
interface manual for details.
(1) Uses the plug-in style SC connector.
Page 27
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
5. TROUBLESHOOTING
PROBLEM
DIAGNOSTIC LED
SOLUTION
FLASH CODE(1)
POWER LED off.
Check if supply voltage is present in terminals 1 and 2. If present, an overvoltage
may have caused the power supply to shutdown. Cycle the supply voltage. If POW-
ER LED remains off, consult Littelfuse.
POWER LED flashes.
A power-supply overload has occurred. Cycle supply voltage. If problem persists,
consult Littelfuse.
Calibration-Error Trip
DIAGNOSTIC LED flash code
1 L - 1 S - 1 L
The total resistance of the NGR and sensing-resistor circuit is outside the calibration
range. Verify that switch S5 is set to match the resistance of the sensing resistor,
check the resistance of the NGR, and verify the sensing-resistor circuit. See Section
9.2 for sensing-resistor tests.
Repeat the calibration procedure after the open or shorted condition has been
corrected.
Critical diagnostic code.
GF LED(2): No Change; RF LED(2): ON; Assigned Relay: Trip
Remote Trip
DIAGNOSTIC LED flash code
1 L - 2 S - 1 L
1 L - 4 S - 1 L
The SE-330 was tripped by a signal from network communications. Press RESET
to clear the trip.
Critical diagnostic code.
GF LED(2): ON; RF LED(2): ON; Assigned Relay: Trip
A/D-Converter-Error Trip
DIAGNOSTIC LED flash code
An A/D-converter error was detected. Press RESET to clear the trip. If the problem
persists, consult Littelfuse.
Critical diagnostic code.
GF LED(2): No Change; RF LED(2): ON; Assigned Relay: Trip
SD Card
DIAGNOSTIC LED flash code
1 L - 5 S - 1 L
SD card is full or a write error occurred. Delete files or use a different microSDcard.
Non-critical diagnostic code.
GF LED(2): No Change; RF LED(2): No Change; Assigned Relay: No Change
If this diagnostic was caused during an attempt to upgrade the firmware, follow
this alternative process:
•
•
Remove supply from SE-330.
Insert a microSD card containing the firmware upgrade file in the root directory
of the SD card.
Power on the SE-330.
Set switch S8 to UPGRADE within 30 seconds of startup.
The upgrade should continue as described in Section 4.1.2.
•
•
•
Watchdog Trip
DIAGNOSTIC LED flash code
1 L - 6 S - 1 L
A watchdog trip results in a processor reset. During reset, UNIT HEALTHY relay
K4 will be de-energized. After a reset, UNIT HEALTHY relay K4 will be energized.
Press RESET to clear the trip. If the problem persists, consult Littelfuse.
Critical diagnostic code.
GF LED(2): ON; RF LED(2): ON; Assigned Relay: Trip
Non-Volatile Memory
Error Trip
DIAGNOSTIC LED flash code
1 L - 8 S - 1 L
1 L - 9 S - 1 L
An error was detected in the non-volatile memory. Press RESET to clear the trip. If
the problem persists, consult Littelfuse.
Critical diagnostic code.
GF LED(2): ON; RF LED(2): ON; Assigned Relay: Trip
SD Upgrade Error
DIAGNOSTIC LED flash code
An error occurred during the flash-memory upgrade procedure. Ensure that the
firmware upgrade file is correct or use a different microSD card.
Critical diagnostic code.
GF LED(2): No Change; RF LED(2): No Change; Assigned Relay: No Change
Page 28
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
PROBLEM
USB Error
DIAGNOSTIC LED
SOLUTION
FLASH CODE(1)
1 L - 10 S – 1 L
A USB algorithm timeout has been detected. Remove and reconnect the USB cable
and cycle supply voltage. If the problem persists, consult Littelfuse.
Non-critical diagnostic code.
DIAGNOSTIC LED flash code
GF LED(2): No Change; RF LED(2): No Change; Assigned Relay: No Change
DIAGNOSTIC LED = solid red
SE-330 processor failed to start. Cycle supply. If problem persists, consult Littelfuse.
K1: De-energized.
Pressing RESET does not
clear trips.
Trip condition is still present. Locate and correct.
The RESET button is disabled if remote-reset terminals 15 and 16 are connected.
Replace shorted remote-reset switch or issue Reset command from the
communications network.
UNIT HEALTHY relay K4
momentarily changes state
Processor has been reset.
No analog-output current.
The output at terminals 19 and 20 requires a voltage source. See Fig. 2 for
analog-output connections. See Section 9.3 for the analog-output tests.
NOTES:
(1) L = long pause, S = short flash.
(2) When LED is on, corresponding indication relay is energized when in the non-fail-safe mode or de-energized when in the fail-safe mode.
Page 29
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
NGR Short Detection:
6. TECHNICAL SPECIFICATIONS
6.1 SE-330
Nominal NGR Resistance ...............15 to 2,000 Ω, 166 Ω
min for 100 kΩ
Supply:
sensing resistors
Option 0.......................................... 30 VA, 120 to 240 Vac
(+10, -45%), 50/60 Hz;
NGR Short Trip Level.......................10 to 70% of the nominal
NGR resistance
NGR Short Mode.............................Monitor only, monitor and
trip, disabled
Accuracy:
ER-600VC, ER-5KV, ER-5WP:
0 to 40°C ................................. 5 Ω typical, 10 Ω max
-40 to 60°C .............................. 12 Ω typical, 20 Ω max
ER-15KV, ER-25KV, ER-35KV:
20 W, 110 to 250 Vdc
(+10, -25%)
Option 2.......................................... 20 W, 48 Vdc
(+50, -25%);
35 VA, 48 Vac
(+10, -45%), 50/60 Hz
Power-Up Time....................................... 3 s at 120 Vac
0 to 40°C ................................. 30 Ω typical, 50 Ω max
-40 to 60°C .............................. 60 Ω typical, 100 Ω max
AC Measurements ................................. Discrete Fourier
Transform. 16 samples
per cycle, 50 or 60 Hz
Optimum Calibration
Temperature....................................Midpoint of local/installed
temperature range
Resistor-Fault Circuit:
Neutral-To-Ground Voltage Trip Levels(1):
ER-600VC or ER-5KV............... 20; 60; 100; 130; 170; 200;
340; 800; 1,200; 1,700;
Ground-Fault Circuit:
Trip Level.........................................2, 4, 6, 8, 10, 20, 40, 60,
80, 100% of CT-primary
2,000 Vac
rating or 2 to 100% using
MEM parameter
ER-15KV to ER-35KV............... 100; 300; 500; 650; 850;
1,000; 1,700; 4,000; 6,000;
Trip Time..........................................0.1, 0.2, 0.3, 0.4, 0.5, 0.7,
1.0, 2.0, 3.0, 5.0, 10.0 s
Trip-Level Accuracy:
8,500; 10,000 Vac
Accuracy................................. 10% of setting
3 dB Frequency Response:
EFCT-x, CS30-x.........................max of 1% of CT-primary
S6 = 50 Hz.....................25 to 85 Hz
S6 = 60 Hz.....................30 to 90 Hz
NGR Calibration Range:
rating or 3% of setting(2)
ELCT5-x, ELCT30-x...................max of 1% of CT-primary
rating or 5% of setting(2)
ER-600VC, ER-5KV, or
Trip-Time Accuracy..........................10% of setting, 20 ms
min
ER-5WP....................................0 to 2 kΩ
ER-15KV to ER-35KV................0 to 10 kΩ
3 dB Frequency Response:
Trip Resistance, VN = 0:
S6 = 50 Hz .......................................25 to 85 Hz
S6 = 60 Hz .......................................30 to 90 Hz
Maximum CT lead resistance:
ELCT5 & ELCT30..............................5 Ω
Other CTs.........................................Consult CT curve
CT-Input Burden:
5-A Input ........................................< 0.01 Ω
1-A Input .........................................< 0.05 Ω
EFCT Input .......................................< 10 Ω
Thermal Withstand:
ER-600VC, ER-5KV, or
ER-5WP:
Range(5) .........................250 to 750-Ω change
200 Ω
Default..........................500-Ω change
ER-15KV to ER-35KV:
Range(5) .........................1.25 to 3.75-kΩ change
1 kΩ
Default..........................2.5-kΩ change
Neutral-To-Ground DC-Voltage Rejection:
ER-600VC, ER-5KV, or
ER-5WP....................................25 Vdc
ER-15KV to ER-35KV................125 Vdc
Trip Time..........................................12 to 60 s 1 s
Trip Hold-Off Level ..........................5% of CT-primary rating
Trip Mode ......................................Latching/non-latching
1-A and 5-A Inputs:
Continuous...............................2 x CT rating
1-Second..................................20 x CT rating
EFCT Input:
Continuous...............................10 x CT rating
1-Second..................................25 x CT rating
Measurement Range ......................25 x CT-primary pating
Trip Mode........................................Latching/non-latching
Pulsing Circuit:
Pulse Period ....................................1.0 to 3.0 s,
0.2-s increments
Page 30
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
Duty Cycle .......................................50%
Time Accuracy.................................10% of setting
Trip/Pulsing Relay K1 Contacts:
Range..............................................4 to 22 mA
Loop Voltage...................................8 to 36 Vdc
Load ................................................500 Ω (max with
24-Vdc supply)
Isolation..........................................120 Vac
Parameter .......................................NGR current, 20 mA =
CT primary current
Configuration.................................. N.O. (Form A)
Operating Mode............................. Fail-safe or non-fail-safe
CSA/UL Contact Ratings................ 8 A resistive 250 Vac, 5 A
resistive 30 Vdc
Supplemental Contact Ratings:
Make/Carry 0.2 s.................... 30 A
Break:
USB Communications:
Baud Rate .......................................12 Mbit/s
Protocol...........................................USB Device
Connector .......................................Mini-B
dc....................................... 75 W resistive
35 W inductive
(L/R = 0.004 s)
ac....................................... 2,000 VA resistive
1,500 VA inductive
SD Memory Card:
Type.................................................Standard grade
Form Factor.....................................microSD(3) and
microSDHC(3)
(PF = 0.4)
Subject to maxima of 8 A at 250 Vac, 8 A resistive
at 30 Vdc, and 0.4 A resistive at 150 Vdc.
Format.............................................FAT32
Capacity:
SE-330 Hardware
Revision 16 and higher........... 512 MB to 32 GB
SE-330 Hardware
Revision 15 and lower............ 512 MB to 4 GB
GF (K2) and RF (K3) Relay Contacts:
Configuration ..................................N.O. and N.C. (Form C)
Operating Mode (5).........................Non-fail-safe or fail-safe
CSA/UL Contact Ratings.................8 A resistive 250 Vac
8 A resistive 30 Vdc
Operating Temperature:
Standard Grade
Supplemental Contact Ratings:
Make/Carry 0.2 s.................... 30 A
Break:
(Included)................................ -25 to 85°C (-13 to 140°F)
Industrial Grade...................... -40 to 85°C (-40 to 140°F)
Real-Time Clock:
dc....................................... 75 W resistive
35 W inductive
Power-Off Operation...................... approx. 6 months at 20°C (68°F)
Battery included only in hardware revision 10 and higher.
(L/R = 0.004 s)
ac....................................... 2,000 VA resistive
1,500 VA inductive
Terminal-Block Ratings .......................... 10 A, 300 Vac, 12 AWG
(2.5 mm2)
(PF = 0.4)
Subject to maxima of 8 A at 250 Vac, 8 A resistive
at 30 Vdc, and 0.4 A resistive at 150 Vdc.
PWB Conformal Coating ........................ MIL-1-46058 qualified,
UL QMJU2 recognized
Mounting Configurations ....................... Panel mount and optional
Surface mount
Unit Healthy Output K4 (Option 0):
Configuration ..................................N.O. (Form A)
Operating Mode..............................Closed when healthy
Ratings............................................100 mA, 250 V (ac or dc)
Closed Resistance ..........................30 to 50 Ω
Dimensions:
Height............................................. 213 mm (8.4 in.)
Width ............................................. 99 mm (3.9 in.)
Depth.............................................. 132 mm (5.2 in.)
Unit Healthy Output K4 (Option 1):
Configuration ..................................N.C. (Form B)
Operating Mode .............................Open when healthy
Ratings............................................100 mA, 250 V (ac or dc)
Closed Resistance ..........................25 to 50 Ω
Shipping Weight .................................... 2.0 kg (4.4 lb)
Environment:
Operating Temperature.................. -40 to 60°C (-40 to 140°F)
Storage Temperature ..................... -55 to 80°C (-67 to 176°F)
Humidity ........................................ 85% Non-condensing
IP Rating......................................... IP30
Auto-reset time.......................................2.8 s max
4-20-mA Analog Output:
Surge Withstand.....................................ANSI/IEEE C37.90.1-1989
(Oscillatory and fast transient)
Type.................................................Self-powered and
Loop-powered
Page 31
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
Voltage Interruption....................... IEC 61000-4-11,
EMC Tests:
Verification tested in accordance with IEC 60255-26:2013.
IEC 61000-4-29
0% for 10, 20, 30,
50 ms (dc)
Radiated and Conducted
0% for 0.5, 1, 2.5,
5 cycles (60 Hz)
Emissions ....................................... CISPR 11:2009,
CISPR 22:2008,
IEC 61000-4-17
Level 4, 15% of the rated dc
value
EN 55022:2010 Class A
Current Harmonics and
Voltage Fluctuations ...................... IEC 61000-3-2 and
Certification............................................ CSA, Canada and United States
IEC 61000-3-3
Class A
LR 53428
C
US
Electrostatic Discharge.................. IEC 61000-4-2
UL Listed
6 kV contact discharge
(direct and indirect)
8 kV air discharge
Australia
Radiated RF Immunity.................... IEC 61000-4-3
10 V/m, 80-1,000 MHz,
80% AM (1 kHz)
10 V/m, 1.0 to 2.7 GHz,
80% AM (1 kHz)
CE, European Union
FCC
Fast Transient................................. IEC 61000-4-4
Zone B
2 kV (power supply
port), 1 kV (all other
ports)
Surge Immunity.............................. IEC 61000-4-5
Zone B
1 kV differential mode
2 kV common mode
To: CSA C22.2 No. 14 Industrial Control Equipment
UL 508 Industrial Control Equipment
UL 1053 Ground Fault Sensing and Relaying
Equipment
Australia, Regulatory Compliance Mark (RCM)
CE Low Voltage Directive
IEC 61010-1:2010 (3rd Edition) + AMD 1:2016
FCC CFR47, Part 15, Subpart B,
Class A – Unintentional Radiators
Conducted RF Immunity ................. IEC 61000-4-6
10 V, 0.15-80 MHz,
80% AM (1 kHz)
Compliance............................................. RoHS Compliant
Magnetic Field
Immunity ........................................ IEC 61000-4-8
50 Hz and 60 Hz
NOTES:
(1)
See sensing resistor specifications for applicable voltage limits.
(2)
30 A/m and 300 A/m
Accuracy included for EFCT-x, SE-CS30-x, ELCT5-x, and ELCT30-x
current sensors only.
microSD and microSDHC are trademarks of SD-3C, LLC.
Remote-reset and pulse-enable wiring is limited to 10 m (32 ft).
This value can only be modified using SE-MON330 software. See
Power Frequency(4) ......................... IEC 61000-4-16
Zone A: differential mode
100 Vrms
(3)
(4)
(5)
Zone A: common mode
300 Vrms
Section 4.2.
6.2 Sensing Resistors
1 MHz Burst ................................... IEC 61000-4-18
1 kV differential mode
Environment:
Operating Temperature.................. -40 to 60°C (-40 to 140°F)
Storage Temperature ..................... -55 to 80°C (-67 to 176°F)
Extended Operating
(line-to-line)
2.5 kV common mode
Temperature................................... -55 to 60°C (-67 to
140°F)(1)
Page 32
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
ER-600VC:
Maximum Voltage.......................... 600 Vac
ER-35KV:
Maximum Voltage.......................... 22,000 Vac
Maximum Current .......................... 30 mA
Resistance...................................... 20 kΩ
Thermal:
Maximum Current .......................... 220 mA
Resistance ..................................... 100 kΩ
Thermal:
420 Vac...................................... Continuous
600 Vac...................................... 6 minutes on,
60 minutes off
22,000 Vac.............................. 1 minute on,
120 minutes off
3,000 Vac................................ Continuous
Torque (Terminal N) ....................... 9.0 N•m (80 lbf•in.)
Shipping Weight ............................ 40 kg (88 lb)
Shipping Weight ............................ 300 g (0.7 lb)
ER-5KV:
Maximum Voltage.......................... 2,500 Vac
Maximum Current .......................... 125 mA
Resistance...................................... 20 kΩ
Thermal .......................................... Continuous
Torque:
Certification ........................................... CSA, Canada and United States
LR 53428
C
US
UL Listed
Terminal N:
10-32 Insert ....................... 5.6 N•m (50 lbf•in.)
Others................................ 9.0 N•m (80 lbf•in.)
Shipping Weigh.............................. 5.0 kg (11 lb)
Australia
ER-5WP:
CE, European Union
Maximum Voltage.......................... 2,500 Vac
Maximum Current .......................... 125 mA
Resistance...................................... 20 kΩ
Thermal .......................................... Continuous
Torque:
NOTES:
(1)
Electrical specifications have been verified at a Littelfuse lab.
Terminal N:
6.3 Current Sensors
10-32 Insert ....................... 5.6 N•m (50 lbf•in.)
Others................................ 9.0 N•m (80 lbf•in.)
Shipping Weight ............................ 5.0 kg (11 lb)
Environment:
Operating Temperature.................. -40 to 60°C (-40 to
140°F)
Storage Temperature ..................... -55 to 80°C (-67 to
176°F)
Compliance .................................... RoHS,
IEC 61869-2
ER-15KV:
Maximum Voltage.......................... 8,400 Vac
Maximum Current .......................... 84 mA
Resistance...................................... 100 kΩ
Thermal:
ANSI/IEEE C57.13
EFCT-1:
8,400 Vac................................ 1 minute on,
120 minutes off
Current Ratio.................................. 5:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 82 mm (3.2”)
Shipping Weight ............................ 0.9 kg (2.0 lb)
Certifications.................................. CSA, UL, CE
Compliance .................................... RoHS, IEC 60044-1
Extended Operating
1,900 Vac................................ Continuous
Torque (Terminal N)........................ 9.0 N•m (80 lbf•in.)
Shipping Weight ............................ 5.0 kg (11 lb)
ER-25KV:
Maximum Voltage.......................... 14,400 Vac
Maximum Current .......................... 144 mA
Resistance ..................................... 100 kΩ
Thermal:
Temperature................................... -55 to 60°C (-67 to
140°F)(1)
Supplemental
Specifications:
14,400 Vac.............................. 1 minute on,
120 minutes off
Trip Level Accuracy:
≤ 1 A ............................ 1% of CT-Primary Rating
> 1 A ............................ 3% of CT-Primary Rating
2,500 Vac................................ Continuous
Torque (Terminal N)........................ 9.0 N•m (80 lbf•in.)
Shipping Weight ............................ 20 kg (44 lb)
Page 33
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
EFCT-26:
Current Ratio.................................. 5:0.05 A
Extended Operating
Temperature................................... -55 to 60°C (-67 to
140°F) (1)
Insulation ....................................... 600-V Class
Window Diameter.......................... 26 mm (1.0”)
Shipping Weight ............................ 0.45 kg (1.0 lb)
Certifications.................................. CSA, UL, CE
Compliance .................................... RoHS, IEC 60044-1
Extended Operating
SE-CS30-26:
Current Ratio.................................. 30:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 26 mm (1.0”)
Shipping Weight ............................ 0.45 kg (1.0 lb)
Certifications.................................. CSA, UL, CE
Compliance .................................... RoHS, IEC 60044-1
Extended Operating
Temperature .................................. -55 to 60°C (-67 to
140°F)(1)
Supplemental
Specifications:
Trip Level Accuracy:
Temperature................................... -55 to 60°C (-67 to
140°F)(1)
≤ 1 A..........................1% of CT-Primary Rating
> 1 A..........................3% of CT-Primary Rating
SE-CS30-70:
Current Ratio.................................. 30:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 70 mm (2.7”)
Shipping Weight ............................ 1.2 kg (2.5 lb)
Certifications.................................. CSA, UL, CE
Compliance .................................... RoHS, IEC 60044-1
Extended Operating
ELCT30-31:
Current Ratio.................................. 30:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 31 mm (1.22 in.)
Shipping Weight ............................ 0.45 kg (1 lb)
Certifications.................................. cUL, CE
Temperature................................... -55 to 60°C (-67 to
ELCT30-88:
140°F)(1)
Current Ratio.................................. 30:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 88 mm (3.46 in.)
Shipping Weight ............................ 0.91 kg (2 lb)
Certifications.................................. cUL, CE
(1)
Electrical specifications have been verified at a Littelfuse
lab.
ELCT5-31:
Current Ratio.................................. 5:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 31 mm (1.22 in.)
Shipping Weight ............................ 0.45 kg (1 lb)
Certifications.................................. cUL, CE
ELCT5-88:
Current Ratio.................................. 5:0.05 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 88 mm (3.46 in.)
Shipping Weight ............................ 0.91 kg (2 lb)
Certifications.................................. cUL, CE
CT200:
Current Ratio.................................. 200:5 A
Insulation ....................................... 600-V Class
Window Diameter.......................... 56 mm (2.2 in.)
Shipping Weight ............................ 1 kg (2.2 lb)
Certifications.................................. CSA, UL
Compliance .................................... RoHS
Page 34
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
CT200 ............................................. Current sensor,
7. ORDERING INFORMATION
200-A-primary rating,
56-mm (2.2 in.) window
-
SE-330-
5SHT-101-E..................................... Current sensor,
K4 Contact:
0 N.O. UNIT HEALTHY Contact
1 N.C. UNIT HEALTHY Contact
100-A-primary rating,
40-mm (1.6 in.) window
5SHT-151-E..................................... Current sensor,
150-A-primary rating,
40-mm (1.6 in.) window
5SHT-500-E..................................... Current sensor,
50-A-primary rating,
40-mm (1.6 in.) window
7SHT-301-E..................................... Current sensor,
300-A-primary rating,
64-mm (2.5 in.) window
7SHT-401-E..................................... Current sensor,
Options:
0 No Options
Network Communications:(1)
0 None
1 DeviceNet™
3 Ethernet (Dual RJ45)(2)
4 Ethernet (SC fiber & RJ45)(2)
5 Ethernet (Dual SC fiber)(2)
6 IEC 61850 (Dual RJ45)
7 IEC 61850 (SC fiber & RJ45)
8 IEC 61850 (Dual SC fiber)
Supply:
400-A-primary rating,
64-mm (2.5 in.) window
0 Universal ac/dc supply
2 48 Vdc supply
Accessories:
RK-332............................................ Remote indication and reset,
includes two 120-V pilot
lights, a reset push button,
and legend plates
SE-IP65CVR-G ................................ Hinged transparent cover,
IP65
NOTE: Please refer to the SE-330 Product Change Notice (PCN)
document for updated ordering information and new revision
details, available at www.littelfuse.com/se-330.
SE-MRE-600................................... Moisture-resistant
enclosure for ER-600VC
PGA-0520 ....................................... Percent analog meter
SE-330-SMA .................................. Surface mount adapter
AC300-MEM-00 ............................. Industrial-grade
microSD card
NOTE: The SE-330-SMA surface mount adapter is available as an
accessory only.
Sensing Resistors:
ER-600VC ....................................... For system voltages up to
1 kVac
Software:(4)
ER-5KV ........................................... For system voltages up to
5 kVac
ER-5WP .......................................... For system voltages up to
5 kVac, weather protected
ER-15KV ......................................... For system voltages up to
15 kVac
ER-25KV ........................................ For system voltages up to
25 kVac
ER-35KV ......................................... For system voltages up to
35 kVac
SE-MON330 Software ................... SE-330 Data-display
Program for PC, version
4.0 or higher
NGR Monitor
Set-Point Assistant ........................ SE-330 settings guide
NOTES:
(1)
(2)
(3)
(4)
Profibus models only available on legacy SE-330.
Includes Modbus TCP and EtherNet/IP protocols.
Includes IEC 61850 protocol only.
Current Sensors:
Available at www.littelfuse.com/relayscontrols.
ELCT5-31 ........................................ Current sensor, 31-mm
(1.22 in.) window
ELCT5-88 ........................................ Current sensor, 88-mm
(3.46 in.) window
ELCT30-3 ........................................ Current sensor, 31-mm
(1.22 in.) window
ELCT30-88 ...................................... Current sensor, 88-mm
(3.46 in.) window
Page 35
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
NOTE: Resistor-fault-trip reset can take up to one second.
8. WARRANTY
The SE-330 Neutral-Grounding-Resistor Monitor is warranted to
be free from defects in material and workmanship for a period of
five years from the date of purchase.
9.1.2 Voltage Test
Test Equipment: 0 to 120 Vac voltage source, multimeter, and ER
sensing resistor.
Littelfuse will (at the choice of Littelfuse) repair, replace, or
refund the original purchase price of an SE-330 that is determined
by Littelfuse to be defective if it is returned to Littelfuse, freight
prepaid, within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an accident,
improper installation, tampering, or insufficient care. Littelfuse
does not warrant products repaired or modified by non-Littelfuse
personnel.
NOTE: Use an isolation transformer if the test-voltage source
does not provide dc continuity for the SE-330 resistance-measuring
circuit.
NOTE: Applying the test voltage to the R and G terminals will
damage the SE-330 and the ER sensing resistor. The VN TRIP LEVEL
is the trip voltage at terminal N, not terminal R.
9. TEST PROCEDURES
Procedure:
NOTE: Ensure the real-time clock is set. See Section 4.2.
•
•
Connect the ER sensing resistor to the SE-330 and calibrate
the SE-330.
9.1 Resistor-Fault Tests
Disconnect the wire from sensing-resistor terminal N. A
resistor-fault trip will occur.
Perform tests with system de-energized and supply voltage
applied to the SE-330.
•
•
Set the voltage source to 0 V.
Connect the voltage source between sensing resistor N and
G terminals.
9.1.1 Calibration and Open Test
Test Equipment: 20-kΩ and 100-kΩ, ¼-watt, 1%
calibration resistors (calibration resistors
are supplied with SE-330).
•
•
•
•
Set the VN TRIP LEVEL (VAC) to 20.
Press RESET.
Procedure:
The RESISTOR FAULT TRIP LED should be off.
•
•
•
•
•
•
•
Remove connections to terminals 6 and 7.
Connect the 20-kΩ resistor to terminals 6 and 7.
Set switch S5 to the 20-kΩ position.
Perform calibration as per Section 2.2.
The CALIBRATED LED should be on.
Press RESET.
Increase the test voltage to 25 Vac for 20-kΩ sensors or 120
Vac for 100-kΩ sensors and wait for the resistor-fault trip
time.
PASS: The SE-330 should trip on RESISTOR FAULT. A time
delayed ground-fault trip follows the resistor-fault trip if
neutral voltage persists after the resistor fault. For legacy
units with firmware revision 6 or less, this does not apply.
9.2 Sensing-Resistor Test
Test Equipment: Multimeter
Procedure:
Remove the 20-kΩ resistor and wait for the resistor-fault trip
time.
PASS: The SE-330 should trip on resistor fault.
Connect the 100-kΩ resistor to terminals 6 and 7.
Set switch S5 to the 100-kΩ position.
Perform calibration as per Section 2.2.
The CALIBRATED LED should be on.
Press RESET.
•
•
•
•
•
•
•
•
Disconnect the sensing resistor.
Measure the resistance between sensing-resistor terminals R
and N.
PASS: Resistance should be between 19.6 and 20.4 kΩ for
20-kΩ sensing resistors. Resistance should be between 98
and 102 kΩ for 100-kΩ sensing resistors.
Remove the 100-kΩ resistor and wait for the resistor-fault trip
time.
•
Measure the resistance between sensing-resistor terminals R
and G in both directions.
PASS: The SE-330 should trip on resistor fault.
PASS: Resistance should be greater than 10 MΩ in both
directions.
Page 36
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
NOTE: Do not inject test current directly into CT-input terminals 8,
9, 10, and 11.
9.3 Analog-Output Test
Test Equipment: multimeter with an mAdc scale.
Procedure:
NOTE: For accurate trip-time measurement, the fault current should
not be re-applied for the time defined by the GF TRIP TIME setting to
allow the trip accumulator to initialize.
•
Connect the 4-20-mA output as a self-powered output (see Fig.
3). Measure the current from terminal 20 to terminal 21.
PASS: With no CT current, the analog output should be 4
mA.
•
Output is linear to 20 mA. output is 20 mA when CT-primary
current is equal to the CT-primary rating.
9.4 Ground-Fault Performance Test
To meet the requirements of the National Electrical Code*, the
overall ground-fault protection system requires a performance
test when first installed (as applicable). A written record of the
performance test must be retained by those in charge of the
electrical installation in order to make it available to the authority
having jurisdiction. A test-record form is included for recording the
date and the final results of the performance tests. The following
ground-fault system tests are to be conducted by qualified
personnel:
•
Evaluate the interconnected system in accordance with the
overall equipment manufacturer’s detailed instructions.
•
Verify proper installation of the ground-fault current sensor.
Ensure the cables pass through the ground-fault-current-
sensor window. This check can be visually conducted with
knowledge of the circuit. The connection of the current-sensor
secondary to the SE-330 is not polarity sensitive.
•
•
Verify that the system is correctly grounded and that alternate
ground paths do not exist that bypass the current sensor.
High-voltage testers and resistance bridges can be used to
determine the existence of alternate ground paths.
FIG. 22. Ground-fault-test circuits.
TABLE 3. Ground-fault-test record
DATE
TEST RESULTS
Verify proper reaction of the circuit-interrupting device in
response to a simulated or controlled ground-fault current. To
simulate ground-fault current, use CT-primary current injection
(does not apply for bushing-type CTs). Fig. 22a shows a test
circuit using an SE-400 Ground-Fault-Relay test unit. The SE-
400 has a programmable output of 0.5 to 9.9 A for a duration
of 0.1 to 9.9 seconds. Set the test current to 120% of GF TRIP
LEVEL. Fig. 22b shows a test circuit using an SE-100T Ground-
Fault-Relay Tester. The SE-100T provides a test current of 0.65
or 2.75 A for testing 0.5- and 2.0-A trip levels. Inject the test
current through the current-sensor window for at least 2.5
seconds. Verify that the circuit under test has reacted properly.
Correct any problems and re-test until the proper reaction is
verified.
Record the results and date of each test on the attached test-
record form.
Retain this record for the authority having jurisdiction.
Page 37
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
APPENDIX A
SE-330 REVISION HISTORY
MANUAL RELEASE
DATE
PRODUCT REVISION
(REVISION NUMBER ON PRODUCT LABEL)
MANUAL REVISION
FIRMWARE VERSION
3.00
2.60
2.60
2.55
2.54
2.53
June 30, 2018
11-A-063018
17A
17
October 18, 2017
December 7, 2016
10-P-101817
10-N-120716
September 21, 2016
10-M-092116
16
June 30, 2016
September 8, 2015
June 22, 2015
May 20, 2015
10-L-063016
10-K-090815
10-J-062215
10-I-052015
10-H-030315
2.52
2.50
2.40
15
14
March 3, 2015
2.31
2.30
July 7, 2014
10-G-070714
10-F-041414
April 14, 2014
13
12
11
2.20
January 8, 2014
10-E-010814
November 29, 2013
October 8, 2013
September 12, 2013
August 30, 2013
10-D-112913
10-C-100813
10-B-091213
10-A-083013
2.10
2.08
2.07
2.07
10A
10
MANUAL REVISION HISTORY
REVISION 11-A-063018
GENERAL
Manual format and many sections have been updated.
SECTION 1
Descriptions for NGR short detection and assignable relays added.
SECTION 2
Enhanced health status added.
SECTION 6
NGR short detection specifications added.
REVISION 10-P-101817
SECTION 2
New features described in Section 2.8.
SECTION 3
Installation instruction updated.
SECTION 4
SD Card note added.
SECTION 5
Troubleshooting information added.
SECTION 7
Ordering information updated.
REVISION 10-N-120716
APPENDIX A
Revision history updated.
Page 38
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
REVISION 10-M-092116
SECTION 4
Firmware upgrade instructions updated.
APPENDIX A
Revision history updated.
REVISION 10-L-063016
SECTION 4
Section 4.1.2 updated.
SECTION 6
microSDstorage capacity increased to 32 GB.
RCM certification added.
REVISION 10-K-090815
SECTION 4
Section 4.1.2 updated.
SECTION 5
SD card diagnostic troubleshooting updated.
REVISION 10-J-062215
SECTION 2
Section 2.1.7 added.
SECTION 4
SD card approximate annual data logging usage updated.
SE-MON330 software version updated.
SECTION 6
Resistor-fault trip level ranges added.
REVISION 10-I-030315
SECTION 4
SD card storage capacity updated.
SECTION 6
SD card storage capacity specification updated.
REVISION 10-H-030315
SECTION 2
Sections 2.1.6 and 2.1.7 added.
SECTION 4
Section 4.2 new features added.
SECTION 6
Resistor-fault circuit trip time update
REVISION 10-G-070714
SECTION 6
Added CE, C-Tick, and FCC information.
REVISION 10-F-041414
APPENDIX A
Hardware revision updated.
REVISION 10-E-010814
SECTION 6
Extended operating temperatures added to all sensing resistors and SE-CS30 current sensors.
REVISION 10-D-112913
SECTION 6
CE added to sensing resistors.
SECTION 7
Ordering information updated.
REVISION 10-C-100813
SECTION 2
Section 2.8 updated.
SECTION 4
Real-time clock note added in Section 4.2.
Page 39
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
SECTION 5
LED and relay status added to troubleshooting solutions.
SECTION 7
Ordering information updated.
REVISION 10-B-091213
APPENDIX A
Hardware revision updated.
REVISION 10-A-083013
SECTION 1
Faceplate updated.
New features added.
SECTION 2
Communications options updated.
Configuration switches updated.
Indication relays explanation added.
Non-volatile-memory error added.
SECTION 3
Connection drawing updated.
SECTION 4
Section heading changed to Data Interfaces.
Updated with microSD and USB interfaces.
Upgrade procedure added.
SECTION 5
Non-volatile-memory error added.
Switch S8 diagnostic LED error removed.
SECTION 6
Ground-fault circuit trip level updated.
USB communications specifications added.
Resistor-fault accuracy changed.
microSD memory card specifications added.
SECTION 7
Ordering information updated.
SE-330-SMA surface mount adapter listed as an accessory only.
APPENDIX A
Added revision history.
HARDWARE REVISION HISTORY
HARDWARE REVISION 17A
Additional EMC filter capacitors added.
HARDWARE REVISION 17
Enhanced transient protection added.
HARDWARE REVISION 16
microSD storage capacity increased to 32 GB.
HARDWARE REVISION 15
RTC circuit updated.
HARDWARE REVISION 14
CE and C-Tick compliance added.
HARDWARE REVISION 13
ESD sensitivity of front-panel dials reduced
HARDWARE REVISION 12
Fiber ethernet support improved.
HARDWARE REVISION 11
ESD sensitivity of USB and SD card connectors reduced.
HARDWARE REVISION 10A
RTC circuit updated.
Page 40
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 11-A-063018
HARDWARE REVISION 10
SE-330 platform updated to include USB and microSD interfaces, programmable trip level (MEM) feature, and ability to add
future options.
Real-time clock and rechargeable battery added.
Dual cable and fiber Ethernet ports added.
FIRMWARE REVISION HISTORY
FIRMWARE REVISION 3.00
NGR short detection functionality added.
Assignable functions for K1, K2, and K3 added.
Standard and non-accumulating selections added to ground-fault trip time algorithm.
UTC Offset added to SNTP Client functionality.
SD card logging limited to two most recent months of data.
FIRMWARE REVISION 2.60
Option to display only critical diagnostic codes with DIAGNOSTIC LED added.
FIRMWARE REVISION 2.55
IEC 61850 network watchdog resets corrected.
FIRMWARE REVISION 2.54
NAND FLASH bit-error-correction update to prevent solid-red diagnostic LED error when bit errors are correctable.
Resistor-fault trip level added to web interface.
MODBUS TCP/IP write response byte count corrected.
TCP Keep Alive network setting no longer resets to 5 s after power cycle.
FIRMWARE REVISION 2.53
NAND FLASH bit error correction code to prevent solid-red diagnostic error fixed.
FIRMWARE REVISION 2.52
Improved compatibility with Internet Explorer* web browser.
FIRMWARE REVISION 2.50
Support for adjustable resistor-fault trip level added.
Web page functionality re-enabled for Ethernet options.
FIRMWARE REVISION 2.40
Support for geo-magnetic filter added.
Support for 12 to 60 s resistor-fault trip time added.
Improved log file descriptions.
IEC 61850 GOOSE network input support now always enabled.
Improved compatibility for Modbus TCP.
Web page disabled for Ethernet options. This will be enabled in a future firmware release.
IP setting changes for Ethernet options now require power cycle to take effect.
FIRMWARE REVISION 2.31
SD card and USB diagnostic events no longer cause a trip.
FIRMWARE REVISION 2.30
Remote calibration feature added.
FIRMWARE REVISION 2.20
Added support for Ethernet/IP protocol.
IED name now reported correctly through IEC 61850 interface.
Ethernet/IP and Modbus communications card LED status updated.
Hardware version viewable in the SE-MON330 software and through the MODBUS and IEC 61850 servers.
FIRMWARE REVISION 2.10
Added support for IEC 61850 and DeviceNet protocols.
FIRMWARE REVISION 2.08
Added support for communications options.
FIRMWARE REVISION 2.07
Updated firmware to include USB and microSD interfaces, datalogging, and firmware update via microSD.
K2 and K3 indication relays can be configured for fail-safe or non-fail-safe operation.
Trip records increased to 100 with date and time stamping.
* Bluetooth, Internet Explorer, National Electric Code, and microSD are trademarks of their respective owners.
相关型号:
©2020 ICPDF网 联系我们和版权申明