Protection Relays  
Neutral-Grounding-Resistor Monitoring  
SE-330, SE-330HV SERIES  
Neutral-Grounding-Resistor Monitor  
Description  
The SE-330 is an advanced ground-fault and neutral-grounding-  
resistor monitoring relay that is compliant with Rule10-302 of the  
2018 Canadian Electrical Code Part I (CE Code). It measures neutral  
current, neutral-to-ground voltage, and neutral-to-ground resistance.  
It provides continuous monitoring of the neutral-to-ground path to  
verify that the neutral-grounding resistor (NGR) is intact and that it  
has not been bypassed or shorted. An open NGR renders current-  
sensing ground-fault protection inoperative and could result in a false  
belief that the system is functioning properly. A shorted NGR results  
in higher-than-expected ground-fault current.The SE-330 can be used  
with low- and medium-voltage transformers and generators with  
low- or high-resistance grounding used in processing, manufacturing,  
chemical, pulp and paper, petroleum, and water-treatment facilities.  
For high-voltage applications, use the SE-330HV. For applications that  
require conformance to Australian standards, use the SE-330AU.  
Simplified Circuit Diagram  
Resistor Monitoring  
The SE-330 combines the measured values of resistance, current,  
and voltage to continuously determine that an NGR is intact. It is  
able to detect an open or shorted resistor with or without a ground  
fault present. Sensing resistors are matched to the system voltage  
and are used to monitor NGRs on systems up to 72 kV.  
ꢄꢅ  
B
ER SERIES  
Ground-Fault Monitoring  
SE-330 SERIES  
ꢀꢁensinꢂ Resistorꢃ  
The SE-330 uses an application-appropriate current transformer to  
reliably detect ground-fault currents as small as 100 mA. Discrete-  
FourierTransform (DFT) filtering ensures that false trips due to  
harmonic noise from adjustable-speed drives do not occur. Should  
the resistor open and a ground fault subsequently occur, the SE-330  
will detect the fault through voltage measurement, while other  
current-only sensing relays would be ineffective.  
ꢀꢄꢅR ꢆonitorꢃ  
ꢀꢁR  
ꢂꢆ  
ꢂꢃ  
A
For detailed wiring diagram, see adjacent page.  
Ordering Information  
POWER  
SUPPLY  
K4 UNIT HEALTHY  
ORDERING  
NUMBER  
COMM  
CONTACT  
Pulsing Ground-Fault Location  
X
The SE-330 is capable of controlling a pulsing contactor, which is  
used to switch the NGR resistance in a pulsing-compatible NGR  
package.The resulting ground-fault current is distinguishable from  
charging currents and noise and will only appear upstream of the  
ground fault, making fault location fast and easy, even without  
isolating feeders or interrupting loads.  
SE-330  
-
X
X
-
0
0=USB Only  
1=DeviceNet  
3=EtherNet  
(Dual RJ45)  
SE-330  
for applications  
35 kV or less  
4=EtherNet  
(SC Fiber & RJ45)  
0=120/240  
Vac/Vdc  
0=Normally Open  
1=Normally Closed  
5=EtherNet  
(Dual SC Fiber)  
6=IEC61850  
(Dual RJ45)  
Accessories  
SE-330HV  
for 72 kV  
applications  
2=48 Vdc  
ER Series Sensing Resistor  
A
Required interface between the power system and the  
SE-330/SE-330HV. Eliminates hazardous voltage levels at  
the relay.  
7=IEC61850  
(SC Fiber & RJ45)  
8=IEC61850  
(Dual SC Fiber)  
B
ELCT5 Series Ground-Fault CurrentTransformer  
Sensitive ground-fault current detection (5 A primary).  
NOTE: For Australian applications, see the SE-330AU.  
ACCESSORIES  
ER Series Sensing Resistor  
Current Transformer  
SE-IP65CVR-G  
SE-MRE-600  
RK-332  
NGRM-ENC  
PGA-0520  
SE-330-SMA  
REQUIREMENT  
Required  
Required  
Optional  
Optional  
Optional  
Optional  
Optional  
Optional  
ELCT30 Series Ground-Fault CurrentTransformer  
Sensitive ground-fault current detection (30 A primary).  
Other CurrentTransformer  
For low-resistance NGRs choose a CT primary  
approximately equal to the NGR rating. Inputs are  
provided for 1- and 5- A- secondary CTs.  
SE-IP65CVR-G HingedTransparent Cover  
Watertight cover, tamper resistant, IP65 protection.  
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.  
Rev: 4-D-042519  
Based on SE-330 Manual Rev: 11-A-063018  
Based on SE-330 HV Manual Rev: 5-M-101817  
© 2019 Littelfuse Protection Relays & Controls  
©
Littelfuse.com/se-330 Littelfuse.com/se-330hv  
Protection Relays  
Neutral-Grounding-Resistor Monitoring  
SE-330, SE-330HV SERIES  
Neutral-Grounding-Resistor Monitor  
Features & Benefits  
FEATURES  
IEEE #  
BENEFITS  
Continuous NGR monitoring  
Shorted NGR detection  
3
Detects resistor failure within seconds, reduces transient-overvoltage risk, removes risk of ground-fault-detection failure  
Detects a ground fault on the neutral that could bypass the resistor, ensures fault current is not higher than expected  
Main or backup protection to detect a ground fault anywhere on the monitored system  
Select greatest sensitivity without false operation, adjustable in 1% increments (MEM setting)  
Adjustable trip delay allows quick protection and system coordination  
3
Ground-fault detection  
50G/N, 51G/N, 59N  
Adjustable pickup (2-100%)  
Adjustable time delay (0.1-10 s)  
Universal CT compatibility  
Programmable output contacts  
Allows the use of a CT that gives required ground-fault settings  
Two programmable Form C and One programmable Form A (Ground Fault, Resistor Fault, Unit Health)  
Selectable contact  
operating mode  
Selectable fail-safe or non-fail-safe operating modes allows connection to shunt or undervoltage breaker  
coil or alarm circuit (K1, K2, and K3 output contacts)  
Analog output (4-20 mA)  
Pulsing output (SE-330 only)  
Trip records  
Connect an optional PGA-0520 meter or control system  
Control the operation of a pulsing ground-fault-location circuit  
On-board 100-event (with date and time) recorder helps with system diagnostics  
Eliminate false trips due to harmonic noise from ASDs  
Harmonic filtering (DFT)  
Local communications  
Data logging  
Mini USB port to view measured values, configure settings, and check event records  
On-board microSD card (included) can be used for long-term data logging  
Remotely view measured values and event records, reset trips, and cause a remote trip  
Available Protocol Options:  
IEC 61850 - with dual RJ45, SC Fiber and RJ45, or Dual SC Fiber Interface  
Modbus TCP and Ethernet/IP - with dual RJ45, SC Fiber and RJ45, or Dual SC Fiber Interface  
DeviceNet - with CAN interface  
Network communications  
Software  
PC-interface software (SE-MON330) is available at Littelfuse.com/RelaySoftware  
Selectable latching or auto-reset operation  
Selectable reset mode  
Unit-healthy output  
Conformal coating  
Verifies SE-330 is operating correctly, available as Form A or Form B output contact  
Internal circuits are conformally coated to protect against corrosion and moisture  
TypicalValues  
NEUTRAL-GROUNDING RESISTOR  
SENSING RESISTOR  
RESISTANCE  
(SWITCH S5 SETTING)  
GROUND-FAULT  
PICKUP LEVEL  
(AMPERES)  
SYSTEM VOLTAGE  
(VOLTS)  
VN PICKUP LEVEL  
(VOLTS)  
CURRENT  
RESISTANCE  
(OHMS)  
MODEL  
(AMPERES)  
480  
600  
2,400  
4,160  
7,200  
14,400  
5
5
5
5
10  
15  
55  
69  
277  
480  
416  
554  
ER-600VC  
ER-600VC  
ER-5KV  
ER-5KV  
ER-15KV  
ER-15KV  
20 k  
20 k  
20 k  
20 k  
100 k  
100 k  
Ω
Ω
Ω
Ω
Ω
Ω
2.5  
2.5  
2.5  
3
2
3
170  
200  
800  
1,700  
170 x 5 = 850  
340 x 5 = 1,700  
DISCLAIMER: The above table is for illustrative purposes only. Actual values may differ based on a variety of individual system considerations, such as capacitive charging current and coordination study results.  
Specifications  
Wiring Diagram  
IEEE Device Numbers  
Input Voltage  
Ground Fault (50G/N, 51G/N, 59N), Checking Relay (3), Lockout Relay (86)  
See ordering information  
ꢘꢛ  
ꢘꢐ  
ꢇꢂꢈꢃ  
ꢉꢆꢊꢉꢋ  
ꢀꢁꢂꢃRꢁꢄ  
PꢁꢅꢆR  
Dimensions  
H 213 mm (8.4"); W 98 mm (3.9"); D 132 mm (5.2")  
2-100% of CT-Primary Rating in 1% increments  
0.1-10 s  
Rꢆꢌꢆꢃ  
GF Trip-Level Settings  
GF Trip-Time Settings  
Vn Trip-Level Settings  
PꢁꢅꢆR ꢌꢋꢌꢃꢆꢖ  
ꢂꢆꢇꢃRꢊꢄ ꢎꢗꢑꢒ  
ꢘꢙ  
ꢘꢠ  
ꢘꢟ  
ꢂꢆꢇꢃRꢊꢓRꢁꢇꢂꢕꢈꢂꢓꢏ  
20-2,000 Vac (≤5 kV systems) 100-10,000 Vac (>5 kV systems)  
RꢆꢌꢈꢌꢃꢁR ꢖꢁꢂꢈꢃꢁR  
SE-330 SERIES  
ꢌꢆꢂꢌꢈꢂꢓ RꢆꢌꢈꢌꢃꢁR  
Pꢇꢄꢌꢆ  
ꢆꢂꢊꢍꢄꢆ  
ꢎꢌꢆꢏꢐꢐꢑ ꢁꢂꢒ  
ER SERIES  
Contact Operating Mode Selectable fail-safe or non-fail-safe (K1, K2, K3)  
Harmonic Filtering  
Reset Button  
+24 Vdc ꢘꢞ  
ꢊꢂꢊꢄꢁꢓ  
ꢁꢇꢃPꢇꢃ  
ꢚꢏꢛꢑ ꢜꢊ  
ꢘꢝ  
+
Standard feature  
ꢀreꢁuireꢂꢃ  
R
R
ꢛꢑ  
Standard feature  
ꢛꢘ  
0 V  
A
Output Contacts  
Pulsing Circuit  
Approvals  
Two Form A and two Form C  
ꢛꢛ  
ꢛꢐ  
1.0-3.0 s in 0.2 s increments (SE-330 only)  
CSA certified, UL Listed (E340889), CE (European Union), RCM (Australian)  
Mini USB (standard); DeviceNet (optional), IEC 61850 (optional),  
Modbus TCP and EtherNet/IP (optional)  
4-20 mA, self or loop powered  
Standard feature  
ꢃRꢈP ꢁR  
Pꢇꢄꢌꢈꢂꢓ  
ꢎꢡꢘꢒ  
ꢀꢇRRꢆꢂꢃ ꢃRꢊꢂꢌꢔꢁRꢖꢆR  
Communications  
EFCT FAMILY  
ꢛꢚ  
ꢛꢙ  
ꢛꢠ  
ꢆꢔꢀꢃ  
ꢘ ꢊ  
ꢓRꢁꢇꢂꢕ  
ꢔꢊꢇꢄꢃ  
ꢎꢡꢛꢒ  
ꢀreꢁuireꢂꢃ  
Analog Output  
Conformally Coated  
Warranty  
ꢘꢑ  
ꢘꢘ  
ꢙ ꢊ  
B
ꢀꢁꢖꢖꢁꢂ  
ꢛꢟ  
ꢛꢞ  
ꢛꢝ  
RꢆꢌꢈꢌꢃꢁR  
ꢔꢊꢇꢄꢃ  
ꢎꢡꢐꢒ  
5 years  
Panel and Surface (optional)  
Mounting  
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.  
Rev: 4-D-042519  
Based on SE-330 Manual Rev: 11-A-063018  
Based on SE-330 HV Manual Rev: 5-M-101817  
© 2018 Littelfuse Protection Relays & Controls  
©
Littelfuse.com/se-330 Littelfuse.com/se-330hv  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY