2000W Front End Power Supply
RCP-2000 series
Features :
Universal AC input / Full range
Built-in 5V/0.3A, 12V/0.8A auxiliary power
Built-in active PFC function, PF>0.98
High efficiency up to 92%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage / Over temperature
High Power density 21.4W/inch3
Forced air cooling by built-in DC fan with fan speed control
Low profile:1U height
Remote control for single unit
Built-in remote sense function
Output voltage trimming function
Hot-swap operation
PMBus serial communication
AC OK, DC OK signal, fan fail, OTP alarm signal
Internal OR-ing FET
3 years warranty
Description :
The RCP-2000 series are state of the art AC/DC frond-end rectifiers with 1U compact size and 21.4 W/in3 of high power density. They can
provide up to 2000W per unit for the applications of servers, information technology equipment, networking, telecommunications, and wide
range of industrial applications using distributed power architecture. Equipped with hot-swap function and PMBus communication protocol,
RCP-2000 can be assembled in 1U 19 rack and controlled/monitored by external device such as monitoring unit (RCP-CMU-1) or PC.
SPECIFICATION - Single Unit
MODEL
RCP-2000-12
RCP-2000-24
RCP-2000-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
100A
80A
42A
0 ~ 100A
1200W
0 ~ 80A
1920W
200mVp-p
21 ~ 28V
1.0%
0 ~ 42A
2016W
300mVp-p
42 ~ 56V
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
VOLTAGE ADJ. RANGE 10.5 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1500ms, 60ms/230VAC at full load
16ms/230VAC at 75% load
10ms/230VAC at full load
VOLTAGE RANGE
Note.5 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
47 ~ 63Hz
0.98/230VAC at full load
86%
90.5%
92%
INPUT
13A/115VAC
7A/230VAC
16A/115VAC
10A/230VAC
16A/115VAC
10A/230VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
COLD START 50A
<1.1mA / 230VAC
LEAKAGE CURRENT
105 ~ 125% rated output power
OVERLOAD
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
14.7 ~ 17.5V
29.5 ~ 35V 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
80 (TSW1) detect on heatsink of power bridge 85 (TSW2) detect on heatsink of o/p diode
OVER VOLTAGE
PROTECTION
5
5
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
5V @ 0.3A, 12V @ 0.8A
AUXILIARY POWER
By electrical signal or dry contact ON:short OFF:open
Compensate voltage drop on the load wiring up to 0.5V
The isolated TTL signal out, refer to function manual
The isolated TTL signal out, refer to function manual
Adjustment of output voltage, possible between 90 ~ 110% of rated output
Logic " High" for over temperature warning, refer to function manual, isolated signal
The isolated TTL signal out, refer to function manual
-40 ~ +70 (Refer to "Derating Curve")
REMOTE ON/OFF CONTROL
REMOTE SENSE
DC OK SIGNAL
FUNCTION
AC OK SIGNAL
OUTPUT VOLTAGE TRIM
OVER TEMP WARNING
FAN FAIL SIGNAL
WORKING TEMP.
20 ~ 90% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
-40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
TEMP. COEFFICIENT
VIBRATION
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
File Name:RCP-2000-SPEC 2011-05-09
2000W Front End Power Supply
RCP-2000 series
MODEL
RCP-2000-12
RCP-2000-24
RCP-2000-48
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
SAFETY &
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMC
(Note 4)
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
60.1Khrs min. MIL-HDBK-217F (25
295*127*41mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
2Kg;6pcs/13Kg/1.04CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Output of all the RCP-2000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
Mechanical Specification (Single Unit)
Case No. 974A
Unit:mm
295
41
24
SVR1
CN501
Air flow
direction
1
2
3
4
5
6
7
8
9
33
11 14 17 20 23 26 29
12 15 18 21 24 27 30
13 16 19 22 25 28 31
10
32
34
Input / Output Connector Pin No. Assignment(CN501) : Postronic PCIM34W13M400A1
Pin No. Assignment Pin No. Assignment Pin No. Assignment Pin No. Assignment Pin No. Assignment Pin No. Assignment
Mating Housing
+V
-V
DA
DB
+S
-S
ON/OFF
A1
NC
SDA
T-ALARM
FAN-FAIL
+5V-AUX
+12V-AUX
GND-AUX
FG
12
17
22
27
32
1,2,3,4
5,6,7,8
9
AC/L
AC/N
13
14
15
16
18
19
20
21
23
24
25
26
28
29
30
31
33
34
Postronic
PCIM34W13F400A1
-V(signal)
+V(signal)
PV
A2
SCL
A3
AC-OK
DC-OK
10
A0
A4
11
File Name:RCP-2000-SPEC 2011-05-09
2000W Front End Power Supply
RCP-2000 series
Block Diagram
PFC fosc : 110KHz
PWM fosc : 90KHz
+S
ACTIVE
INRUSH
CURRENT
LIMITING
ORING
+V
RECTIFIERS
RECTIFIERS
&
FILTER
POWER
SWITCHING
EMI
FILTER
FET
I/P
&
PFC
-V
-S
O.V.P.
ORING FET
CONTROL
DETECTION
CIRCUIT
PWM
CONTROL
PFC
CONTROL
PV
TRANSCEIVERS
DA/DB
T-Alarm
DC-OK
AC-OK
FAN FAIL
SDA/SCL
DETECTION
CIRCUIT
MCU
MCU
DATA
ISOLATION
O.T.P.
PM BUS
FAN
ON/OFF
AUX
POWER
12V/0.8A
AUX POWER
5V/0.3A
RECTIFIERS
&
FILTER
Function Description of CN501
Pin No.
1,2,3,4
5,6,7,8
9
Function
+V
Description
Positive output voltage
Negative output voltage.
-V Signal
-V
-V
10
+V
+V Signal
11
PV
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
Differential digital signal for parallel control. (Note.1)
12,13
DA,DB
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
14
15
+S
-S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
16,18,19, A0,A1,A2,
A3,A4
PMBus interface address lines. (Note.1)
20,21
17
ON/OFF The unit can turn the output on and off by electrical signal or dry contact. (Note.2)
22
NC
SDA
Not use.
23
Serial Data used in the PMBus interface. (Note.2)
24
SCL
Serial Clock used in the PMBus interface. (Note.2)
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms . (Note.2)
High : When the Vout 80% 5%. Low : When Vout 80% 5%. (Note.2)
25
AC-OK
DC-OK
26
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
27
28
29
T-ALARM
FAN-FAIL High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX (pin 31). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
+5V-AUX
Auxiliary voltage output, 10.8~13.2V, referenced to GND-AUX (pin 31). The maximum load current is 0.8A. This output has
the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
30
+12V-AUX
31
32
33
34
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
FG
AC Ground connection.
AC Line connection.
AC/L
AC/N
AC Neutral connection.
Note1: Non-isolated signal, referenced to the output terminals (-V).
Note2: Isolated signal, referenced to GND-AUX.
File Name:RCP-2000-SPEC 2011-05-09
2000W Front End Power Supply
RCP-2000 series
Derating Curve
Static Characteristics
100
90
100
80
80
75
70
230VAC
Input only
12V
60
50
40
65
24V,48V
50
40
20
90
100
115
180
264
(HORIZONTAL)
-40
-25 -10
0
15
30
50
60
70
AMBIENT TEMPERATURE (
)
INPUT VOLTAGE (VAC) 60Hz
EFFICIENCY vs LOAD (48V Model)
DERATING LOAD(%) VS INPUT VOLTAGE
INPUT / VOLTAGE
94
92
90
88
86
84
82
>180VAC
115VAC
100VAC
90VAC
MODEL
100%
100%
95%
80%
90%
75%
80%
65%
RCP-2000-12
RCP-2000-24
RCP-2000-48
100%
80%
75%
65%
10
20
30
40
50
60
70
80
90
100
LOAD
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
Between ON/OFF and +5V-AUX
SW Open
Output
OFF
ON
17
29
ON/OFF
RCP-2000
SW
+5V-AUX
SW Short
2. Voltage Drop Compensation
2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
+S
+V
14
15
RCP-2000
LOAD
-S
-V
-V
Sense lines should be twisted in pairs
File Name:RCP-2000-SPEC 2011-05-09
2000W Front End Power Supply
RCP-2000 series
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
+V
14
+S
RCP-2000
-V
15
-S
3. Output Voltage Trimming
Output voltage can be trimmed between 90~110% of its rated value by the following method.
11
PV
0~5V
RCP-2000
9
-V Signal
Add on 0~5V external voltage
Vout
110
100
90
80
70
60
V
0
0.5
1.5
3
4.5
5
EXTERNAL VOLTAGE (DC)
4. Front Panel Indicators & Corresponding Signal at Function Pins
*
Function
LED
Signal
PSU Output
ON
Description
AC-OK GREEN
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
When input voltage 87V
When input voltage 75V
AC-NG
RED
OFF
ON
DC-OK GREEN
When output voltage 80% 5% of Vo rated.
DC-NG
T-OK
RED
4.5 ~ 5.5V
0 ~ 0.5V
When output voltage 80% 5% of Vo rated.
ON
GREEN
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
ON
T-ALARM RED
4.5 ~ 5.5V
OFF
*Signal between function pin and "GND-AUX".