18AR-56-R/BL [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18AR-56-R/BL
型号: 18AR-56-R/BL
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总4页 (文件大小:128K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18AR  
3: Lo (coil energized at alarm)  
Rack-mounted DCS Signal Conditioners 18-RACK  
4: Lo (coil de-energized at alarm)  
5: Hi/Lo; N.O., OFF in power failure  
(connector output not available)  
6: Hi/Lo; N.C., OFF in power failure  
(connector output not available)  
0: Specify  
RTD ALARM  
Functions & Features  
• Providing relay contact closures at preset input levels  
• Direct input from an RTD  
• Burnout protection  
• Single or dual (Hi/Lo) trip  
POWER INPUT  
DC Power  
• Front-accessed screwdriver setpoint adjustments  
• Enclosed relays  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
Typical Applications  
• Annunciator  
• Various alarm applications  
[3] OPTIONS  
Burnout  
blank: Upscale burnout  
/BL: Downscale burnout  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
Connection  
MODEL: 18AR–[1][2]–R[3]  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Alarm output: M3.5 screw terminals (torque 0.8 N·m) and  
connector  
ORDERING INFORMATION  
• Code number: 18AR-[1][2]-R[3]  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output to power  
Relay: Enclosed  
Specify a code from below for each of [1] through [3].  
(e.g. 18AR-45-R/BL)  
• Temperature range (e.g. 0 – 250°C)  
Use Ordering Information Sheet (No. ESU-1033) to specify  
alarm output code 0 specifications.  
Setpoint adjustments: Multi-turn screwdriver adjustments  
(front); -5 – +105 % independently  
Hysteresis (deadband): Approx. 1 %  
Front LEDs: Red LED turns on when the coil is energized.  
[1] INPUT RTD (2- or 3-wire)  
1: JPt 100 (JIS'89)  
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 30°C, 54°F)  
3: Pt 100 (JIS'89)  
INPUT SPECIFICATIONS  
Maximum leadwire resistance: 20 Ω per wire (3-wire)  
Sensing current: 2 mA (Pt)  
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 30°C, 54°F)  
4: Pt 100 (JIS'97, IEC)  
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 30°C, 54°F)  
5: Pt 50 Ω (JIS'81)  
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 60°C, 108°F)  
6: Ni 508.4 Ω  
(Usable range: -50 to +200°C, -58 to +392°F; min.span: 20°C, 36°F)  
0: Specify  
Note: Consult M-System for 2-wire RTD  
[2] ALARM OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
18AR SPECIFICATIONS  
ES-1764 Rev.5 Page 1/4  
http://www.m-system.co.jp/  
MODEL: 18AR  
OUTPUT SPECIFICATIONS  
Output: Enclosed SPST and SPDT relays  
Rating: 120 V AC @ 1 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
0.2 A maximum for the connector output  
Maximum switching voltage: 120 V AC or 30 V DC  
Max. switching power: 120 VA or 30 W (24 VA or 6 W for the  
connector output)  
Minimum load: 5 V DC @ 10m A  
Mechanical life: 5 × 10 cycles  
7
Single Alarm  
Front terminals  
5 – 6  
ON  
5 – 7  
OFF  
ON  
Energized  
De-energized (or power OFF)  
OFF  
Rear connector  
ALARM  
OUTPUT  
CODE  
POWER ON  
POWER OFF  
IN < SET  
OFF  
IN > SET  
ON  
1
2
3
4
OFF  
ON  
OFF  
ON  
ON  
OFF  
OFF  
ON  
ON  
OFF  
Dual Alarm (front terminals)  
POWER ON  
ALARM  
POWER OFF  
5 – 6 7 – 8  
IN < SET  
IN > SET  
OUTPUT  
CODE  
5 – 6 7 – 8 5 – 6 7 – 8  
5
6
ON  
OFF  
ON  
OFF  
ON  
ON  
OFF OFF  
OFF OFF  
OFF  
OFF  
Shades indicates that the relay is energized.  
INSTALLATION  
Current consumption: Approx. 80 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 150 g (0.33 lb)  
PERFORMANCE in percentage of span  
Trip point repeatability: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)  
Burnout response: ≤ 10 sec.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to output or power)  
500 V AC @ 1 minute (output to power)  
1500 V AC @ 1 minute (input or output or power to ground)  
18AR SPECIFICATIONS  
ES-1764 Rev.5 Page 2/4  
http://www.m-system.co.jp/  
MODEL: 18AR  
EXTERNAL VIEW  
SINGLE ALARM  
DUAL ALARM  
7
8
7
8
Indicator  
Hi Alarm Indicator  
5
1
6
5
1
6
2
High Setpoint Adj.  
Low Setpoint Adj.  
Lo Alarm Indicator  
Setpoint Adj.  
2
3
4
3
4
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
18AR SPECIFICATIONS  
ES-1764 Rev.5 Page 3/4  
http://www.m-system.co.jp/  
MODEL: 18AR  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
SINGLE ALARM  
Relay Protection  
•AC Powered  
8
5
6
7
Burnout  
RTD  
SETPOINT ADJ.  
Comparator  
Inductive  
Load (Coil)  
1
2
3
4
A
B
B
Reference  
Resistor  
COM  
+
Varistor or Spark  
Quenching Circuit  
Differential  
Amplifier  
Ry  
LOAD  
*
*
H
L
OUTPUT  
2mA  
2mA  
U
•DC Powered  
Inductive  
Load (Coil)  
HI / LO  
Output  
Diode, Varistor or  
CR Circuit  
LOAD  
POWER  
DUAL ALARM  
Burnout  
RTD  
SETPOINT ADJ.  
Comparator  
1
2
3
4
A
B
B
*
*
5
6
7
8
Reference  
Resistor  
+
Differential  
Amplifier  
LO OUTPUT  
HI OUTPUT  
Ry  
Ry  
2mA  
2mA  
Comparator  
SETPOINT ADJ.  
POWER  
*Relay status is determined by output codes.  
Specifications are subject to change without notice.  
18AR SPECIFICATIONS  
ES-1764 Rev.5 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY