18PP-622-R [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18PP-622-R
型号: 18PP-622-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总3页 (文件大小:112K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18PP  
Rack-mounted DCS Signal Conditioners 18-RACK  
POWER INPUT  
DC Power  
R: 24 V DC  
PULSE ISOLATOR  
Functions & Features  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
• Galvanically isolating pulse rate signals  
• Input frequency = output frequency  
• Second channel output available at the front terminals  
and at the Standard Rack connector  
• Excitation  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
Connection  
Typical Applications  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output 1: Connector  
• Isolating field pulse signals in order to reduce noises  
Output 2: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output 1 to output 2 to power  
Frequency range: Input and output are the same.  
Chattering protection: Filter provided for mechanical  
contact input  
MODEL: 18PP–[1]22–R  
ORDERING INFORMATION  
• Code number: 18PP-[1]22-R  
Specify a code from below for [1].  
(e.g. 18PP-322-R)  
• Frequency range (e.g. 0 – 1000 Hz)  
[1] INPUT  
1: Mechanical contact (max. 5 Hz)  
2: Open collector (max. 10 kHz)  
3: Voltage pulse (max. 10 kHz)  
4: Two-wire current pulse, receiving resistor 200 Ω  
(max. 10 kHz)  
5: Two-wire current pulse, receiving resistor 510 Ω  
(max. 10 kHz)  
6: Two-wire current pulse, receiving resistor 1 kΩ  
(max. 10 kHz)  
OUTPUT 1  
2: Open collector (max. 10 kHz)  
OUTPUT 2  
2: Open collector (max. 10 kHz)  
(Output 1 and 2 frequency is equal)  
18PP SPECIFICATIONS  
ES-1861 Rev.7 Page 1/3  
http://www.m-system.co.jp/  
MODEL: 18PP  
Convert the current to the voltage for the amplitude.  
INPUT SPECIFICATIONS  
Excitation: 12 V DC ±10 % @ 40 mA; shortcircuit protection  
Open Collector  
OUTPUT SPECIFICATIONS  
Open collector  
Input pulse sensing: DC coupled  
Pulse width time requirement: ≥ 20 μsec. for ON and OFF  
Sensing: Approx. 12 V DC @ 3 mA  
Rating: 30 V DC @ 100 mA (resistive load)  
Maximum frequency: 10 kHz  
Saturation voltage: 0.5 V DC  
ON/OFF level: ≤ 200 Ω / 5 V for ON, ≥ 100 kΩ / 7 V for OFF  
Mechanical Contact  
Input pulse sensing: DC coupled  
INSTALLATION  
Pulse width time requirement: ≥ 20 msec. for ON and OFF  
Sensing: Approx. 12 V DC @ 3 mA  
Current consumption: Approx. 80 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 150 g (0.33 lb)  
ON/OFF level: ≤ 200 Ω / 5 V for ON, ≥ 100 kΩ / 7 V for OFF  
Time constant: 10 msec. (able to cancel it by changing  
jumper, J6)  
Voltage Pulse: Square or sine waveform  
Input pulse sensing: AC coupled  
Input impedance: ≥ 10 kΩ  
PERFORMANCE  
(Refer the graph and tables below for waveform, detection  
level range, the minimum amplitude, pulse width (duty  
ratio) and frequency requirements)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to output 1 or output 2 or power)  
500 V AC @ 1 minute  
Square Waveform  
Pulse width is the smaller of TH or TL.  
(output 1 to output 2 to power)  
1500 V AC @ 1 minute  
Duty ratio = frequency  
× TH × 100 (%)  
(input or output or power to ground)  
TH  
1 – 50Vp-p  
TL  
Sine or similar waveform  
The input frequency range is 10 Hz to 10 kHz.  
1 – 50Vp-p  
0V  
Detection level range: -50 to +50 V; max. 50 Vp-p  
Waveform requirements  
Square Waveform  
FREQUENCY RANGE  
0 to 10 kHz  
AMPLITUDE  
PULSE WIDTH & DUTY RATIO  
1 to 3Vp-p  
Duty 50 10%  
0 to 10 kHz  
Min. 3Vp-p Min. 60 µsec.*  
*When the frequency is 6 kHz or more, the pulse  
width is 30 µsec. or more.  
Sine or similar waveform  
FREQUENCY RANGE  
50 Hz to 10 kHz  
10 Hz to 10 kHz  
AMPLITUDE  
1 to 3Vp-p  
Min. 3Vp-p  
PULSE WIDTH & DUTY RATIO  
-
-
Two-wire Current Pulse  
Input pulse sensing: AC coupled  
Refer to the table above for the minimum amplitude, pulse  
width (duty ratio) and frequency requirements.  
18PP SPECIFICATIONS  
ES-1861 Rev.7 Page 2/3  
http://www.m-system.co.jp/  
MODEL: 18PP  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Isolation  
Weveform  
Shaper  
Output  
Driver  
+
1
2
3
4
7
8
5
+
INPUT  
OUTPUT 2  
6
*
SENSOR EXCITATION  
+
Output  
Driver  
12V Supply  
OUTPUT 1  
OUTPUT 2  
POWER  
*4kΩ attached for mechanical contact and open collector input.  
200Ω, 510Ω or 1kΩ attached for two-wire current pulse input (jumper selectable).  
Specifications are subject to change without notice.  
18PP SPECIFICATIONS  
ES-1861 Rev.7 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

18PR-11-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-12-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-13-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-14-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-21-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-22-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-23-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-24-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A1S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A2

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A2S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM