MODEL: 40DPT
R: 24 V DC
Digital Panel Meters 40 Series
(Operational voltage range 24 V ±20 %, ripple 10 %p-p max.)
AC VOLTAGE INPUT DIGITAL PANEL METER
(4 digit, process meter, true RMS sensing)
Functions & Features
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
• 4 digit (±9999) panel meter
• Scaling and HOLD functions
• High visible, 0.8" (20.3mm) high and bright LED
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
Moving parts and indicators are not coated.
/C01: Silicone coating
96 (3.78)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
48
(1.89)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9537)
96 (3.78)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Connection: M3 screw terminals (torque 0.6 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
MODEL: 40DPT–[1]–[2][3]
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
ORDERING INFORMATION
• Code number: 40DPT–[1]–[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 40DPT-V1-K3/Q)
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to power
Input waveform
• Specify the specification for option code /Q
(e.g. /C01/SET)
RMS sensing: Up to 15 % of 3rd harmonic content
Sampling rate: 10 times/sec. (100 msec.)
Averaging: None or moving average
Setting: (Front button)
[1] INPUT
Voltage
V1: 0.0 - 200.0 mV AC (Conformance range)
(Input range: 0.0 – 240.0 mV AC, Input resistance: ≥100 kΩ)
V2: 0.000 - 2.000 V AC (Conformance range)
(Input range: 0.000 – 2.400 V AC, Input resistance: ≥1 MΩ)
V3: 0.00 - 20.00 V AC (Conformance range)
(Input range: 0.00 – 24.00 V AC, Input resistance: ≥1 MΩ)
V4: 0.0 - 200.0 V AC (Conformance range)
(Input range: 0.0 – 240.0 V AC, Input resistance: ≥1 MΩ)
V5: 0.0 - 400.0 V AC (Conformance range)
(Input range: 0.0 – 480.0 V AC, Input resistance: ≥1 MΩ)
(CE not available)
• Scaled range
• Low-end cutout
• Moving average
• Brightness
• Others
■Recommended solderless terminal
3.3 (.13) max
mm (inch)
[2] POWER INPUT
AC Power
K3: 100 – 120V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz)
L3: 200 – 240V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz)
DC Power
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 1/7
https://www.m-system.co.jp/
MODEL: 40DPT
(input to power to ground)
DISPLAY
Display: 4 digits of 20.3 mm (0.8 inch) height, 7-segment,
red LED
STANDARDS & APPROVALS
EU conformity:
Display range: -9999 to 9999
Scaling range: -9999 to 9999 counts
EMC Directive
Decimal point position: 10-1, 10-2, 10-3 or none
Zero indication: Higher-digit zeros are suppressed.
Over-range indication: '-9999' or '9999' blinking for display
values out of the display range. 'S.ERR' blinks surpassing
the permissible range. 'ERR' blinks when input scaling
setting is inappropriate.
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category I (input)
Installation Category II (power)
Pollution degree 2
Engineering unit indication: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
Input to power: Reinforced insulation (300 V)
RoHS Directive
m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec,
m3
/min, m
3
/h, Nm /h, N·m, N/m , g, kg, kg/h,
3
2
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.
INPUT SPECIFICATIONS
■ AC Input voltage
Frequency: 40 - 100 Hz
Overload capacity: 120 % of max. measurement range
(continuous)
• V1 Max. input: 10 V
• V2 Max. input: 100 V
• V3, V4, V5 Max. input: 500 V
Input burden: ≤ 0.5 VA
■ Hold Input: Dry contact input
Detecting level: ≤ 1.5 V
Sensing: Approx. 5 V DC, 1 mA
INSTALLATION
Power consumption
•AC:
≤ 2.7 VA for 100 – 120 V
≤ 3.4 VA for 200 – 240 V
•DC: ≤ 1.0 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 180 g (0.40 lb)
PERFORMANCE
Input accuracy: ±0.3% rdg ±1digit,
< 35 % of full scale: ±0.3% FS ±1digit
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Line voltage effect: ±0.2 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 2/7
https://www.m-system.co.jp/
MODEL: 40DPT
DISPLAY HOLD COMMAND
Displayed value is held with an external HOLD command input. Connect the contacts across HOLD to COM.
(Isolate with photo-coupler or relay as terminals 3 and 4 are not isolated to input signal, terminals 1 and 2.)
(a)
Photo-Coupler
HOLD
H
L
4
3
HOLD
COM
Photo-Coupler
Twisted pair cable
(b)
Relay
HOLD
H
L
4
3
HOLD
COM
Relay
Twisted pair cable
EXTERNAL VIEW
(1) Front Panel
(3) 4-digit Display
(4) Polarity Indicator
(8) Up Button
(5) Disp/ Button
(6) Scale/ Button
(2) Sticker Label
(7) Shift Button
■ FUNCTION TABLE
No.
(1)
(2)
(3)
(4)
(5)
COMPONENT
Front panel
FUNCTIONS
Removed at configuration.
Engineering unit label position
Sticker label
4-digit display
Polarity indicator
Disp/ ↓ button
4-digit LED display. Range: 0 to 9999 (not including decimal point)
Turns on when negative value is displayed.
Used to move on to the display setting modes, to shift through setting items in each setting mode,
or shift through display digits in each setting item.
(6)
Used to move on to the scaling setting modes, to shift through setting items in each setting mode,
or shift through display digits in each setting item.
Scale/ ↑ button
(7)
(8)
Shift button
Up button
Used to move on to the setting standby status.
Used to select setting value.
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 3/7
https://www.m-system.co.jp/
MODEL: 40DPT
PARAMETER LIST
■ SCALING SETTING MODE
ITEM
DISPLAY
DEFAULT
VALUE
INPUT
CODE
DISPLAY
4th LSD – 2nd LSD, none Decimal point position
PARAMETER
FUNCTION
V1
V2
V3
V4
V5
V1
V2
V3
V4
V5
V1
V2
V3
V4
V5
V1
V2
V3
V4
V5
V1
V2
V3
V4
V5
Decimal Point Position
–
–
Input value to be set as Zero
in the measurement range
Input Scaling Value A
Input Scaling Value B
Display Scaling Value A
1
*
)
(
(
–
–
Input value to be set as Full
Scale in the measurement
range
1
*
)
–
–
Display value for input
scaling value A
Display value for input
scaling value B
Display Scaling Value B
2
*
Low-end cutout OFF
Low-end cutout
–
Low-end cutout ON
Absolute value low-end cutout ON
Low-end cutout value setting
2
*
–
Low-end cutout value
–
*1. Only for input code ‘V5’
*2. Input signal less than the preset cutout value is forcibly cut to display scaling value “zero”.
Use when minus value is not required. Lower 3 digits of displayed value are set regardless of decimal point position.
Note: With the low-end cutout or absolute value low-end cutout set to ON, the low-end cutout value setting is valid.
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 4/7
https://www.m-system.co.jp/
MODEL: 40DPT
• Input scaling
Zero and full scale of input range can be re-configured to user's desired value by entering parameters.
When initialization of setting is executed, these data is lost and return to the default value.
Input Scaling Value A:
Input value for zero point
(Input scaling value A < Input scaling value B)
Enter the value you want to set to zero in the measurement range.
Input Scaling Value B: Input value for full scale point
Enter the value you want to set to full scale in the measurement range.
• Display scaling
Display Scaling Value A:
Display Scaling Value B:
Display value for Input Scaling Value A
Display value for Input Scaling Value B
• Normal Scaling
The display value increases when the input signal increases.
• Inverted Scaling
The display value decreases when the input signal increases.
Display
Display
Full Scale
B
Zero
A
Display Scaling
Display Scaling
Zero
A
Full Scale
B
Input
Input
A
B
A
B
Input Scaling
Input Scaling
Decimal point position: Decimal point position is specified independently from the scaling. When you set the display scaling, include zeros
for fractions.
■ DISPLAY SETTING MODE
DEFAULT
VALUE
PARAMETER
ITEM DISPLAY
DISPLAY
FUNCTION
No moving averaging
Moving Average
Moving average with 2 samples
Moving average with 4 samples
Moving average with 8 samples
Moving average with 16 samples
Brightness level 0 (dark)
Brightness level 1
Brightness
Brightness level 2
Brightness level 3
Brightness level 4
Brightness level 5 (bright)
Non-initialization
Initialization
Initialize settings (change to factory settings) *1
Version number, indication only
−
Version Indication
–
–
*1. While “on” is shown, pressing Shift button initializes settings.
When initialization of setting is executed, existing each parameter setings are lost and return to default value.
Be aware that settings does not return to the ex-factory settings specied by /SET option.
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 5/7
https://www.m-system.co.jp/
MODEL: 40DPT
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ TOP VIEW
92 (3.62)
■ FRONT VIEW
■ SIDE VIEW
103 (4.06)
96 (3.78)
96 (3.78)
85 (3.35)
11
(.43)
12 (.47)
■ REAR VIEW
10–M3 SCREW
TERMINALS
6.4 (.25)
1
2
3
4
5
6
7
8
9
10
MOUNTING REQUIREMENTS unit: mm
92 +– 00.8
min. 120
Panel thickness: 1.6 to 8.0 mm
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 6/7
https://www.m-system.co.jp/
MODEL: 40DPT
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SOURCE
VT
Fuse
U
V
u
v
1
2
3
4
9
10
5
U(+)
V(–)
POWER
Fuse
A/D
Converter
COM
LOAD
Digital
Computation
6
HOLD
7
Display /
Setting
8
Specifications are subject to change without notice.
40DPT SPECIFICATIONS
ES-9537 Rev.7 Page 7/7
https://www.m-system.co.jp/