51U-4A4-M3 [MSYSTEM]

Panel Mounted Multi Power Meter 51-UNIT;
51U-4A4-M3
型号: 51U-4A4-M3
厂家: M-SYSTEM    M-SYSTEM
描述:

Panel Mounted Multi Power Meter 51-UNIT

文件: 总16页 (文件大小:299K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Panel Mounted Multi Power Meter 51-UNIT  
MODEL  
MULTI POWER METER  
51U  
MODEL & SUFFIX CODE SELECTION  
110 (4.33)  
51U–❑❑❑  
R
S
T
MODEL  
A
V
INPUT (balanced load) *1  
R-S  
S-T  
T-R  
110  
(4.33)  
2
0 : Single-phase / 2-wire, 105V / 5AAC (P. 5/16)  
*
x1kW  
x10kW  
1 : Single-phase / 3-wire, 105V / 210V / 5AAC (P. 7/16)  
2 : 3-phase / 3-wire, 220V / 5A AC (P. 10/16)  
3 : 3-phase / 3-wire, 110V / 5A AC (P. 10/16)  
4 : 3-phase / 4-wire, 110V / 3 V / 5A AC (P. 13/16)  
DISPLAY ITEMS *3  
DISPLAY  
126  
(4.96)  
mm (inch)  
Functions & Features  
A : A × 3  
B : V × 3  
C : A × 3, V × 3  
D : A × 3, V × 3, kW  
E : A × 3, V × 3, kWh  
F : A × 3, kW, kWh  
G : Hz, PF, kvar  
H : V × 3, MV  
• Measuring all major factors required for power &  
energy management • Transducer combined with  
3 displays in one enclosure • RS-485 or DC current  
output • Totalized counter values stored in non-vola-  
tile memory • Occupying less panel space, requir-  
ing fewer connection• Easily replacing standard 110  
mm (4 /16 in.) square size, long scale meter • Pa-  
rameters are field-selectable  
Application Examples  
5
0
, V0  
J : A × 3, DA, MDA  
K : A × 3 or DA, MDA, alarm setpoint  
L : Hz, PF, kW  
M : PF, kW, kWh  
• Updating conventional power meter to a remote  
controlled power logger, only with additional trans-  
mitter output wiring • Installed within an indus-  
trial piece of electrical equipment  
N : V × 3, kW, kWh  
P : A × 3 or DA or MDA, V × 3, kWh  
Q : A × 3, PF, kW  
R : A × 3, PF, kvar  
S : A × 3 or PF, kW, kWh  
T : A × 3, PF, kvarh  
U : V × 3, Hz  
*1 : Some display items or output types are not selectable  
according to the input type. See the detailed selection  
guide in the following pages.  
*2 : Page No. of the detailed selection guide  
*3 : V = Line voltage  
kW = Kilowatt  
A = Line current  
kvar = Kilovar  
W : A × 3 or DA or MDA, V × 3, alarm setpoint  
X : A × 3, kvar, kvarh  
Y : Hz, PF, kWh  
OUTPUT  
0 : None  
1 : 4 – 20mA DC, 3 points  
2 : 4 – 20mA DC, 2 points + pulse  
3 : 4 – 20mA DC, 2 points + reset input  
4 : RS-485 (MsysNet use only. Consult Factory.)  
AUXILIARY POWER SUPPLY  
M : 85 – 264V AC  
PF = Power factor  
kWh = Kilowatthours  
DA = Demand (current)  
MDA = Maximum demand (current)  
V0 = Zero-phase voltage  
Hz = Frequency  
kvarh = Kilovarhours  
MV0 = Maximum zero-phase voltage  
DEFAULT SETTING  
ITEM  
DEFAULT SETTING  
CT primary rating  
5.00A (element S for demand,  
time lag 15 min.)  
R : 24V DC  
P : 110V DC  
VT primay rating  
GVT tertiary rating  
110.0V or 220.0V, same as input rating  
110.0V  
REMOTE CONTROL  
Frequency range  
45 – 65 Hz  
Pulse out. scaling factor 1 kWh/pulse (kvarh/pulse)  
Demand alarm setpoint 100%  
1 : 85 – 132V AC or 85 – 143V DC  
2 : 20 – 30V DC  
RS-485  
Address: 01  
Transmission speed: 4800 bps  
3 : 170 – 264V AC  
P. 1 / 16 ES-6481 Rev.9  
51U  
PULSE OUTPUT: totalizing watt in forward flow or  
var in lag.  
Scaling factor: 0.01, 0.1, 1, 10, 100 kWh/pulse  
(default: 1)  
Contact rating: 110V DC @0.1A (resistive load)  
110V AC @0.1A (resistive load)  
Pulse width time: 100 – 150 msec.  
(pulse rate 12000 pulses/h)  
GENERAL SPECIFICATIONS  
Construction: 110 mm-square (4 5/16 in.) panel  
surface, cylindric body  
Connection  
Input & auxiliary power: M4 screw terminals  
Output: M3 screw terminals  
Housing material: plastic (black)  
Isolation: input to output to power; not isolated  
between analog outputs  
TRANSMISSION OUTPUT (Multi-Meter Protocol)  
Transmission: conform to RS-485, EIA  
Transmission distance: 1 kilometer max. (31 units)  
Scaling:  
primary values for CT and VT; tertiary  
value for GVT (Inform M-System CT and  
VT ratios when ordering.)  
5 – 8000A (up to 15000A for Code K)  
110 – 77kV  
Cable:  
shielded twisted-pair cable (CPEV-S 0.9 dia.)  
CT:  
VT:  
Terminator: incorporated  
GVT:  
63.5 – 190.5V  
DEMAND ALARM CONTACT OUTPUT  
Alarm setpoint: 5 – 100%; adjustable in 0.5% incre-  
ments  
Contact rating: 110V DC @0.1A (resistive load)  
ON resistance: 50Ω  
Time lag for demand: 0 sec., 30 sec. or 1, 2, 3, 5, 7,  
10, 15, 30 min. (default: 15 min.)  
Sampling cycle: 400 µsec. (DO NOT connect a  
device such like inverters.)  
Measurable frequency ranges: 45 – 44 Hz, 55 – 65  
Hz, 45 – 65 Hz  
Low-end cutout: Display shows 0 for the input less  
than the following: approx. 1% for current,  
watt and var; approx. 3% for voltage.  
I/O RANGES  
Proportional to 4 – 20mA DC  
DISPLAY ITEMS  
Current  
RATING  
5A  
INPUT RANGE  
0 – 5A  
INPUT  
Voltage 1ø / 2w 1 – 2 105V  
0 – 150V  
VOLTAGE INPUT  
(must be balanced with 3-phase connection)  
Operational range  
1ø / 3w 1 – N 105V  
2 – N 105V  
0 – 150V  
0 – 150V  
0 – 300V  
1 – 2 210V  
Voltage, watt, var, zero-phase voltage: 0 – 100% of rat-  
ing  
3ø / 3w line  
110V  
220V  
0 – 150V  
0 – 300V  
Power factor: 30V  
Frequency: 30V  
3ø / 4w line  
110V  
0 – 150V  
phase 110 / 3 V 0 – 150 / 3 V  
Watt  
Var  
110V / 5A 0 – 1 kW (0 – 5 kW)  
110V / 5A -1 – +1 kW (-0.5 – +0.5 kW)  
220V / 5A 0 – 2 kW  
Overload capacity: 200% of rating for 60 sec.,  
115% for 3 hours  
Input burden: 0.3VA/phase  
220V / 5A -2 – +2 kW  
110V / 5A 0 – lag1 kvar  
(0 – lag500 var)  
110V / 5A lead1 – lag1 kvar  
(lead500 – lag 500 var)  
CURRENT INPUT  
(may be unbalanced with 3-phase connection)  
Operational range  
220V / 5A 0 – lag2 kvar  
220V / 5A lead2 – lag2 kvar  
Current, watt, var, demand: 0 – 100% of rating  
Power factor: 5% of rating  
Overload capacity: 4000% of rating for 1 sec., 2000%  
for 60 sec., 115% for 3 hours  
Power factor  
Frequency  
––  
––  
lead 50 – 100 – lag 50 %  
45.0 – 55.0 Hz  
55.0 – 65.0 Hz  
45.0 – 65.0 Hz  
Input burden: 0.1VA/phase  
Max. zero-phase voltage 63.5V  
0 – 86.6V  
0 – 150.0V  
0 – 259.8V  
REMOTE CONTROL  
110.0V  
190.5V  
Display switching: same functions as the front  
DISPLAY button does; input time 0.3  
sec., input current 5mA  
Reset input: max. zero-phase voltage and demand;  
input time 0.3 sec., input current 5mA  
Demand  
5A  
5A  
0 – 5A, element S  
0 – 5A, element S  
Maximum demand  
Remarks:  
1) Values for single-phase connection in brackets.  
2) Displays are automatically scaled according to the scal-  
ing factor settings for VT and CT.  
3) Reverse or lead flow are displayed with the negative (–)  
indicator.  
OUTPUT  
CURRENT OUTPUT: 4 – 20mA DC  
Load resistance: 500maximum  
Specifications subject to change without notice.  
P. 2 / 16 ES-6481 Rev.9  
INSTALLATION  
FRONT PANEL CONFIGURATION  
Auxiliary power supply  
The front display configuration varies according to  
model numbers (display items).  
AC:  
DC:  
operational voltage range 85 – 264V,  
50/60 Hz, approx. 5.5VA  
operational voltage range for R: 24V ±10%  
or P: 85 – 143V; ripple 10% p-p max.;  
approx. 5.5W (approx. 230mA at 24V)  
A
R
C
S
T
A
V
A
A
R – S  
S – T  
T – R  
D
Operating temperature: -10 to +50°C (14 to 122°F)  
Operating humidity: 30 to 85% RH (non-condensing)  
Grounding: grounding resistance 100Ω  
B
x
1 kWh  
x
10 kWh  
Mounting: panel flush mounting  
Dimensions: W110×H110×D126 mm (4.33"×4.33"×4.96")  
DISPLAY  
DISPLAY  
Weight:  
500 g (1.10 lbs)  
S.R.  
A
V RESET  
PERFORMANCE in percentage of span  
Accuracy  
Voltage, current: ±1.0%  
Watt, var: ±1.5%  
Power factor: ±3.0%  
Frequency: ±0.5%  
Demand: ±1.5%  
Zero-phase voltage: ±1.5%  
E F G H  
J
A. Display  
LED:  
Display items:  
10 mm (.39") 7 segment, orange  
NO. OF  
DIGITS  
DISPLAY ITEMS  
REMARKS  
Current  
Voltage  
Watt  
A (1, N, 2)  
A (R, S, T)  
4
4
Single-phase / 3-wire  
3-phase / 3-wire or 4-wire  
Max. zero-phase voltage: ±1.5%  
Watthours: ±2.0% (load current 5 – 100%, power factor 1.0)  
±2.5% (load current 10 – 100%, power  
factor 0.5, lag current)  
V (RS, ST, TR)  
4
4
3-phase / 3-wire or 4-wire  
3-phase / 4-wire  
V
(RN, SN, TN)  
kW  
4
– indicator (reverse flow),  
×1, ×10 scaling factor ind. LED  
×1, ×10, ×100 scaling factor LED  
Varhours: ±2.5% (load current 10 – 100%, power factor 0)  
±2.5% (load current 20 – 100%, power factor 0.866)  
±3.0% (load current 10%, power factor 0.866)  
Temp. conditioning incl. in the accuray: 23 ±10°C  
(73.4 ±18°F)  
Watthours kWh  
5
4
Var  
kvar  
– indicator (lead),  
×1, ×10 scaling factor ind. LED  
×1, ×10, ×100 scaling factor LED  
– indicator (lead)  
Varhours  
Power factor  
Frequency  
kvarh  
5
3
3
Freq. conditioning incl. in the accuracy: 45 – 65 Hz  
Response time: ≤2 sec. (0 – 100% ±1%)  
PF  
Hz  
Ripple:  
0.5% p-p max.  
Zero-phase voltage V0  
Max. zero-phase volt. MV0  
4
4
4
Auxiliary supply voltage effect: ±0.1% over voltage  
range  
Demand  
DA  
Measuring/displaying  
preset element only  
Power failure protection: VT/CT scaling factors,  
watthours, max. zero-phase voltage and  
demand are stored in non-volatile memory.  
Insulation resistance: 100Mwith 500V DC  
Dielectric strength: 2000V AC @1 minute  
(voltage input to current input to trans-  
mission section to display switch input to  
aux. power to ground terminal)  
Max. demand  
MDA  
4
When values exceed the preset values, corresponding LEDs blink.  
B. Multiplication factor: watt, watthours, var or  
varhours on the display (A)  
C. Line current indicators: Pressing DISPLAY (J) or  
"A" (F) button changes lines (elements).  
D. Line current indicators: Pressing DISPLAY (J) or  
"V" (G) button changes lines.  
2000V AC @1 minute  
(circuit to ground terminal; not applica-  
ble to analog or transmission terminal)  
Surge withstand voltage: 1.2/50 µsec., ±4.5kV  
(input to output or ground; not applica-  
ble to analog or transmission terminal)  
E. Primary rating: indicating the primary rating of  
current, voltage, watt or demand  
F. Line current switch  
G. Line voltage switch  
H. Reset: resetting the max. zero-phase voltage or  
max. demand; same as the external reset  
input via output terminals  
J. Display: changing display items, turning the light  
on or off; same as the Dis. input via  
output terminals  
P. 3 / 16 ES-6481 Rev.9  
51U  
EXTERNAL DIMENSIONS mm (inch)  
SINGLE-PHASE / 2-WIRE or 3-WIRE, 3-PHASE / 3-WIRE CONNECTION  
35 (1.38)  
110 ±1 (4.33 ±.04)  
73 ±1 (2.87 ±.04)  
19  
M4 SCREW  
18  
(.71)  
(.75)  
8(.31)  
8(.31)  
6(.24)  
M5 SCREW  
M3 SCREW  
3-PHASE / 4-WIRE CONNECTION  
35 (1.38)  
110 ±1 (4.33 ±.04)  
73 ±1 (2.87 ±.04)  
19  
M4 SCREW  
18  
(.71)  
(.75)  
8(.31)  
8(.31)  
6(.24)  
16  
(.63)  
M5 SCREW  
M3 SCREW  
MOUNTING REQUIREMENTS mm (inch)  
PANEL CUTOUT  
90 ±0.5  
(3.54 ±0.2)  
102  
+1  
0 dia.  
2– 6 (.24) dia.  
160 (6.30) min.  
Panel Thickness: 1 to 5.5 mm (.04 – .22 in.)  
Specifications subject to change without notice.  
P. 4 / 16 ES-6481 Rev.9  
MODEL  
SINGLE-PHASE / 2-WIRE CONNECTION  
51U-0  
MODEL & SUFFIX CODE SELECTION  
CONNECTION DIAGRAM  
51U–0❑  
MODEL  
P
N
E
INPUT (balanced)  
0 : Single-phase / 2-wire, 105V / 5A AC  
DISPLAY ITEMS  
Power  
V1 V2 V3 1S 1L 3S 3L  
Input  
C : A, V  
Output  
D : A, V, kW  
E : A, V, kWh  
CH1  
CH2  
CH3  
Dis  
F : A, kW, kWh  
J : A, DA, MDA  
K : A or DA, MDA, alarm setpoint  
N : V, kW, kWh  
POWER  
DC or AC  
POWER  
P : A or DA or MDA, V, kWh  
U : V, Hz  
W : A or DA or MDA, V, alarm setpoint  
P
N
E
V = Line voltage  
kW = Kilowatt  
Hz = Frequency  
A = Line current  
kWh = Kilowatthours  
INPUT  
CT  
K
L
1
k
l
2
DA = Demand (current)  
MDA = Maximum demand (current)  
OUTPUT (selectable display items codes)  
0 : None (J K W with reset input)  
1 : 4 – 20mA DC, 3 points (C D U)  
2 : 4 – 20mA DC, 2 points + pulse (E F N P)  
3 : 4 – 20mA DC, 2 points + reset input (J)  
4 : RS-485 (all codes selectable except K W)  
AUXILIARY POWER SUPPLY  
M : 85 – 264V AC  
1S  
V1  
1L  
V2  
Suffix Codes  
C, D, E, F, N, P, W  
V1  
V1  
V2  
V2  
1S  
1S  
1L  
1L  
J, K (measuring current only)  
U (measuring voltage only)  
OUTPUT  
R : 24V DC  
P : 110V DC  
REMOTE CONTROL  
Without Outputs  
4 – 20mA DC, 3 points  
(See the following pages.)  
Dis.  
4 – 20mA DC, 2 points  
+ pulse 1 point  
(See the following pages.)  
1 : 85 – 132V AC or 85 – 143V DC  
2 : 20 – 30V DC  
3 : 170 – 264V AC  
POWER  
POWER  
DISPLAY  
RS-485  
SIWTCHING  
4 – 20mA DC, 2 points  
+ reset input  
(See the following pages.)  
Dis.  
ORDERING INFORMATION  
Specify code number. (e.g. 51U-0D4-M1)  
+
SL  
Ter  
TERMINATOR  
DISPLAY  
SWITCHING  
Close across the terminator  
when the unit is located at  
the end of transmission line.  
RS-485  
P. 5 / 16 ES-6481 Rev.9  
51U  
DISPLAY ITEMS & OUTPUTS  
Items shown in brackets can be displayed when you change settings.  
Suffix Code: C  
Suffix Code: D  
Suffix Code: E  
Suffix Code: F  
A
V
A
V
A
V
A
x1 kW  
x10 kW  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x1 kW  
x
x
x10 kW  
x
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
CH1  
CH2  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
CH1  
CH2  
ITEMS  
TERM.  
CH1  
CH2  
CH3 0 – 0.5 kW  
(-0.5 – +0.5 kW)  
ITEMS  
TERM.  
CH1  
CH2  
ITEMS  
TERM.  
ITEMS  
A
V
A
V
A
V
CH1  
A
CH2 0 – 0.5 kW  
(-0.5 – +0.5 kW)  
PULSE kWh  
Dis. Display switch. inp.  
PULSE kWh  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: J  
Suffix Code: K  
Suffix Code: N  
Suffix Code: P  
A
DA  
A
DA  
MDA  
A
V
DA  
MAX  
x1 kW  
A
A
V
x10 kW  
MDA  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
ALARM  
SET  
x
x
A
A
x
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
CH1  
CH2  
RESET  
Dis.  
ALARM RESET  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
CH1  
CH2  
CH1/CH2 (DA, MDA)  
PULSE kWh  
ITEMS  
CH1  
CH2 DA (MDA)  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
A
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
CH1  
V
A
V
CH2 0 – 0.5 kW  
(-0.5 – +0.5 kW)  
CH1/CH2 (A)  
PULSE kWh  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: U  
Suffix Code: W  
V
A
Hz  
V
ALARM  
SET  
A
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
+
+
CH1  
CH2  
Dis.  
ALARM RESET  
Dis.  
TERM.  
ITEMS  
TERM.  
ITEMS  
CH1  
V
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
CH2 Hz  
Dis. Display switch. inp.  
Specifications subject to change without notice.  
P. 6 / 16 ES-6481 Rev.9  
MODEL  
SINGLE-PHASE / 3-WIRE CONNECTION  
51U-1  
MODEL & SUFFIX CODE SELECTION  
CONNECTION DIAGRAM  
51U–1❑  
MODEL  
P
N
E
INPUT (balanced)  
Power  
1 : Single-phase / 3-wire, 105V / 210V / 5AAC  
DISPLAY ITEMS  
V1 V2 V3 1S 1L 3S 3L  
Input  
A : A × 3  
Output  
B : V × 3  
C : A × 3, V × 3  
CH1  
CH2  
CH3  
Dis  
D : A × 3, V × 3, kW  
E : A × 3, V × 3, kWh  
F : A × 3, kW, kWh  
J : A × 3, DA, MDA  
K : A × 3 or DA, MDA, alarm setpoint  
L : Hz, PF, kW  
POWER  
DC or AC  
POWER  
P
N
E
M : PF, kW, kWh  
N : V × 3, kW, kWh  
P : A × 3 or DA or MDA, V × 3, kWh  
Q : A × 3, PF, kW  
S : A × 3 or PF, kW, kWh  
U : V × 3, Hz  
INPUT  
CT  
K
L
1
k
l
N
2
K
L
k
l
W : A × 3 or DA or MDA, V × 3, alarm setpoint  
Y : Hz, PF, kWh  
1S  
V1  
1L  
VN  
2S  
V2  
2L  
V = Line voltage  
kW = Kilowatt  
PF = Power factor  
DA = Demand (current)  
A = Line current  
kWh = Kilowatthours  
Hz = Frequency  
Suffix Codes  
C, D, E, F, L, M, N, P, Q, S, W, Y V1 VN V2  
A, J, K (measuring current only)  
1S  
1S  
1L  
1L  
2S  
2S  
2L  
2L  
MDA = Maximum demand (current)  
B, U (measuring voltage only)  
V1 VN V2  
OUTPUT (selectable display items codes)  
0 : None (J K W with reset input)  
1 : 4 – 20mA DC, 3 points (A B C D L Q U)  
2 : 4 – 20mA DC, 2 points + pulse (E F M N P)  
3 : 4 – 20mA DC, 2 points + reset input (J)  
4 : RS-485 (all codes selectable except K W)  
AUXILIARY POWER SUPPLY  
M : 85 – 264V AC  
R : 24V DC  
P : 110V DC  
REMOTE CONTROL  
1 : 85 – 132V AC or 85 – 143V DC  
2 : 20 – 30V DC  
OUTPUT  
Without Outputs  
4 – 20mA DC, 3 points  
(See the following pages.)  
Dis.  
4 – 20mA DC, 2 points  
+ pulse 1 point  
(See the following pages.)  
POWER  
POWER  
DISPLAY  
SIWTCHING  
RS-485  
4 – 20mA DC, 2 points  
+ reset input  
(See the following pages.)  
Dis.  
+
SL  
Ter  
TERMINATOR  
DISPLAY  
SWITCHING  
Close across the terminator  
when the unit is located at  
the end of transmission line.  
RS-485  
3 : 170 – 264V AC  
ORDERING INFORMATION  
Specify code number. (e.g. 51U-1D4-M1)  
P. 7 / 16 ES-6481 Rev.9  
51U  
DISPLAY ITEMS & OUTPUTS  
Items shown in brackets can be displayed when you change settings.  
Suffix Code: A  
Suffix Code: B  
Suffix Code: C  
Suffix Code: D  
1
N
2
1 – N  
2 – N  
1 – 2  
1
N
2
1
N
2
A
A
A
V
V
V
A
V
A
V
1 – N  
2 – N  
1 – 2  
1 – N  
2 – N  
1 – 2  
x1 kW  
x10 kW  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
Dis.  
CH1  
CH2  
CH3  
Dis.  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
ITEMS  
, A  
1N (V2N, V12  
TERM.  
CH1  
CH2  
CH3 0 – 1 kW  
(-1 – +1 kW)  
ITEMS  
, A  
1N (V2N, V12)  
A
A
A
1
V
V
V
1N  
2N  
12  
A
V
1
(A  
N
2)  
A
V
1
(A  
N
2)  
N
2
)
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: E  
Suffix Code: F  
Suffix Code: J  
Suffix Code: K  
1
1
1
1
N
N
N
N
2
DA  
A
A
A
A
2
2
2
1 – N  
2 – N  
DA 1  
N
x1 kW  
MAX  
V
A
A
1 – 2  
x10 kW  
2
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
MDA  
ALARM  
SET  
x
x
A
A
x
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
RESET  
Dis.  
ALARM RESET  
Dis.  
TERM.  
CH1  
CH2  
ITEMS  
, A  
1N (V2N, V12  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
TERM.  
ITEMS  
A
V
1
(A  
N
2)  
CH1  
A1  
(A  
N
2
)
CH1  
CH2 DA (MDA)  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
A1  
(A  
N, A  
2)  
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
)
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
PULSE kWh  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: L  
Suffix Code: M  
Suffix Code: N  
Suffix Code: P  
1 – N  
2 – N  
1
N
2
A
DA  
MDA  
Hz  
%
%
V
1 – 2  
1 – N  
2 – N  
1 – 2  
x1 kW  
x1 kW  
V
x10 kW  
x10 kW  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x1 kW  
x
x
x
x10 kW  
x
x
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
CH1 PF  
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
Dis. Display switch. inp.  
ITEMS  
TERM.  
ITEMS  
TERM.  
CH1  
CH2  
ITEMS  
, A  
1N (V2N, V12)  
CH1 Hz  
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
Dis. Display switch. inp.  
CH1  
V
1N (V2N, V12  
)
A
V
1
(A  
N
2)  
CH2 0 – 1 kW  
(-1 – +1 kW)  
, A , A  
PULSE kWh  
Dis. Display switch. inp.  
CH1/CH2 (DA, MDA)  
PULSE kWh  
Dis. Display switch. inp.  
CH1/CH2 (A  
1
N
2)  
Specifications subject to change without notice.  
P. 8 / 16 ES-6481 Rev.9  
Suffix Code: Q  
Suffix Code: S  
Suffix Code: U  
Suffix Code: W  
1
N
2
1
N
2
A
1 – N  
2 – N  
1 – 2  
1
N
2
A
%
DA  
MDA  
A
V
1 – N  
2 – N  
1 – 2  
x1 kW  
x10 kW  
%
Hz  
V
x
1
kWh  
10 kWh  
100 kWh  
ALARM  
SET  
x1 kW  
x
A
x10 kW  
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
Dis.  
ALARM RESET  
Dis.  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
TERM.  
ITEMS  
CH1  
A1  
(AN  
2
)
CH1  
A1  
(AN  
2
)
CH1  
V
1N (V2N, V12  
)
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
CH2 0 – 1 kW  
(-1 – +1 kW)  
CH1/CH2 (PF)  
CH2 Hz  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
PULSE kWh  
Dis. Display switch. inp.  
Suffix Code: Y  
Hz  
%
x
1
kWh  
10 kWh  
100 kWh  
x
x
DISPLAY  
Output Connection  
+
+
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
CH1 Hz  
CH2 PF  
PULSE kWh  
Dis. Display switch. inp.  
P. 9 / 16 ES-6481 Rev.9  
51U  
MODEL  
THREE-PHASE / 3-WIRE CONNECTION  
51U-2 / 51U-3  
MODEL & SUFFIX CODE SELECTION  
ORDERING INFORMATION  
Specify code number. (e.g. 51U-2D4-M1)  
51U–❑❑❑  
MODEL  
CONNECTION DIAGRAM  
INPUT (balanced)  
2 : Three-phase / 3-wire, 220V / 5A AC  
3 : Three-phase / 3-wire, 110V / 5A AC  
DISPLAY ITEMS  
P
N
E
Power  
A : A × 3  
B : V × 3  
V1 V2 V3 1S 1L 3S 3L  
Input  
C : A × 3, V × 3  
Output  
D : A × 3, V × 3, kW  
E : A × 3, V × 3, kWh  
F : A × 3, kW, kWh  
G : Hz, PF, kvar  
CH1  
CH2  
CH3  
Dis  
H : V × 3, MV  
J : A × 3, DA, MDA  
0
, V  
0
POWER  
DC or AC  
POWER  
K : A × 3 or DA, MDA, alarm setpoint  
L : Hz, PF, kW  
M : PF, kW, kWh  
P
N
E
N : V × 3, kW, kWh  
INPUT  
P : A × 3 or DA or MDA, V × 3, kWh  
Q : A × 3, PF, kW  
R : A × 3, PF, kvar  
S : A × 3 or PF, kW, kWh  
T : A × 3, PF, kvarh  
CT  
K
L
R
S
T
R
S
T
k
l
K
L
k
l
U
u
V V  
U
u
U
u
V
v
W
O
O
VT  
GVT  
v v  
w
a
f
1S  
U : V × 3, Hz  
V1  
1L  
V1  
V2  
3S  
V2  
V3  
3L  
V3  
W : A × 3 or DA or MDA, V × 3, alarm setpoint  
X : A × 3, kvar, kvarh  
Y : Hz, PF, kWh  
Suffix Codes  
V1 V2 V3 1S 1L 3S 3L  
C, D, E, F, G, L, M, N, P, Q, R, S, T, W, X, Y  
V = Line voltage  
kW = Kilowatt  
PF = Power factor  
A = Line current  
kvar = Kilovar  
Hz = Frequency  
V1 V2 V3 G1 G4  
H (measuring max. zero-phase voltage)  
1S 1L 3S 3L  
220V AC can be directly connected  
to V1, V2 and V3 terminals without  
VT.  
kWh = Kilowatthours kvarh = Kilovarhours  
DA = Demand (current)  
MDA = Maximum demand (current)  
V0 = Zero-phase voltage  
A, J, K (measuring current only)  
V1 V2 V3  
B, U (measuring voltage only)  
OUTPUT  
MV0 = Maximum zero-phase voltage  
Without Outputs  
4 – 20mA DC, 3 points  
(See the following pages.)  
Dis.  
OUTPUT (selectable display items codes)  
0 : None (H J K W with reset input)  
1 : 4 – 20mA DC, 3 points (A B C D G L Q R U)  
2 : 4 – 20mA DC, 2 points + pulse  
(E F M N P S T X Y)  
3 : 4 – 20mA DC, 2 points + reset input (H J)  
4 : RS-485 (all codes selectable except K W)  
AUXILIARY POWER SUPPLY  
M : 85 – 264V AC  
4 – 20mA DC, 2 points  
+ pulse 1 point  
(See the following pages.)  
POWER  
DISPLAY  
SIWTCHING  
RS-485  
4 – 20mA DC, 2 points  
+ reset input  
(See the following pages.)  
Dis.  
+
SL  
Ter  
POWER  
Close across the terminator  
when the unit is located at  
the end of transmission line.  
TERMINATOR  
DISPLAY  
SWITCHING  
RS-485  
R : 24V DC  
P : 110V DC  
REMOTE CONTROL  
1 : 85 – 132V AC or 85 – 143V DC  
2 : 20 – 30V DC  
3 : 170 – 264V AC  
Specifications subject to change without notice.  
P. 10 / 16 ES-6481 Rev.9  
DISPLAY ITEMS & OUTPUTS  
Items shown in brackets can be displayed when you change settings.  
Suffix Code: A  
Suffix Code: B  
Suffix Code: C  
Suffix Code: D  
R
S
T
R – S  
S – T  
T – R  
R
S
T
R
S
T
A
A
A
V
V
V
A
V
A
V
R – S  
S – T  
T – R  
R – S  
S – T  
T – R  
x1 kW  
x10 kW  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
Dis.  
CH1  
CH2  
CH3  
Dis.  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
ITEMS  
, A  
RS (VST, VTR  
TERM.  
CH1  
CH2  
CH3 0 – 1 kW  
(-1 – +1 kW)  
ITEMS  
, A  
RS (VST, VTR)  
A
A
A
R
S
T
V
V
V
RS  
ST  
TR  
A
V
R
(A  
S
T
)
A
V
R
(A  
S
T)  
)
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: E  
Suffix Code: F  
Suffix Code: G  
Suffix Code: H  
R
S
R
S
R – S  
S – T  
A
A
Hz  
%
V
T
T
T – R  
R – S  
S – T  
MV0  
x1 kW  
V
V
T – R  
x10 kW  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
V0  
x
x
x1 kvar  
V
x
x
x10 kvar  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
RESET  
Dis.  
TERM.  
CH1  
CH2  
ITEMS  
, A  
RS (VST, VTR  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
TERM.  
ITEMS  
A
V
R
(A  
S
T
)
CH1  
AR  
(A  
S
T
)
CH1 Hz  
CH2 PF  
CH3 0 – lag1 kvar  
CH1  
CH2 MV  
RESET MV  
Dis. Display switch. inp.  
VRS (VST, VTR)  
)
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
0
PULSE kWh  
Dis. Display switch. inp.  
0
ext. reset inp.  
(lead1 – lag1 kvar)  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: J  
Suffix Code: K  
Suffix Code: L  
Suffix Code: M  
R
S
R
S
T
DA  
A
A
Hz  
%
%
T
DAR  
S
MAX  
x1 kW  
A
A
T
x10 kW  
MDA  
x
1
kWh  
10 kWh  
100 kWh  
ALARM  
SET  
x1 kW  
x
A
A
x10 kW  
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
CH1  
CH2  
RESET  
Dis.  
ALARM RESET  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
CH1 PF  
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
ITEMS  
CH1  
CH2 DA (MDA)  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
AR  
(A  
S
, A  
T
)
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
CH1 Hz  
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
P. 11 / 16 ES-6481 Rev.9  
51U  
Suffix Code: N  
Suffix Code: P  
Suffix Code: Q  
Suffix Code: R  
R – S  
S – T  
T – R  
R
S
T
A
R
S
T
R
S
T
DA  
MDA  
V
A
A
R – S  
S – T  
T – R  
x1 kW  
x10 kW  
V
%
%
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x
x
x1 kW  
x1 kvar  
x
x
x10 kW  
x10 kvar  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
CH3  
Dis.  
TERM.  
ITEMS  
TERM.  
CH1  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
CH1  
V
RS (VST, VTR  
)
AR  
(AS  
T
)
CH1  
AR  
(AS  
T
)
CH1  
AR  
(AS  
T)  
CH2 0 – 1 kW  
(-1 – +1 kW)  
, A , A  
PULSE kWh  
CH2  
V
RS (VST, VTR  
)
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
CH2 PF  
CH3 0 – lag1 kvar  
(lead1 – lag1 kvar)  
Dis. Display switch. inp.  
CH1/CH2 (DA, MDA)  
PULSE kWh  
Dis. Display switch. inp.  
CH1/CH2 (A  
R
S
T
)
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: S  
Suffix Code: T  
Suffix Code: U  
Suffix Code: W  
R
S
T
A
R
S
R – S  
S – T  
R
S
%
A
V
A
T
T – R  
T
R – S  
S – T  
x1 kW  
x10 kW  
%
Hz  
V
T – R  
x
1
kWh  
10 kWh  
100 kWh  
x1kvarh  
x10kvarh  
x100kvarh  
ALARM  
SET  
x
A
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
Dis.  
ALARM RESET  
Dis.  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
ITEMS  
CH1  
AR  
(AS  
T
)
CH1  
CH2 PF  
PULSE kvarh  
AR  
(A  
S
, AT  
)
CH1  
CH2 Hz  
Dis. Display switch. inp.  
V
RS (VST, VTR  
)
ALARM DA alarm output  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
CH2 0 – 1 kW  
(-1 – +1 kW)  
CH1/CH2 (PF)  
Dis. Display switch. inp.  
PULSE kWh  
Dis. Display switch. inp.  
Suffix Code: X  
Suffix Code: Y  
R
S
A
Hz  
%
T
x1 kvar  
x10 kvar  
x1 kvarh  
x10 kvarh  
x100 kvarh  
x
1
kWh  
10 kWh  
100 kWh  
x
x
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
ITEMS  
CH1  
A
R
(A  
S
, A  
T
)
CH1 Hz  
CH2 PF  
PULSE kWh  
Dis. Display switch. inp.  
CH2 0 – lag1 kvar  
(lead1 – lag1 kvar)  
PULSE kvarh  
Dis. Display switch. inp.  
Specifications subject to change without notice.  
P. 12 / 16 ES-6481 Rev.9  
MODEL  
THREE-PHASE / 4-WIRE CONNECTION  
51U-4  
MODEL & SUFFIX CODE SELECTION  
CONNECTION DIAGRAM  
51U–4❑  
MODEL  
P
N
E
V1 V2 V3 VN  
INPUT (balanced)  
4 : 3-phase / 4-wire, 110V / 3 V / 5A AC  
DISPLAY ITEMS  
Power  
Input  
1S 1L 2S 2L 3S 3L  
Input  
A : A × 3  
B : V × 3  
Output  
CH1  
CH2  
CH3  
Dis  
CT  
C : A × 3, V × 3  
D : A × 3, V × 3, kW  
E : A × 3, V × 3, kWh  
F : A × 3, kW, kWh  
G : Hz, PF, kvar  
J : A × 3, DA, MDA  
L : Hz, PF, kW  
POWER & INPUT  
K
L
R
S
T
k
l
K
L
k
l
K
L
k
l
N
V
U
V
1S  
M : PF, kW, kWh  
U
U
V
v
1L  
VT  
2S  
N : V × 3, kW, kWh  
P : A × 3 or DA or MDA, V × 3, kWh  
Q : A × 3, PF, kW  
R : A × 3, PF, kvar  
S : A × 3 or PF, kW, kWh  
T : A × 3, PF, kvarh  
U : V × 3, Hz  
u
v u v u  
2L  
3S  
V1  
3L  
V2  
DC or AC  
POWER  
V3  
VN  
Suffix Codes  
P
N
E
V1  
V2  
V3 VN  
C, D, E, F, G, L, M, N, P, Q, R, S, T, X, Y  
X : A × 3, kvar, kvarh  
Y : Hz, PF, kWh  
P
N
E
A, J (measuring current only)  
V = Line voltage  
kW = Kilowatt  
PF = Power factor  
A = Line current  
kvar = Kilovar  
Hz = Frequency  
P
N
E
V1 V2  
V3 VN  
B, U (measuring voltage only)  
kWh = Kilowatthours kvarh = Kilovarhours  
DA = Demand (current)  
MDA = Maximum demand (current)  
V0 = Zero-phase voltage  
MV0 = Maximum zero-phase voltage  
Suffix Codes  
1S  
C, D, E, F, G, L, M, N, P, Q, R, S, T, X, Y  
1S 1L 2S 2L 3S 3L  
1L  
2S  
2L  
3S  
3L  
OUTPUT (selectable display items codes)  
0 : None (J with reset input)  
1 : 4 – 20mA DC, 3 points (A B C D G L Q R U)  
2 : 4 – 20mA DC, 2 points + pulse  
(E F M N P S T X Y)  
A, J (measuring current only)  
B, U (measuring voltage only)  
OUTPUT  
Without Outputs  
4 – 20mA DC, 3 points  
(See the following pages.)  
3 : 4 – 20mA DC, 2 points + reset input (J)  
4 : RS-485  
Dis.  
4 – 20mA DC, 2 points  
+ pulse 1 point  
(See the following pages.)  
AUXILIARY POWER SUPPLY  
M : 85 – 264V AC  
R : 24V DC  
POWER  
DISPLAY  
RS-485  
SIWTCHING  
4 – 20mA DC, 2 points  
+ reset input  
(See the following pages.)  
P : 110V DC  
Dis.  
REMOTE CONTROL  
1 : 85 – 132V AC or 85 – 143V DC  
2 : 20 – 30V DC  
3 : 170 – 264V AC  
+
SL  
Ter  
POWER  
Close across the terminator  
when the unit is located at  
the end of transmission line.  
TERMINATOR  
DISPLAY  
SWITCHING  
RS-485  
ORDERING INFORMATION  
Specify code number. (e.g. 51U-4D4-M1)  
P. 13 / 16 ES-6481 Rev.9  
51U  
DISPLAY ITEMS & OUTPUTS  
Items shown in brackets can be displayed when you change settings.  
Suffix Code: A  
Suffix Code: B  
Suffix Code: C  
Suffix Code: D  
R
S
T
R – N(S)  
S – N(T)  
T – N(R)  
PHASE  
LINE  
R
S
T
R
S
T
A
A
A
A
PHASE  
A
PHASE  
V
PHASE  
LINE  
R
S
T
N(S)  
N(T)  
N(R)  
R
S
T
N(S)  
N(T)  
N(R)  
LINE  
LINE  
V
V
V
PHASE  
LINE  
x1 kW  
x10 kW  
V
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
Dis.  
CH1  
CH2  
CH3  
Dis.  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
CH3  
ITEMS  
TERM.  
CH1  
CH2  
ITEMS  
, A  
RS (VST, VTR  
TERM.  
CH1  
CH2  
CH3 0 – 1 kW  
(-1 – +1 kW)  
ITEMS  
, A  
RS (VST, VTR)  
A
A
A
R
S
T
V
V
V
RS  
ST  
TR  
A
V
R
(A  
S
T
)
A
V
R
(A  
S
T)  
)
CH1/CH2 (VRN, VSN, VTN  
Dis. Display switch. inp.  
)
Dis. Display switch. inp.  
CH1/2/3 (VRN, VSN, VTN  
)
Dis. Display switch. inp.  
CH1/2/3 (VRN, VSN, VTN)  
Dis. Display switch. inp.  
Suffix Code: E  
Suffix Code: F  
Suffix Code: G  
Suffix Code: J  
R
S
R
S
R
S
A
PHASE  
A
Hz  
%
A
T
T
T
R
S
T
N(S)  
N(T)  
N(R)  
DAR  
S
LINE  
x1 kW  
A
x10 kW  
T
V
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
MDA  
x
x
x1 kvar  
A
x
x
x10 kvar  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
RESET  
Dis.  
TERM.  
CH1  
CH2  
CH1/CH2 (VRN, VSN, VTN  
PULSE kWh  
ITEMS  
, A  
RS (VST, VTR  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
TERM.  
ITEMS  
A
V
R
(A  
S
T
)
CH1  
AR  
(A  
S
T
)
CH1 Hz  
CH2 PF  
CH3 0 – lag1 kvar  
CH1  
CH2 DA (MDA)  
RESET MDA ext. reset inp.  
Dis. Display switch. inp.  
AR  
(A  
S, AT)  
)
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
)
(lead1 – lag1 kvar)  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Suffix Code: L  
Suffix Code: M  
Suffix Code: N  
Suffix Code: P  
R
S
T
N(S)  
N(T)  
N(R)  
PHASE  
LINE  
R
S
T
A
DA  
MDA  
Hz  
%
%
V
R
S
T
N(S)  
N(T)  
N(R)  
PHASE  
LINE  
x1 kW  
x1 kW  
x10 kW  
x10 kW  
V
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x
1
kWh  
10 kWh  
100 kWh  
x1 kW  
x
x
x
x10 kW  
x
x
x
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
CH1 PF  
CH2 0 – 1 kW  
(-1 – +1 kW)  
PULSE kWh  
Dis. Display switch. inp.  
ITEMS  
TERM.  
ITEMS  
TERM.  
CH1  
CH2  
CH1/CH2 (VRN, VSN, VTN  
(DA, MDA)  
PULSE kWh  
ITEMS  
, A  
RS (VST, VTR)  
CH1 Hz  
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
Dis. Display switch. inp.  
CH1  
V
RS (VST, VTR  
)
A
V
R
(A  
S
T)  
CH2 0 – 1 kW  
(-1 – +1 kW)  
)
CH1/CH2 (AR, AS, AT) (VRN, VSN, VTN)  
PULSE kWh  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
Specifications subject to change without notice.  
P. 14 / 16 ES-6481 Rev.9  
Suffix Code: Q  
Suffix Code: R  
Suffix Code: S  
Suffix Code: T  
R
S
T
R
S
T
R
S
T
A
R
S
T
%
A
A
A
x1 kW  
x10 kW  
%
%
%
x
1
kWh  
10 kWh  
100 kWh  
x1kvarh  
x1 kW  
x1 kvar  
x
x10kvarh  
x10 kW  
x10 kvar  
x
x100kvarh  
DISPLAY  
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
+
+
+
+
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
CH3  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
TERM.  
ITEMS  
, A  
CH1  
AR  
(AS  
T
)
CH1  
AR  
(AS  
T
)
CH1  
AR  
(AS  
T
)
CH1  
AR  
(AS  
T)  
CH2 PF  
CH3 0 – 1 kW  
(-1 – +1 kW)  
CH2 PF  
CH3 0 – lag1 kvar  
CH2 0 – 1 kW  
(-1 – +1 kW)  
CH1/CH2 (PF)  
CH2 PF  
PULSE kvarh  
Dis. Display switch. inp.  
(lead1 – lag1 kvar)  
Dis. Display switch. inp.  
Dis. Display switch. inp.  
PULSE kWh  
Dis. Display switch. inp.  
Suffix Code: Y  
Suffix Code: U  
Suffix Code: X  
R
S
T
N(S)  
N(T)  
N(R)  
PHASE  
LINE  
R
S
Hz  
%
A
T
V
x1 kvar  
Hz  
x10 kvar  
x
1
kWh  
10 kWh  
100 kWh  
x1 kvarh  
x10 kvarh  
x100 kvarh  
x
x
DISPLAY  
DISPLAY  
DISPLAY  
Output Connection  
Output Connection  
Output Connection  
+
+
+
+
+
+
CH1  
CH2  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
CH1  
CH2  
PULSE  
Dis.  
TERM.  
ITEMS  
TERM.  
ITEMS  
TERM.  
ITEMS  
CH1 Hz  
CH2 PF  
PULSE kWh  
Dis. Display switch. inp.  
CH1  
CH2 Hz  
CH1/CH2 (VRN, VSN, VTN  
Dis. Display switch. inp.  
V
RS (VST, VTR  
)
CH1  
A
R
(A  
S, AT)  
CH2 0 – lag1 kvar  
(lead1 – lag1 kvar)  
PULSE kvarh  
Dis. Display switch. inp.  
)
P. 15 / 16 ES-6481 Rev.9  
51U  
SYSTEM CONFIGURATION EXAMPLE  
Nest Bus  
32 Units Max.  
32 Points Max.  
Communication Interface  
for 51-UNIT Use  
model: SMDU  
RS-485 (Multi-Meter Protocol, 31 units per kilometer)*  
Multi Power Meter  
model: 51U  
R
S
T
R
S
T
R
S
T
A
V
A
V
A
V
R-  
R-  
R-  
S
S-  
T
S
S
S-  
S-  
T
T
T-  
T-  
T-  
R
R
R
x1  
P
x1  
P
x1  
P
kW  
kW  
kW  
x1  
x1  
x1  
0k  
0k  
0k  
W
W
W
D
D
D
IS  
IS  
IS  
LA  
LA  
LA  
Y
Y
Y
*MsysNet use only. Consult Factory.  
Specifications subject to change without notice.  
P. 16 / 16 ES-6481 Rev.9  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY