54U-1117-AD4/Q [MSYSTEM]

Power Transducer Series;
54U-1117-AD4/Q
型号: 54U-1117-AD4/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Power Transducer Series

文件: 总10页 (文件大小:476K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 54U  
Power Transducer Series  
[2] INPUT  
1: 480 V / 1 A AC  
2: 480 V / 5 A AC  
MULTI POWER MONITOR  
(4 digital displays)  
Functions & Features  
[3] DISCRETE INPUT  
• Measures simultaneously several variables of a heavy-  
current power system: current, voltage, active, reactive and  
apparent power, active and reactive energy, power factor,  
frequency, etc.  
0: None  
('External Interface' codes 1, 2, 3, 7 and 8 Not selectable.)  
1: 24V DC  
('External Interface' codes 4, 5, 6, 9 and A Not selectable.)  
2: 110V DC  
• All measured values, counter values, display mode,  
setting data are stored in the non-volatile memory at the  
power off  
('External Interface' codes 4, 5, 6, 9 and A Not selectable.)  
• Parameters are programmable using the front buttons or  
the PC via infrared interface  
[4] EXTERNAL INTERFACE  
1: Modbus, Do × 1, Di × 1  
• Mounted using M5 screws or mounting brackets  
• 60-segment bargraph  
2: 4 – 20 mA DC × 4, Do × 1, Di × 1  
3: 1 – 5 V DC × 4, Do × 1, Di × 1  
4: Modbus, Do × 2  
• Displayed measurands are freely selectable  
• Open collector output for alarm or energy count  
• Loop test output  
5: 4 – 20 mA DC × 4, Do × 2  
6: 1 – 5 V DC × 4, Do × 2  
7: 4 – 20 mA DC × 4 (isolated), Do × 1, Di × 1  
8: 1 – 5 V DC × 4 (isolated), Do × 1, Di × 1  
9: 4 – 20 mA DC × 4 (isolated), Do × 2  
A: 1 – 5 V DC × 4 (isolated), Do × 2  
Typical Applications  
• Multi-functional power monitor incorporated in an electric  
device: saves space, wiring works, and cost  
110 (4.33)  
AUXILIARY POWER SUPPLY  
AD4: universal  
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /  
110 – 240 V DC (Operational range 99 – 264 V,  
ripple 10 %p-p max)  
110  
(4.33)  
125  
*
(4.92)  
[5] OPTIONS (multiple selections)  
Language  
mm (inch)  
*140 (5.51) for 54Ux-2  
blank: Japanese  
/E: English  
Other Options  
MODEL: 54U-[1][2][3][4]-AD4[5]  
blank: none  
/Q: Option other than the above (specify the specification)  
ORDERING INFORMATION  
• Code number: 54U-[1][2][3][4]-AD4[5]  
Specify a code from below for each of [1] through [5].  
(e.g. 54U-1211-AD4/Q)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
Moving parts and indicators are not coated.  
/C01: Silicone coating  
• Specify the specification for option code /Q  
(e.g. /C01/S01/SET)  
/C02: Polyurethane coating  
/C03: Rubber coating  
[1] CONFIGURATION  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
1: Single phase / 2-wire and 3-wire, 3-phase / 3-wire  
2: Single phase / 2-wire and 3-wire,  
3-phase / 3-wire and 4-wire  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-6487)  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 1/10  
http://www.m-system.co.jp/  
MODEL: 54U  
RELATED PRODUCTS  
INPUT SPECIFICATIONS  
• Infrared Communication Adaptor (model: COP-IRU)  
• PC configurator software (model: PMCFG)  
Downloadable at M-System’s web site.  
Frequency: 50 / 60 Hz (45 – 65 Hz)  
Voltage Input  
Rated voltage  
Line-to-line (delta voltage): 480 V  
Line-neutral (phase voltage): 277 V  
Consumption VA: ≤ ULN2 / 300 kΩ / phase  
Overload capacity: 200 % of rating for 10 sec., 120 %  
continuous  
GENERAL SPECIFICATIONS  
Construction: 110-mm square panel flush mounted  
Degree of protection  
Front panel: IP 50  
Selectable primary voltage range: 50 – 400 000 V  
Current Input  
Terminal block, housing: IP 30  
Connection  
Rated current: 1 A or 5 A  
Voltage input: M4 screw terminals (torque 1.4 N·m)  
Current input: M4 screw terminals (torque 1.4 N·m)  
Discrete input, discrete output, analog output, Modbus,  
auxiliary power supply: M3 screw terminals (torque 0.6 N·m)  
Configuration  
Consumption VA: ≤ I · 0.01 Ω / phase  
2
Overload capacity: 4000 % of rating for 1 sec., 2000 % for  
4 sec., 120 % continuous  
Selectable primary current range: 1 – 20 000 A  
Operational range  
Code 1: Single phase/2-wire and 3-wire, 3-phase/3- wire  
balanced/unbalanced load  
Voltage, current, apparent power: ≤ 120 % of the rating  
Active / reactive power: -120 to +120 % of the rating  
Frequency: 45 – 65 Hz  
Code 2: Single phase/2-wire and 3-wire, 3-phase/3- wire  
balanced/unbalanced load, 3-phase/4- wire  
balanced/unbalanced load  
Power factor: -1 to +1  
Discrete Input: 24 V DC or 110 V DC  
(input resistance 6 kΩ)  
Screw terminal  
• M3 screw: Nickel-plated steel (standard) or stainless steel  
• M4 screw: Nickel-plated brass (standard) or stainless steel  
Housing material: Flame-resistant resin (black)  
Isolation: Voltage input to current input to discrete input to  
Modbus or analog output to discrete output to power  
Note: Isolated between each analog output for ‘External  
interface’ codes 7, 8, 9 and A  
Detecting voltage: External 24 V DC ±10 % or 110 V DC  
±10 %  
ON current: ≥ 1 mA (≤ 24 kΩ @ 24 V, ≤ 110 kΩ @110 V)  
OFF current: ≤ 0.1 mA (≥ 240 kΩ @ 24 V, ≥ 1.1 MΩ @ 110  
V)  
Detecting time: 10 – 1000 msec.  
The status can be monitored on the Modbus; usable to reset  
energy count or to update average (demand) value.  
Measured variables  
Voltage: 1 – 2, 2 – 3, 3 – 1, 1 – N, 2 – N, 3 – N  
Current: 1, 2, 3, N  
Active / reactive / apparent power: 1, 2, 3, Σ  
Power factor: 1, 2, 3, Σ  
OUTPUT SPECIFICATIONS  
Modbus  
Frequency  
Communication: Half-duplex, asynchronous, no procedure  
Interface: Conforms to TIA/EIA-485-A  
Max. transmission distance: 500 meters  
Baud rate: 1.2 – 38.4 kbps  
Phase angle between voltages: 1 – 2, 2 – 3, 3 – 1  
Active energy incoming / outgoing: Σ  
Reactive energy inductive / capacitive: Σ  
Apparent energy: Σ  
Max. number of nodes: 31 (except the master)  
Protocol: Modbus RTU  
Active / reactive / apparent power intervals (demand)  
Current intervals (demand): 1, 2, 3, N  
Harmonic contents: Σ, 2nd to 31st  
Node address: 1 – 247 (factory default setting: 1)  
Parity: none, even or odd (factory default setting: odd)  
Stop bit: 1 or 2 (factory default setting: 1)  
Media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)  
■ DC Current: 4 – 20 mA DC  
Voltage: 1 – 2, 2 – 3, 3 – 1, 1 – N, 2 – N, 3 – N  
Current: 1, 2, 3, N  
Max. and min. values: 1 = R, 2 = S, 3 = T  
Infrared communication: Transmission distance max. 1  
meter (for use with the COP-IRU and PMCFG)  
DISPLAY: LCD with LED backlight (LED OFF timer  
available)  
Load resistance: ≤ 270 Ω  
Measurands converted into analog output: Voltage, Current,  
Active / reactive / apparent power, Power factor, Frequency,  
Harmonic contents  
Signed: 4 digits, 2 lines  
DC Voltage: 1 – 5 V DC  
Energy: 9 digits, 1 line  
Load resistance: ≥ 5000 Ω  
Bargraph: 1 point (60 segments)  
Measurands converted into analog output: Voltage, Current,  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 2/10  
http://www.m-system.co.jp/  
MODEL: 54U  
Active / reactive / apparent power, Power factor, Frequency,  
Harmonic contents  
Data update period:  
Harmonic contents and frequency: ≤ 1.1 sec.  
Other: ≤ 600 msec.  
Open Collector  
Programmable for either alarm or energy count.  
Max. rated load: 130 V DC @50 mA  
Continuous rated load: 130 V DC @30 mA  
Saturation voltage: 1.5 V DC  
Response time: ≤ 2 sec. (0 – 99 %),  
≤ 3 sec. for frequency and harmonic contents  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(voltage input to current input to discrete input to Modbus  
or analog output to discrete output to power)  
500 V AC @1 minute for 'External interface' code 7, 8, 9 and  
A (between each analog output)  
Measurands applicable to alarm: Voltage, current, current  
intervals, neutral current, frequency, energy, energy  
intervals  
(ON delay, deadband and other parameters are selectable)  
Measurands applicable to count: Energy;  
Pulse rate selectable within  
2000 V AC @1 minute (circuits to housing)  
0.1 – 10 000.0 kWh/p, kvarh/p, kVAh/p  
INSTALLATION  
Power consumption  
AC: < 8 VA; Less than 13 VA for 'External interface' code 7  
and 9  
DC: < 4 W; Less than 6 W for 'External interface' code 7  
and 9  
Operating temperature: -10 to +55°C (14 to 131°F)  
Storage temperature: -20 to +80°C (-4 to +176°F)  
Operating humidity: 0 to 90 %RH (non-condensing)  
Mounting: Panel flush mounting (M5 screws (torque 2 N·m)  
or mounting brackets)  
Weight  
Configuration Code 1: 500 g (1.1 lb)  
Configuration Code 2: 525 g (1.16 lb)  
PERFORMANCE  
Accuracy  
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)  
Voltage: (accur.±0.3 %)  
Rated voltage at ≥ 100 V  
100 V at < 100 V  
Current: (accur.±0.3 %)of Span 1 A or 5 A  
Power: (accur.±0.5 %)  
Rated voltage/current at ≥ 100 V  
Wattage as listed below at < 100 V:  
173.2 W (1 A) or 866 W (5 A) for 3 ph/3 w  
100 W (1 A) or 500 W (5 A) for 1 ph/2 w  
200 W (1 A) or 1000 W (5 A) for 1 ph/3 w  
300 W (1 A) or 1500 W (5 A) for 3 ph/4 w  
PF: (accur.±0.5 %)  
Frequency: (accur.±0.1 %) of span  
Energy: (accur.±1 %)  
Harmonic: (accur.±1 %) of span  
Analog output: Accuracy of assigned measurand or ±0.2 %,  
whichever is greater.  
Sampling rate: 64 samples per cycle  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 3/10  
http://www.m-system.co.jp/  
MODEL: 54U  
MOUNTING REQUIREMENTS  
PANEL CUTOUT unit: mm (inch)  
• USING MOUNTING SCREWS  
Remove the mounting brackets.  
• USING MOUNTING BRACKETS  
Remove the mounting screws.  
45 (1.77)  
45 (1.77)  
+
0.8 (3.65)  
0 (3.63)  
92  
2–6 (.24) ꢀia.  
Panel thickness : 2 to 10 (.08 to .39)  
Panel thickness : 2 to 15 (.08 to .59)  
EXTERNAL VIEW  
FRONT VIEW  
REAR VIEW  
• CONFIGURATION CODE: 1  
2
Voltage Input  
Terminals  
Current Input  
Terminals  
Data Displays  
Auxiliary Power  
Modbus / Analog Output  
Terminals  
Supply Terminals  
Control Buttons  
Discrete I/O  
Terminals  
IU  
PQS  
PF THD  
MAX  
E PRG ESC  
Infrared Interface  
• CONFIGURATION CODE: 2  
Voltage Input  
Terminals  
2
Current Input  
Terminals  
Auxiliary Power  
Modbus / Analog Output  
Terminals  
Supply Terminals  
Discrete I/O  
Terminals  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 4/10  
http://www.m-system.co.jp/  
MODEL: 54U  
TERMINAL CONNECTIONS  
CONFIGURATION CODE: 1  
• Analog Output  
• Modbus  
2
2
P1  
P2  
P3  
1S  
1L  
3S  
3L  
P1  
P2  
P3  
1S  
1L  
3S  
3L  
DO/PO  
+
DO/PO  
+
U(+  
)
NC  
DI  
+
Ao1  
+
Ao2+  
Ao3  
+
Ao4  
+
U(  
+)  
NC  
DI  
+
T1  
T3  
NC  
NC  
DO/PO  
DO/PO  
V(–) NC  
DI– Ao1– Ao2– Ao3– Ao4–  
V(–) NC  
DI–  
T2  
T4  
NC  
NC  
System /  
Application  
System /  
Application  
Terminal  
Terminal  
P1 P2  
1S 1L  
P1 P2  
1S 1L  
P1 P2 P3 1S 1L 3S 3L  
P1 P2 P3 1S 1L 3S 3L  
k
l
k
l
source  
1
load  
source  
1
load  
source  
1
load  
source  
load  
Single-phase /  
3-wire  
1
N / 2  
2 / 3  
K
L
K
L
k
l
2
2
N / 2  
2 / 3  
Single-phase /  
2-wire  
K
L
Three-phase /  
3-wire,  
P1 P2  
1S 1L  
P1 P2 P3 1S 1L 3S 3L  
unbalanced load  
(2CT)  
u
v
u
v
v
u
k
l
k
l
source  
1
U
V
load  
source  
1
load  
U
V
V
U
K
L
K
L
k
l
2
N / 2  
2 / 3  
K
L
P1 P2 P3 1S 1L  
P1 P2 P3 1S 1L  
k
l
source  
1
load  
source  
1
load  
K
L
2
3
2
3
Three-phase /  
3-wire,  
balanced load  
P1 P2 P3 1S 1L  
u
v
v
u
k
l
source  
1
load  
U
V
V
U
K
L
2
3
Note: For low voltage circuit, grounding is not required.  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 5/10  
http://www.m-system.co.jp/  
MODEL: 54U  
CONFIGURATION CODE: 2  
• Analog Output  
• Modbus  
P1  
P2  
P3  
N
P1  
P2  
P3  
N
2
2
NC  
1S  
1L  
2S  
2L  
3S  
3L  
NC  
1S  
1L  
2S  
2L  
3S  
3L  
DO/PO  
+
DO/PO  
+
U(+  
)
NC  
DI  
+
Ao1  
+
Ao2+  
Ao3  
+
Ao4  
+
U(  
+)  
NC  
DI  
+
T1  
T3  
NC  
NC  
DO/PO  
DO/PO  
V(–) NC  
DI– Ao1– Ao2– Ao3– Ao4–  
V(–) NC  
DI–  
T2  
T4  
NC  
NC  
System /  
Application  
System /  
Application  
Terminal  
Terminal  
P1 P2  
1S 1L  
P1 P2  
1S 1L  
P1 P2 P3 1S 1L 3S 3L  
P1 P2 P3 1S 1L 3S 3L  
k
l
k
l
source  
1
load  
source  
1
load  
source  
1
load  
source  
load  
Single-phase /  
3-wire  
1
N / 2  
2 / 3  
K
L
K
L
k
l
2
2
N / 2  
2 / 3  
Single-phase /  
2-wire  
K
L
Three-phase /  
3-wire,  
P1 P2  
1S 1L  
P1 P2 P3 1S 1L 3S 3L  
unbalanced load  
(2CT)  
u
v
u
v
v
u
k
l
k
l
source  
1
U
V
load  
source  
1
load  
U
V
V
U
K
L
K
L
k
l
2
N / 2  
2 / 3  
K
L
P1 P2 P3 1S 1L  
P1 P2 P3 1S 1L  
P1  
N
1S 1L  
P1  
N
1S 1L  
k
l
k
l
source  
1
load  
source  
1
load  
source  
1
load  
source  
1
load  
K
L
K
L
2
3
2
3
2
3
2
3
Three-phase /  
3-wire,  
balanced load  
Three-phase /  
4-wire,  
balanced load  
N
N
P1 P2 P3 1S 1L  
P1  
N
1S 1L  
u
v
u
v
v
u
k
l
k
l
source  
1
load  
source  
1
U
V
load  
U
V
V
U
K
L
K
L
2
3
2
3
N
P1 P2 P3  
P1 P2 P3  
P1 P2 P3  
1S 1L 2S 2L 3S 3L  
P1 P2 P3  
P1 P2 P3  
P1 P2 P3  
N 1S 1L 2S 2L 3S 3L  
source  
1
load  
load  
load  
source  
1
load  
2
3
2
3
N
1S 1L 2S 2L 3S 3L  
N 1S 1L 2S 2L 3S 3L  
Three-phase /  
3-wire,  
Three-phase /  
4-wire,  
k
l
k
l
source  
1
source  
1
load  
k
l
k
l
unbalanced load  
(3CT)  
unbalanced load  
K
L
k
l
K
L
k
l
2
3
2
3
K
L
K
L
K
L
K
L
N
1S 1L 2S 2L 3S 3L  
N
1S 1L 2S 2L 3S 3L  
u
v
u
v
u
v
u
v
v
u
k
l
k
l
source  
1
source  
1
load  
U
V
V
U
U
V
U
V
U
V
k
l
k
l
K
L
k
l
K
L
k
l
2
3
2
3
K
L
K
L
K
L
K
L
N
Note: For low voltage circuit, grounding is not required.  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 6/10  
http://www.m-system.co.jp/  
MODEL: 54U  
EXTERNAL INTERFACE CODE: 1  
EXTERNAL INTERFACE CODE: 4  
DI +  
DI –  
DO/PO1+  
DO/PO1–  
DO/PO2+  
DO/PO2–  
DISCRETE  
INPUT  
DISCRETE  
OUTPUT 1  
DO/PO+  
DO/PO–  
DISCRETE  
OUTPUT  
DISCRETE  
OUTPUT 2  
Shielded Twisted-pair Cable  
Shielded Twisted-pair Cable  
T1  
T2  
T3  
T4  
T1  
T2  
T3  
T4  
+
+
To other  
Modbus devices  
To other  
Modbus devices  
Jumper *1  
Jumper *1  
Term.  
Resist.  
Term.  
Resist.  
U(+)  
V(–)  
U(+)  
V(–)  
AUXILIARY POWER  
AUXILIARY POWER  
EXTERNAL INTERFACE CODE: 2, 3, 7, 8  
EXTERNAL INTERFACE CODE: 5, 6, 9, A  
DI +  
DO/PO1+  
DISCRETE  
INPUT  
DISCRETE  
OUTPUT 1  
DI –  
DO/PO+  
DO/PO–  
AO1 +  
AO1 –  
AO2 +  
AO2 –  
AO3 +  
AO3 –  
AO4 +  
AO4 –  
U(+)  
DO/PO1–  
DO/PO2+  
DO/PO2–  
AO1 +  
AO1 –  
AO2 +  
AO2 –  
AO3 +  
AO3 –  
AO4 +  
AO4 –  
U(+)  
DISCRETE  
OUTPUT  
DISCRETE  
OUTPUT 2  
ANALOG  
OUTPUT 1  
ANALOG  
OUTPUT 1  
2
2
*
*
ANALOG  
OUTPUT 2  
ANALOG  
OUTPUT 2  
ANALOG  
OUTPUT 3  
ANALOG  
OUTPUT 3  
ANALOG  
OUTPUT 4  
ANALOG  
OUTPUT 4  
AUXILIARY POWER  
AUXILIARY POWER  
V(–)  
V(–)  
• Discrete Input Connection E.g. • Discrete Output Connection E.g.  
*1. When the device is located at the end of a transmission line via  
twisted-pair cable, (when there is no cross-wiring), close across the  
terminal T2 – T3 with a leadwire.  
When the device is not at the end, no shortcircuit wire is required.  
*2. For ‘External interface’ code 7, 8, 9 and A, the analog outputs are  
isolated between each other.  
DI +  
DI –  
+
DO/PO+  
DO/PO–  
+
-
-
MODBUS WIRING CONNECTION  
R2K-1  
RS-485  
RS-485  
54U  
T1  
T2  
T3  
T4  
54U  
T1  
T2  
T3  
T4  
T1  
RS-232-C  
T2  
1
1
*
*
T3  
T4  
2
*
FG  
*1. Internal terminating resistor is used when the device is at the end of a transmission line.  
*2. Install shield cables to all sections and ground them at single point.  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 7/10  
http://www.m-system.co.jp/  
MODEL: 54U  
EXTERNAL DIMENSIONS unit: mm (inch)  
CONFIGURATION CODE: 1  
110 (4.33)  
25 (.98)  
100 (3.94)  
91.5 (3.60)  
2
2-M5 SCREW  
91.5 (3.60)  
MOUNTING BRACKET  
CONFIGURATION CODE: 2  
110 (4.33)  
25 (.98)  
115 (4.53)  
2
2-M5 SCREW  
MOUNTING BRACKET  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 8/10  
http://www.m-system.co.jp/  
MODEL: 54U  
SYSTEM CONFIGURATION EXAMPLES  
RS-485 / RS-232-C  
RS-232-C  
RS-232-C/RS-485  
Converter  
(model: R2K-1 or LK1)  
Lightning Surge Protector  
for RS-485/422  
(model: MDP-4R or MD74R) *1  
RS-485 (Modbus RTU)  
Lightning Surge Protector  
for RS-485/422  
(model: MDP-4R or MD74R) *1  
Multi Power Monitor  
(model: 54U)  
RS-485 / ETHERNET  
Ethernet  
Communication Adaptor  
(model: 72EM2-M4)  
ETHERNET  
RS-485  
RUN  
SEND  
FIELD  
CNFG  
Lightning Surge Protector  
for RS-485/422  
(model: MDP-4R or MD74R) *1  
RS-485 (Modbus RTU)  
Lightning Surge Protector  
for RS-485/422  
(model: MDP-4R or MD74R) *1  
Multi Power Monitor  
(model: 54U)  
*1. Insert lightning surge protectors recommended in this example if necessary.  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 9/10  
http://www.m-system.co.jp/  
MODEL: 54U  
Specifications are subject to change without notice.  
54U SPECIFICATIONS  
ES-6487 Rev.10 Page 10/10  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY