60C-041-K [MSYSTEM]
Field Network Modules 60-UNIT Series;型号: | 60C-041-K |
厂家: | M-SYSTEM |
描述: | Field Network Modules 60-UNIT Series |
文件: | 总4页 (文件大小:142K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 60C
Field Network Modules 60-UNIT Series
[4] OPTIONS
blank: none
/Q: With options (specify the specification)
ANALOG I/O MODULE
(CC-Link)
Functions & Features
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with CC-Link
• Saving power and I/O wiring inside an instrumentation
panel
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
72
(2.83)
RELATED PRODUCTS
•Special cable (model: MCN34)
80
(3.15)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
153
(6.02)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
MODEL: 60C-[1][2]-[3][4]
CC-Link: Euro type connector terminal (applicable wire
size: 0.2 to 2.5 mm , stripped length 7 mm)
2
ORDERING INFORMATION
• Code number: 60C-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. 60C-161-K/Q)
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless
steel
• Specify the specification for option code /Q
(e.g. /C01/S01)
Housing material: Flame-resistant resin (black)
Isolation: I/O to CC-Link to power to FG1
Power indicator: Green LED turns on with power supplied.
[1] NO. OF CHANNELS
04: 4 points
CC-Link COMMUNICATION
CC-Link: Conforms to Version 1.10
Station type: Remote device station
Station No. setting: Rotary switch; 1 – 64
Number of occupied stations:
08: 8 points
16: 16 points
[2] I/O TYPE
1: Input
60C-04 1 station
60C-08 2 stations
2: Output
60C-16 4 stations
Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting: Rotary switch
[3] POWER INPUT
AC Power
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps,
10Mbps)
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
Transmission cable: Approved for CC-Link
L RUN indicator: Red LED turns on in an normal condition.
L ERR. indicator: Red LED turns on or flashes in an
abnormality; off with wire breakdown.
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
60C SPECIFICATIONS
ES-6602 Rev.10 Page 1/4
http://www.m-system.co.jp/
MODEL: 60C
INPUT SPECIFICATIONS
■ Analog Input
OUTPUT SPECIFICATIONS
■ Analog Output
Input range: 1 – 5 V DC
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held.
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
■ A/D CONVERSION DATA
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
■ D/A CONVERSION DATA
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
SIGN
BIT
RWr n+0
RWr n+1
RWr n+2
RWr n+3
INPUT 1 A/D CONVERSION DATA
INPUT 2 A/D CONVERSION DATA
INPUT 3 A/D CONVERSION DATA
INPUT 4 A/D CONVERSION DATA
SIGN
BIT
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
SIGN
BIT
RWw n+0
RWw n+1
RWw n+2
RWw n+3
OUTPUT 1 D/A CONVERSION DATA
OUTPUT 2 D/A CONVERSION DATA
OUTPUT 3 D/A CONVERSION DATA
OUTPUT 4 D/A CONVERSION DATA
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
RWr n+7
RWr n+11
RWr n+15
INPUT 8 A/D CONVERSION DATA
INPUT 12 A/D CONVERSION DATA
INPUT 16 A/D CONVERSION DATA
SIGN
BIT
RWw n+7
RWw n+11
RWw n+15
OUTPUT 8 D/A CONVERSION DATA
OUTPUT 12 D/A CONVERSION DATA
OUTPUT 16 D/A CONVERSION DATA
SIGN
BIT
SIGN
BIT
SIGN
BIT
RWr n+0 through RWr n+3 for 4 inputs.
RWr n+0 through RWr n+7 for 8 inputs.
RWr n+0 through RWr n+15 for 16 inputs.
SIGN
BIT
• Input Connector Pin Assignment
RWw n+0 through RWw n+3 for 4 outputs.
RWw n+0 through RWw n+7 for 8 outputs.
RWw n+0 through RWw n+15 for 16 outputs.
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
COM
COM
Input 10
Input 11
COM
COM
Input 12
COM
Input 13
COM
Input 14
COM
Input 15
COM
Input 16
COM
No connection
No connection
Input 1 – 4 for 4 points, 1 – 8 for 8 points.
60C SPECIFICATIONS
ES-6602 Rev.10 Page 2/4
http://www.m-system.co.jp/
MODEL: 60C
• Output Connector Pin Assignment
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Output
Output
Output
Output
Output
Output
Output
Output
Output
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
COM
COM
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
No connection
COM
COM
COM
COM
COM
COM
COM
No connection
Output 1 – 4 for 4 points, 1 – 8 for 8 points.
INSTALLATION
Power consumption
•AC: Approx. 4 VA
•DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output
to CC-Link to power)
2000 V AC @ 1 minute (input or output or CC-Link or power
to FG1)
EXTERNAL VIEW
CN1
Modular Jack
for Factory Calibration
L RUN
L ERR.
SD
Status Indicator LED
I/O Connector
RD
PWR
Power LED
Station No. Setting
Baud Rate Setting
Euro Type Connector Terminal
for CC-Link
60C SPECIFICATIONS
ES-6602 Rev.10 Page 3/4
http://www.m-system.co.jp/
MODEL: 60C
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
7
14
6
5
12
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
8
9
15 10
1
11
2
14–M3.5
SCREW
14
72 (2.83)
(.55)
109 (4.29)
139 (5.47)
60 (2.36)
72 (2.83)
38 (1.50)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
COMMUNICATION MODULE
INDICATOR ROTARY
Terminator
DA
LED
SW
*
To 10-RACK,
18-RACK etc.
DB
To Other
CC-Link
Devices
CC-Link
INTERFACE
DG
SLD
FG
A / D
or
D / A
Conv.
I / O
CPU
Modular Jack
for Factory
Calibration
MODULAR JACK
SERIAL
TRANSMISSION
LINE
U(+)
V(–)
FG1
7
14
8
POWER
*Attach the terminating resistor when the module is
at the termination of a transmission line.
■ COMMUNICATION CABLE CONNECTIONS
MASTER UNIT
ANALOG I/O MODULE
I/O UNIT
TERMINATOR
blue
DA
DB
DA
DB
DA
DB
white
yellow
DG
SLD
FG
DG
SLD
FG
DG
SLD
FG
Specifications are subject to change without notice.