MODEL: 60F
Field Network Modules 60-UNIT Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ANALOG I/O MODULE
(Fuji Electric T-Link use)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with T-Link
• Saving power and I/O wiring inside an instrumentation
panel
RELATED PRODUCTS
•Special cable (model: MCN34)
72
(2.83)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
80 (3.15)
T-Link: Euro type connector terminal (applicable wire size:
0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminal
153 (6.02)
Screw terminal: Chromated steel (standard) or stainless
steel
mm (inch)
Housing material: Flame-resistant resin (black)
Isolation: I/O to T-Link to power to FG1
Power indicator: Green LED turns on with power supplied.
MODEL: 60F-16[1]-[2][3]
T-Link SPECIFICATIONS
Configuration: Multi-drop
ORDERING INFORMATION
• Code number: 60F-16[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. 60F-161-K/Q)
Communication: Half-duplex
Baud rate: 500 kbps
Transmission media/distance:
• Specify the specification for option code /Q
(e.g. /C01/S01)
KPEV-SB 0.75 mm
2
× 1 pair, 700 m
× 1 pair, 1000 m
T-KPEV-SB, 1.25 mm
2
Station No.: Rotary switch; 00 - 99
NO. OF CHANNELS
16: 16 points
(Factory default setting: 00)
L RUN indicator: Red LED ON at normal communication
L ERR. indicator: Red LED ON/blinking at communication
abnormality
[1] I/O TYPE
1: Input
L I/O indicator: Red LED blinking at normal I/O
L COM indicator: RED LED blinking at T-Link normal
communication
2: Output
■ NUMBER OF CONNECTABLE UNITS WITH T-Link
Up to a maximum of 32 T-Link devices can be connected in
a single T-Link system. There is a limit of 100 words in
processor memory. Make sure that the configured word
area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to
this device.
[2] POWER INPUT
AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
The below describes the number of words occupied per
device by number of modules.
[3] OPTIONS
• For input 16 / output 16 modules: 16
blank: none
/Q: With options (specify the specification)
60F SPECIFICATIONS
ES-6610 Rev.3 Page 1/4
http://www.m-system.co.jp/
MODEL: 60F
INPUT SPECIFICATIONS
■ Analog Input
• Output Connector Pin Assignment
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Input range: 1 – 5 V DC
Output
Output
Output
Output
Output
Output
Output
Output
Output
1
2
3
4
5
6
7
8
9
3
4
COM
Input resistance: ≥ 1 MΩ
5
6
COM
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
COM
COM
COM
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
No connection
COM
COM
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
COM
COM
COM
• Input Connector Pin Assignment
COM
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
COM
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
No connection
3
4
COM
5
6
COM
7
8
COM
INSTALLATION
Power consumption
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
•AC: Approx. 3 VA
COM
COM
•DC: Approx. 4 W (160 mA)
COM
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Input 10
Input 11
COM
COM
Input 12
COM
Input 13
COM
Weight: 450 g (0.99 lb)
Input 14
COM
Input 15
COM
Input 16
COM
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
No connection
No connection
D/A conversion: ±0.1 %
OUTPUT SPECIFICATIONS
■ Analog Output
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output
to T-Link to power)
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held.
Output range: 1 – 5 V DC
2000 V AC @ 1 minute (input or output or T-Link or power to
FG1)
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
60F SPECIFICATIONS
ES-6610 Rev.3 Page 2/4
http://www.m-system.co.jp/
MODEL: 60F
EXTERNAL VIEW
Modular Jack
for Factory Calibration
CN1
L RUN
L ERR.
L I/O
Operating Status Indicator LED
I/O Connector
L COM
Power Indicator LED
PWR
Euro Type Connector Terminal
for T-Link
Station No. Setting Rotary Switches
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
7
14
6
5
12
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
8
9
15 10
1
11
2
14–M3.5
SCREW
14
72 (2.83)
(.55)
109 (4.29)
139 (5.47)
60 (2.36)
72 (2.83)
38 (1.50)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Transmission
Station No.
Setting Rotary
Switches
Indicator
LED
SHIELDED
TWISTED-PAIR
T1
T2
+
CPU For T-Link
Transmission
To other T-Link devices
−
To 10-RACK, 18-RACK etc.
SD
A/D
or
D/A
Converter
RT+
RT−
*
JUMPER PIN
I/O Side
CPU
TERMINATING
RESISTOR
Modular Jack
for Factory
Calibration
MODULAR
JACK
SERIAL
TRANSMISSION LINE
7
14
8
U( + )
V( − )
POWER
GROUNDING FG1
* When the unit is located at the end of transmission line via twisted-pair
cable (= no cross-wiring), short across terminals RT+, RT- with the
jumper pin (or wire) provided with the unit.
Remove the jumper pin for the one not located at the end.
Note: Use T1, T2, SD terminals for cross-wiring.
60F SPECIFICATIONS
ES-6610 Rev.3 Page 3/4
http://www.m-system.co.jp/
MODEL: 60F
Specifications are subject to change without notice.
60F SPECIFICATIONS
ES-6610 Rev.3 Page 4/4
http://www.m-system.co.jp/