60S-161-K [MSYSTEM]
Field Network Modules 60-UNIT Series;型号: | 60S-161-K |
厂家: | M-SYSTEM |
描述: | Field Network Modules 60-UNIT Series |
文件: | 总5页 (文件大小:181K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 60S
Field Network Modules 60-UNIT Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ANALOG I/O MODULE
(Multiplex Transmission System)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with Multiplex Transmission System
• Saving power and I/O wiring inside an instrumentation
panel
RELATED PRODUCTS
•Special cable (model: MCN34)
72
(2.83)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
80 (3.15)
SIN-NET, RUN contact output: Euro type connector
terminal (applicable wire size: 0.2 to 2.5 mm
2, stripped
length 7 mm)
153 (6.02)
mm (inch)
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to SIN-NET to RUN contact output to power to
FG1
MODEL: 60S-16[1]-[2][3]
Power indicator: Red LED turns ON in normal conditions;
OFF when the voltage level becomes low.
RUN indicator: Red LED turns ON when the selfdiagnosis
proves normal, OFF in an abnormality.
■ RUN Contact Output: Contact opens at error
Rated load: 30 V DC @ 0.4 A (resistive load)
Maximum switching voltage: 125 V DC
Maximum switching power: 60 W
ORDERING INFORMATION
• Code number: 60S-16[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. 60S-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Minimum load: 10 mV DC @ 1 mA
NO. OF CHANNELS
Mechanical life: 5 x 10
7
cycles
16: 16 points
Self-diagnosis
Communication: The receiver modules detect loss of
communication and wire break.
CPU: Watch-dog timer
[1] I/O TYPE
1: Input
2: Output
Memory: Sum check
Power voltage: Detects when the voltage supply to the
CPU drops.
[2] POWER INPUT
AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
60S SPECIFICATIONS
ES-6612 Rev.3 Page 1/5
http://www.m-system.co.jp/
MODEL: 60S
COMMUNICATION
• Output Connector Pin Assignment
Configuration: Multi-drop
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Standard: Conforms to EIA RS-422
Communication: 2-wire, half-duplex
Transmission speed: 125 kbps
Control procedure: SDLC
Output
Output
Output
Output
Output
Output
Output
Output
Output
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
Data encoding: NRZ
11
13
15
17
19
21
23
25
27
29
31
33
COM
Protocol: SIN-NET (M-System's)
Error check: CRC
COM
COM
COM
Transmission distance: 500 m
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
No connection
COM
Transmission media: Twisted-pair cable CPEV-0.9 dia.
Station No.: Rotary switch
COM
COM
Terminator: Incorporated (remove jumper pin with those
modules not located at the end of transmission line)
COM
COM
COM
COM
INPUT SPECIFICATIONS
■ Analog Input
No connection
Input range: 1 – 5 V DC
INSTALLATION
Power consumption
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
•AC: Approx. 4 VA
•DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
• Input Connector Pin Assignment
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
3
4
COM
Weight: 450 g (0.99 lb)
5
6
COM
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
COM
D/A conversion: ±0.1 %
COM
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output
to SIN-NET to RUN contact output to power)
2000 V AC @ 1 minute (input or output or SIN-NET or RUN
contact output or power to FG1)
Input 10
Input 11
COM
COM
Input 12
COM
Input 13
COM
Input 14
COM
Input 15
COM
Input 16
COM
No connection
No connection
OUTPUT SPECIFICATIONS
■ Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
60S SPECIFICATIONS
ES-6612 Rev.3 Page 2/5
http://www.m-system.co.jp/
MODEL: 60S
DESCRIPTIONS
■ RUN Contact Output (LED) Behaviors
• Input module
The LED for the Input Modules turns ON when the network is on-line.
When there is an abnormality in the network, the LED turns OFF.
The network is reconfigured after an abnormality.
• Output module
The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding
Input Module.
When there is an abnormality in the network or there is no data receiving, the LED turns OFF.
■ Station Number (Address)
A) 1 input module and X output modules:
Match the address for input and output modules.
B) Computer interface:
Set address numbers to correspond with the computer as output module.
■ Transmission Time
Integrate all the transmission time for each process input module in the system.
•Analog input 16 points: 24.0 msec.
An analog module does not transmit all its signals in serial but does 1 point per each cycle. For example, when 1 contact input
module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32 point contact signal and 1 point analog
signal are transmitted in turn. One cycle time is therefore calculated as:
32 points × 1.5 msec. + 24 msec. = 72 msec.
This method is beneficial for giving a priority to contact signals which vary rapidly.
■ Applicable models for use with 60S Input Module
• 60S-162 (Ao 16 points)
• DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)
60S SPECIFICATIONS
ES-6612 Rev.3 Page 3/5
http://www.m-system.co.jp/
MODEL: 60S
¢
TRANSMISSION LINE CONFIGURATION
The multi-drop transmission line containing 22LA1, DLA1
and 60S modules should meet the following conditions.
Contact M-System's sales office or representatives when
designing.
A) 10 kilometers at maximum in total system.
B) 60S module plus DLA1 units: One multitransmission
line containing a 60S module can consist of a maximum
of 16 units within the total distance of 500 m.
7
DLA1
60S
DLA1
C) 60S modules, DLA1 units plus Repeater (model:
DAL4): DAL4 units can expand the total distance.
(6 DAL4 units max.)
DAL4
DAL4
60S
DLA1
DLA1
60S
D) 60S module, 22LA1 module plus DLA1 units: The
total distance of a section consisting of 60S and 22LA1
modules is less than 500 meters. They can be connected
to DLA1 units via a DLA1-7 unit.
(Eight DLA1-7 units max.)
22LA1
60S
DLA1
DLA1
EXTERNAL VIEW
Modular Jack
CN1
for Factory Calibration
Power Indicator LED
RUN Indicator LED
PU-2x
I/O Connector
PWR
RUN
SIN-NET Terminals
4
4
SA1
Station No. Setting
Rotary Switches
C
C
Terminals for Terminating Resistor
RUN Contact Output
SA2
60S SPECIFICATIONS
ES-6612 Rev.3 Page 4/5
http://www.m-system.co.jp/
MODEL: 60S
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
7
14
6
5
12
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
8
9
15 10
1
11
2
14–M3.5
SCREW
14
72 (2.83)
(.55)
109 (4.29)
139 (5.47)
60 (2.36)
72 (2.83)
38 (1.50)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Transmission
LED Station No. Setting Rotary SW
TWISTED PAIR
Isolation
A
B
C
D
E
F
+
−
TO OTHER
SIN-NET DEVICES
Transceiver
Circuit
Control
Circuit
A/D or D/A
Converter
JUMPER PIN *1
TERMINATING RESISTOR
Ry
To 10-RACK,
18-RACK etc.
RUN CONTACT
OUTPUT
Modular Jack
for Factory
Calibration
MODULAR JACK
SERIAL TRANSMISSION LINE
7
14
8
U(+)
V(−)
POWER
GROUNDING FG1
*1. When the unit is located at the end of transmission line via twisted-pair cable (= no cross-wiring), short across terminals C – D with the jumper pin (or wire) provided with the unit.
Remove the jumper pin for the one not located at the end.
Specifications are subject to change without notice.
60S SPECIFICATIONS
ES-6612 Rev.3 Page 5/5
http://www.m-system.co.jp/
相关型号:
60S-6093-1422-0
Board Euro Connector, 24 Contact(s), 3 Row(s), Female, Right Angle, 0.2 inch Pitch, Solder Terminal, Plug
WINCHESTER
60S-6093-1422-2
Board Euro Connector, 24 Contact(s), 3 Row(s), Female, Right Angle, 0.2 inch Pitch, Solder Terminal, Plug
WINCHESTER
60S-6093-1431-0
Board Euro Connector, 24 Contact(s), 3 Row(s), Female, Right Angle, 0.2 inch Pitch, Solder Terminal, Plug
WINCHESTER
©2020 ICPDF网 联系我们和版权申明