61C-042-R/Q [MSYSTEM]
Field Network Modules 61-UNIT Series;型号: | 61C-042-R/Q |
厂家: | M-SYSTEM |
描述: | Field Network Modules 61-UNIT Series |
文件: | 总4页 (文件大小:111K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 61C
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the 61C is to be
combined with the M8BS2.)
Field Network Modules 61-UNIT Series
ANALOG I/O MODULE
(CC-Link)
[4] OPTIONS
Functions & Features
blank: none
• Interfacing analog I/O signals from/to Mini-M, Pico-M and
other signal conditioner modules with CC-Link
• Saving power and I/O wiring inside an instrumentation
panel
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
50
(1.97)
/C02: Polyurethane coating
/C03: Rubber coating
100
(3.94)
RELATED PRODUCTS
• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
3 4
2
9
1
0
5
6
7
8
3 4
2
9
1
0
5
6
7
8
3 4
2
9
1
0
5
6
7
8
115
(4.53)
mm (inch)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
MODEL: 61C-[1][2]-[3][4]
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
ORDERING INFORMATION
• Code number: 61C-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. 61C-161-K/Q)
CC-Link: Euro type connector terminal (applicable wire
size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: Via Installation Base (model: MxBS2)
Power input: Via Installation Base (model: MxBS2)
Housing material: Flame-resistant resin (black)
Isolation: I/O to CC-Link to power
• Specify the specification for option code /Q
(e.g. /C01)
Power indicator: Green LED turns on with power supplied.
[1] NO. OF CHANNELS
04: 4 points
CC-Link COMMUNICATION
CC-Link: Conforms to Version 1.10
Station type: Remote device station
Station No. setting: Rotary switch; 1 – 64
Number of occupied stations:
08: 8 points
16: 16 points
[2] I/O TYPE
1: Input
61C-04x: 1 station
2: Output
61C-08x: 2 stations
3: Input/output (Select 16 for no. of channels)
(8 points for input, 8 points for output)
(Use Installation Base model: M8BS2-164)
61C-161: 4 stations
61C-162: 4 stations
61C-163: 2 stations
Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting: Rotary switch
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps,
10Mbps)
[3] POWER INPUT
AC Power
K: 85 – 132 V AC
Transmission cable: Approved for CC-Link
L RUN indicator: Red LED turns on in an normal condition.
L ERR. indicator: Red LED turns on or flashes in an
abnormality; off with wire breakdown.
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
61C SPECIFICATIONS
ES-6627 Rev.8 Page 1/4
http://www.m-system.co.jp/
MODEL: 61C
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.
0000 – 2710 (0 – 10000).
-15 to 0 % is a negative range represented by 2's
complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
■ D/A CONVERSION DATA
INPUT SPECIFICATIONS
■ Analog Input
Input range: 1 – 5 V DC
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Input resistance: ≥ 1 MΩ
SIGN
BIT
RWw n+0
RWw n+1
RWw n+2
RWw n+3
OUTPUT 1 D/A CONVERSION DATA
OUTPUT 2 D/A CONVERSION DATA
OUTPUT 3 D/A CONVERSION DATA
OUTPUT 4 D/A CONVERSION DATA
(Each input must be isolated by signal conditioners. Non-
isolated modules such as M2BW and M8BW are not usable.)
A/D conversion
SIGN
BIT
Moving averaging: 4 samples
SIGN
BIT
Sampling rate: 160 ms
SIGN
BIT
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
■ A/D CONVERSION DATA
SIGN
BIT
RWw n+7
RWw n+11
RWw n+15
OUTPUT 8 D/A CONVERSION DATA
OUTPUT 12 D/A CONVERSION DATA
OUTPUT 16 D/A CONVERSION DATA
SIGN
BIT
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
SIGN
BIT
RWr n+0
RWr n+1
RWr n+2
RWr n+3
INPUT 1 A/D CONVERSION DATA
INPUT 2 A/D CONVERSION DATA
INPUT 3 A/D CONVERSION DATA
INPUT 4 A/D CONVERSION DATA
SIGN
BIT
SIGN
BIT
SIGN
BIT
RWw n+0 through RWw n+3 for 4 outputs.
RWw n+0 through RWw n+7 for 8 outputs or outputs of 16-input/output.
RWw n+0 through RWw n+15 for 16 outputs.
SIGN
BIT
INSTALLATION
Power consumption
SIGN
BIT
RWr n+7
RWr n+11
RWr n+15
INPUT 8 A/D CONVERSION DATA
INPUT 12 A/D CONVERSION DATA
INPUT 16 A/D CONVERSION DATA
•AC: Approx. 4 VA
•DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: MxBS2)
Weight: 250 g (0.55 lb)
SIGN
BIT
SIGN
BIT
RWr n+0 through RWr n+3 for 4 inputs.
RWr n+0 through RWr n+7 for 8 inputs or inputs of 16-input/output.
RWr n+0 through RWr n+15 for 16 inputs.
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(I/O to CC-Link to power)
OUTPUT SPECIFICATIONS
■ Analog Output
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
(Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held. Non-isolated modules such as M2BW
and M8BW are not usable. )
D/A conversion input: Signed binary
Signal range 0 – 100 % is converted into hexadecimal
61C SPECIFICATIONS
ES-6627 Rev.8 Page 2/4
http://www.m-system.co.jp/
MODEL: 61C
EXTERNAL VIEW
PU-2
A
L
L
RUN
ERR.
E
F
SD
RD
PWR
B
C
D
STATION NO.
X
10
X1
B
RATE
A: Modular jack for factory calibration
B: Power LED
C: Station No. Setting
D: Baud rate Setting
E: Status indicator LED
F: Euro type connector terminal for CC-Link
COMMUNICATION CABLE CONNECTIONS
MASTER UNIT
61C
I/O UNIT
TERMINATOR
blue
DA
DB
DA
DB
DA
DB
white
yellow
DG
SLD
FG
DG
SLD
FG
DG
SLD
FG
EXTERNAL DIMENSIONS unit: mm (inch)
2–M3 SCREWS
12
(.47)
50 (1.97)
38 min.
(1.50)
103 (4.06)
61C SPECIFICATIONS
ES-6627 Rev.8 Page 3/4
http://www.m-system.co.jp/
MODEL: 61C
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
INDICATOR ROTARY
Terminator
DA
LED
SW
*
DB
To Other
CC-Link
Devices
CC-Link
INTERFACE
DG
SLD
FG
A / D
or
D / A
Conv.
To
Installation
Base
I / O
CPU
Modular Jack
for Factory
Calibration
MODULAR JACK
SERIAL
TRANSMISSION
LINE
Attach the terminating resistor when the module is
at the termination of a transmission line.
*
Specifications are subject to change without notice.
61C SPECIFICATIONS
ES-6627 Rev.8 Page 4/4
http://www.m-system.co.jp/