61M-161-K [MSYSTEM]

Field Network Modules 61-UNIT Series;
61M-161-K
型号: 61M-161-K
厂家: M-SYSTEM    M-SYSTEM
描述:

Field Network Modules 61-UNIT Series

文件: 总5页 (文件大小:152K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 61M  
Field Network Modules 61-UNIT Series  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
ANALOG I/O MODULE  
(Modbus; RS-485)  
Functions & Features  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Interfacing analog I/O signals from/to Mini-M, Pico-M and  
other signal conditioner modules with Modbus  
• Saving power and I/O wiring inside an instrumentation  
panel  
/C02: Polyurethane coating  
/C03: Rubber coating  
RELATED PRODUCTS  
• Installation Base (model: M2BS2)  
• Installation Base (model: M8BS2)  
50  
(1.97)  
100  
(3.94)  
PACKAGE INCLUDES...  
12  
4
5
0
7 6  
9
12  
4
5
0
• Terminating resistor (110 Ω, 0.25 W)  
7 6  
9
115  
(4.53)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
mm (inch)  
Connection  
Modbus: Euro type connector terminal (applicable wire  
size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
MODEL: 61M–16[1]–[2][3]  
I/O: Via Installation Base (model: MxBS2)  
Power input: Via Installation Base (model: MxBS2)  
Housing material: Flame-resistant resin (black)  
Isolation: I/O to Modbus to power  
ORDERING INFORMATION  
• Code number: 61M-16[1]-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. 61M-161-K/Q)  
Power indicator: Green LED turns on with power supplied.  
• Specify the specification for option code /Q  
(e.g. /C01)  
MODBUS COMMUNICATION  
Communication: Conforms to TIA/EIA-485-A  
Transmission setting: DIP switch  
NO. OF CHANNELS  
Data: RTU (Binary) or ASCII  
16: 16 points  
Parity: none, even or odd  
Baud rate: 4800, 9600, 19.2 k, 38.4 k (bps)  
Node address setting: Rotary switch; 01 – F7  
(factory setting: 00)  
[1] I/O TYPE  
1: Input  
L RUN indicator: Red LED turns on for 10 sec. when the  
module receives data.  
2: Output  
L ERR. indicator: Red LED turns on at errors in parity,  
framing, overrun, CRC or LRC.  
[2] POWER INPUT  
AC Power  
SD indicator: Red LED turns on when transmitting.  
RD indicator: Red LED turns on when receiving.  
Analog input: Programming Unit (model: PU-2x) or via  
Modbus  
K: 85 – 132 V AC  
(Operational voltage range 85 – 132 V, 47 – 66 Hz)  
DC Power  
R: 24 V DC  
Moving averaging: None, every 2 or 4 samples  
Sampling rate: 400, 240, or 160 (msec.)  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
(Specify power suffix code R (24 V DC) when the UNIT is to be  
combined with the M8BS2.)  
61M SPECIFICATIONS  
ES-6631 Rev.9 Page 1/5  
http://www.m-system.co.jp/  
MODEL: 61M  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
INPUT SPECIFICATIONS  
Analog Input  
Dielectric strength: 1500 V AC @ 1 minute (I/O to Modbus to  
power)  
Input range: 1 – 5 V DC  
Input resistance: ≥ 1 MΩ  
(Each input must be isolated by signal conditioners. Non-  
isolated modules such as M2BW and M8BW are not usable.)  
A/D conversion output  
Signed binary (2-byte data)  
Signal range 0 – 100 % is proportional to hexadecimal 0000  
– 2710 (0 – 10000). -15 to 0 % is a negative range  
represented by 2's complements.  
Overall range is represented by hexadecimal FA24 – 2CEC (-  
1500 – +11500), for -15 – +115 %.  
Floating data (4-byte data)  
Initial signal range 0 – 100 % is proportional to 0 – 10000,  
that is possible to be scaled into a specific range.  
OUTPUT SPECIFICATIONS  
Analog Output  
Output range: 1 – 5 V DC  
Load resistance: 20 kΩ minimum  
(Output must be isolated with signal conditioners.  
When the transmission line is open, the last value sampled  
before failure is held. Non-isolated modules such as M2BW  
and M8BW are not usable. )  
D/A Conversion Input  
Signed binary (2-byte data)  
Signal range 0 – 100 % is proportional to hexadecimal 0000  
– 2710 (0 – 10000). -15 to 0 % is a negative range  
represented by 2's complements.  
Overall range is represented by hexadecimal FA24 – 2CEC (-  
1500 – +11500), for -15 – +115 %.  
Floating data (4-byte data)  
Initial signal range 0 – 100 % is proportional to 0 – 10000,  
that is possible to be scaled into a specific range.  
INSTALLATION  
Power consumption  
AC: Approx. 4 VA  
DC: Approx. 4 W (160 mA)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: MxBS2)  
Weight: 250 g (0.55 lb)  
PERFORMANCE in percentage of span  
A/D conversion: ±0.1 %  
D/A conversion: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Permissible power failure duration: ≤ 10 msec.  
61M SPECIFICATIONS  
ES-6631 Rev.9 Page 2/5  
http://www.m-system.co.jp/  
MODEL: 61M  
EXTERNAL VIEW  
Modular Jack  
for Factory Calibration  
Power Indicator LED  
L RUN  
L ERR.  
SD  
Status Indicator LED  
PWR  
RD  
Node Address No. Setting  
Transmission Setting  
Euro Type Connector Terminal  
for Modbus  
1
2
3
4
5
6
MODBUS FUNCTION CODES & SUPPORTED CODES  
Data and Control Functions  
CODE  
01  
NAME  
Read Coil Status  
X
X
X
X
X
X
Digital output from the slave  
02  
Read Input Status  
Read Holding Registers  
Read Input Registers  
Force Single Coil  
Status of digital inputs to the slave  
General purpose register within the slave  
Collected data from the eld by the slave  
Digital output from the slave  
03  
04  
05  
06  
Preset Single Registers  
Read Exception Status  
Diagnostics  
General purpose register within the slave  
07  
08  
X
09  
Program 484  
10  
Poll 484  
11  
Fetch Comm. Event Counter  
Fetch Comm. Event Log  
Fetch a status word and an event counter  
12  
A status word, an event counter, a message count and  
a eld of event bytes  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
Program Controller  
Poll Controller  
Force Multiple Coils  
Preset Multiple Registers  
Report Slave ID  
X
X
Digital output from the slave  
General purpose register within the slave  
Slave type / ‘RUN’ status  
Program 884 / M84  
Reset Comm. Link  
Read General Reference  
Write General Reference  
Mask Write 4X Register  
Read/Write 4X Registers  
Read FIFO Queue  
Exception Codes  
CODE NAME  
01  
02  
03  
04  
05  
06  
07  
08  
Illegal Function  
X
X
X
Function code is not allowable for the slave  
Address is not available within the slave  
Data is not valid for the function  
Illegal Data Address  
Illegal Data Value  
Slave Device Failure  
Acknowledge  
Slave Device Busy  
Negative Acknowledge  
Memory Parity Error  
61M SPECIFICATIONS  
ES-6631 Rev.9 Page 3/5  
http://www.m-system.co.jp/  
MODEL: 61M  
Diagnostic Subfunctions  
CODE NAME  
00  
01  
02  
03  
04  
Return Query Data  
X
X
X
X
X
Loop back test  
Restart Comm. Option  
Return Diagnostic Register  
Change ASCII Input Delimiter  
Force Listen Only Mode  
Reset the slave and clear all counters  
Contents of the diagnostic data (2 bytes)  
Delimiter character of ASCII message  
Force the slave into Listen Only Mode  
MODBUS I/O ASSIGNMENT  
TYPE  
ADDRESS  
DATA TYPE  
2
DATA  
1
X
X
X
X
X
X
Coil (0X)  
1 – 16  
17 – 32  
1 – 16  
Averaging SW *  
Sampling rate SW **  
Inputs (1X)  
X
X
Analog channel status (active channel)  
Analog status (out of range)  
Analog input  
17 – 32  
1 – 16  
Input Registers (3X)  
Holding Registers (4X)  
I
17 – 48  
1 – 16  
F
I
Analog input  
X
X
X
X
Analog output  
17 – 48  
49 – 80  
81 – 112  
F
F
F
Analog output  
X
X
Full scale  
Zero scale  
Type  
1
2
: Analog input  
: Analog output  
Data Type  
F
I
: Floating  
: Int 0 – 10000 (0 – 100%)  
*Averaging SW  
1
2
3
: 4 samples  
: 2 samples  
: None  
**Sampling rate SW  
17 : 400 millisec.  
18 : 240 millisec.  
19 : 160 millisec.  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3 SCREWS  
12  
(.47)  
50 (1.97)  
38 min.  
(1.50)  
103 (4.06)  
61M SPECIFICATIONS  
ES-6631 Rev.9 Page 4/5  
http://www.m-system.co.jp/  
MODEL: 61M  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
INDICATOR ROTARY  
Terminator  
DA  
LED  
SW  
*
DB  
To Other  
Modbus  
Devices  
RS-485  
INTERFACE  
DG  
SLD  
FG  
A / D  
or  
D / A  
Conv.  
To  
Installation  
Base  
TRANSMISSION  
SETTING  
I / O  
CPU  
Modular Jack  
for Factory  
Calibration  
MODULAR JACK  
SERIAL  
TRANSMISSION  
LINE  
*Attach the terminating resistor when the module is  
at the termination of a transmission line.  
■ COMMUNICATION CABLE CONNECTIONS  
HOST PC  
TERMINATOR  
Tx+ / Rx+  
ANALOG I/O MODULE  
ANALOG I/O MODULE  
DA  
DB  
DA  
DB  
Tx– / Rx–  
SG  
DG  
SLD  
FG  
DG  
SLD  
FG  
Rx+  
Rx–  
FG  
FG  
Specifications are subject to change without notice.  
61M SPECIFICATIONS  
ES-6631 Rev.9 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

61M-161-K/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61M-161-R

Field Network Modules 61-UNIT Series
MSYSTEM

61M-161-R/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61M-162-K

Field Network Modules 61-UNIT Series
MSYSTEM

61M-162-K/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61M-162-R

Field Network Modules 61-UNIT Series
MSYSTEM

61M-162-R/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61M08-01-01

Rotary Position Encoder, Single, 2 Channels, ROHS COMPLIANT PACKAGE
GRAYHILL

61M08-01-02

Rotary Position Encoder, Single, 2 Channels, ROHS COMPLIANT PACKAGE
GRAYHILL

61M08-02-01

Rotary Position Encoder, Single, 2 Channels, ROHS COMPLIANT PACKAGE
GRAYHILL

61M08-02-02

Rotary Position Encoder, Single, 2 Channels, ROHS COMPLIANT PACKAGE
GRAYHILL

61M10

Rectifier Diode, 1 Phase, 1 Element, 60A, 100V V(RRM), Silicon,
NIEC