MODEL: 61S  
Field Network Modules 61-UNIT Series  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
ANALOG I/O MODULE  
(Multiplex Transmission System)  
Functions & Features  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Interfacing analog I/O signals from/to Mini-M or Pico-M  
modules with Multiplex Transmission System  
• Saving power and I/O wiring inside an instrumentation  
panel  
/C02: Polyurethane coating  
/C03: Rubber coating  
50  
(1.97)  
RELATED PRODUCTS  
• Installation Base (model: M2BS2)  
• Installation Base (model: M8BS2)  
100 (3.94)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection  
115 (4.53)  
SIN-NET, RUN contact output: Euro type connector  
mm (inch)  
terminal (applicable wire size: 0.2 to 2.5 mm  
2,  
stripped length 7 mm)  
I/O: Via Installation Base (model: MxBS2)  
MODEL: 61S–16[1]–[2][3]  
Power input: Via Installation Base (model: MxBS2)  
Housing material: Flame-resistant resin (black)  
Isolation: I/O to SIN-NET to RUN contact output to power  
Power indicator: Red LED turns ON in normal conditions;  
OFF when the voltage level becomes low.  
RUN indicator: Red LED turns ON when the selfdiagnosis  
proves normal, OFF in an abnormality.  
ORDERING INFORMATION  
Code number: 61S-16[1]-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. 61S-161-K/Q)  
• Specify the specification for option code /Q  
(e.g. /C01)  
RUN Contact Output: Contact opens at error  
Rated load: 30 V DC @ 0.4 A (resistive load)  
Maximum switching voltage: 125 V DC  
NO. OF CHANNELS  
Maximum switching power: 60 W  
16: 16 points  
Minimum load: 10 mV DC @ 1 mA  
Mechanical life: 5 x 10  
7
cycles  
Self-diagnosis  
[1] I/O TYPE  
1: Input  
Communication: The receiver modules detect loss of  
communication and wire break.  
CPU: Watch-dog timer  
2: Output  
Memory: Sum check  
[2] POWER INPUT  
AC Power  
Power voltage: Detects when the voltage supply to the  
CPU drops.  
K: 85 – 132 V AC  
(Operational voltage range 85 – 132 V, 47 – 66 Hz)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
(Specify power suffix code R (24 V DC) when the UNIT is to be  
combined with the M8BS2.)  
61S SPECIFICATIONS  
ES-6637 Rev.2 Page 1/5  
http://www.m-system.co.jp/  
MODEL: 61S  
Dielectric strength: 1500 V AC @ 1 minute (I/O to SIN-NET to  
RUN contact output to power)  
COMMUNICATION  
Configuration: Multi-drop  
Standard: Conforms to EIA RS-422  
Communication: 2-wire, half-duplex  
Transmission speed: 125 kbps  
Control procedure: SDLC  
Data encoding: NRZ  
Protocol: SIN-NET (M-System's)  
Error check: CRC  
Transmission distance: 500 m  
Transmission media: Twisted-pair cable CPEV-0.9 dia.  
Station No.: Rotary switch  
Terminator: Incorporated (remove jumper pin with those  
modules not located at the end of transmission line)  
INPUT SPECIFICATIONS  
Analog Input  
Input range: 1 – 5 V DC  
Input resistance: ≥ 1 MΩ  
(Each input must be isolated by signal conditioners. Non-  
isolated modules such as M2BW and M8BW are not usable.)  
A / D conversion  
Moving averaging: 4 samples  
Sampling rate: 160 ms  
OUTPUT SPECIFICATIONS  
Analog Output  
Output range: 1 – 5 V DC  
Load resistance: 20 kΩ minimum  
(Output must be isolated with signal conditioners.  
When the transmission line is open, the last value sampled  
before failure is held. Non-isolated modules such as M2BW  
and M8BW are not usable. )  
INSTALLATION  
Power consumption  
AC: Approx. 4 VA  
DC: Approx. 4 W (160 mA)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: MxBS2)  
Weight: 250 g (0.55 lb)  
PERFORMANCE in percentage of span  
A/D conversion: ±0.1 %  
D/A conversion: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Permissible power failure duration: ≤ 10 msec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
61S SPECIFICATIONS  
ES-6637 Rev.2 Page 2/5  
http://www.m-system.co.jp/  
MODEL: 61S  
DESCRIPTIONS  
RUN Contact Output (LED) Behaviors  
Input module  
The LED for the Input Modules turns ON when the network is on-line.  
When there is an abnormality in the network, the LED turns OFF.  
The network is reconfigured after an abnormality.  
Output module  
The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding  
Input Module.  
When there is an abnormality in the network or there is no data receiving, the LED turns OFF.  
Station Number (Address)  
A) 1 input module and X output modules:  
Match the address for input and output modules.  
B) Computer interface:  
Set address numbers to correspond with the computer as output module.  
Transmission Time  
Integrate all the transmission time for each process input module in the system.  
• Analog input 16 points: 24 msec.  
An analog module does not transmit all its signals in serial but does 1 point per each cycle. For example, when 1 contact input  
module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32-point contact signal and 1 point analog  
signal are transmitted in turn.  
One cycle time is therefore calculated as:  
32 points x 1.5 msec. + 24 msec. = 72 msec.  
This method is beneficial for giving a priority to contact signals which vary rapidly.  
Applicable models for use with 61S Input Module  
• 61S-162 (Ao 16 points)  
• DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)  
61S SPECIFICATIONS  
ES-6637 Rev.2 Page 3/5  
http://www.m-system.co.jp/  
MODEL: 61S  
¢
TRANSMISSION LINE CONFIGURATION  
The multi-drop transmission line containing 22LA1, DLA1 and  
61S modules should meet the following conditions.  
Contact M-System's sales office or representatives when  
designing.  
A) 10 kilometers at maximum in total system.  
B) 61S modules plus DLA1 units: One multitransmission  
line containing a 60S module can consist of a maximum of  
16 units within the total distance of 500 m.  
DLA1  
61S  
DLA1  
C) 61S modules plus DLA1 units plus Repeaters (model:  
DAL4): DAL4 units can expand the total distance.  
(6 DAL4 units max.)  
DAL4  
DAL4  
7
7
61S  
DLA1  
DLA1  
61S  
D) 61S modules plus 22LA1 modules plus DLA1 units:  
The total distance of a section consists of 61S and 22LA1  
modules is less than 500 meters.  
They can be connected to DLA1 units via a DLA1-7 unit.  
(Eight DLA1-7 units max.)  
7
22LA1  
61S  
DLA1  
DLA1  
EXTERNAL VIEW  
Modular Jack  
for Factory Calibration  
Power Indicator LED  
RUN Indicator LED  
PU-2x  
PWR  
RUN  
SIN-NET Terminals  
4
4
SA1  
Station No. Setting  
Rotary Switches  
C
C
Terminals for Terminating Resistor  
RUN Contact Output  
SA2  
61S SPECIFICATIONS  
ES-6637 Rev.2 Page 4/5  
http://www.m-system.co.jp/  
MODEL: 61S  
EXTERNAL DIMENSIONS unit: mm (inch)  
2-M3 SCREW  
12  
(.47)  
38 min  
(1.50)  
50 (1.97)  
103 (4.06)  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Station No.  
Indicator Setting Rotary  
LED Switches  
TWISTED-PAIR  
Isolation  
A
B
C
D
E
F
TO OTHER  
SIN-NET DEVICES  
Control  
Circuit  
A/D or D/A  
Converter  
Transceiver  
TERMINATING RESISTOR  
JUMPER PIN*  
Ry  
To Installation Base  
RUN CONTACT  
OUTPUT  
Modular Jack  
for Factory  
Calibration  
MODULAR  
JACK  
SERIAL TRANSMISSION LINE  
* When the unit is located at the end of transmission line via twisted-pair cable (= no cross-wiring),  
short across terminals C - D with the jumper pin (or wire) provided with the unit.  
Remove the jumper pin for the one not located at the end.  
Specifications are subject to change without notice.  
61S SPECIFICATIONS  
ES-6637 Rev.2 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY