MODEL: 73VR1100
Paperless Recording System
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
PAPERLESS RECORDER
(remote I/O modules)
Functions & Features
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• 100 msec. storing rate for the max. of 64 points (1
station) with the R3-NE1 module
• Graphic image view helps to recognize measuring points
and signal status at a glance
/C02: Polyurethane coating
/C03: Rubber coating
• Data stored in CF Cards and SD Cards
• Memory card slot accessible at the front
• Real time monitoring at the host PC via Ethernet
• Dedicated application software to view and analyze the
data
TERMINAL SCREW MATERIAL
/S01: Stainless steel
INSTALLATION
/HA: Desktop type (with handle and feet)
(Desktop type cannot be mounted on a panel surface.
The handle and rubber feet cannot be detached.)
• Touch panel operation
• IP 65 front panel
RELATED PRODUCTS
144 (5.67)
Please refer to data sheets for the respective models.
• PC recorder R1M, R2M, R1MS, RZMS series
• Remote I/O R3 series
Ethernet (Modbus/TCP) interface module (model: R3-NE1)
Modbus interface module (model: R3-NM1)
• Remote I/O R5 series
144
(5.67)
133
(5.24)
Ethernet (Modbus/TCP) interface module (model: R5-NE1)
Modbus interface module (model: R5-NM1)
• Modbus I/O module (model: R7M)
mm (inch)
• Ethernet I/O module, Modbus/TCP (model: R7E)
R7 configurator software (model: R7CON) To connect with
R7M series, change Modbus Communication Parameters of
the R7M by using R7CON and the special cable.
• Multi power monitor (model: 53U)
MODEL: 73VR1100-[1]-[2][3]
ORDERING INFORMATION
• Code number: 73VR1100-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 73VR1100-E-M2/Q)
· Ethernet tower light (Model: IT60RE, IT40SRE, IT50SRE,
IT60SRE)
Lamps and buzzer are turned on/off in combination with
alarm output of 73VR1100.
• Specify the specification for option code /Q
(e.g. /C01/S01/HA)
• Ethernet communication adaptor (model: 72EM2-M4)
■ Memory card
A memory card is required to store data in the 73VR1100.
Available for purchase from M-System. Consult M-System
(except SD/CF conversion adapter).
[1] LANGUAGE
N: Japanese
E: English
M-System will not guarantee the product’s described
performance if a memory card other than purchased from M
-System, or specified below, is used.
[2] POWER INPUT
AC Power
• CF Card
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
1. Manufacturer: Hagiwara Solutions
47 – 66 Hz)
Model No.: MCF10P-xxxxS
(CE not available for desktop type)
Capacity: 128 MB through 1 GB
DC Power
(CFI-xxxxDG ... discontinued)
R: 24 V DC
2. Manufacturer: Apacer Technology
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Model name: CFC III
Model No.: AP-CFxxxxE3NR-ETNDNRQ
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 1/18
https://www.m-system.co.jp/
MODEL: 73VR1100
Capacity: 256 MB through 1 GB
RUN output indicator LED: Green light turns on in normal
conditions; off in an abnormality.
Part No.: 81.27L20.TB47C (256 MB)
81.29910.TB37C (512 MB)
Power indicator LED: Green light turns on when the power is
supplied.
81.29920.TB37C (1 GB)
(AP-CFxxxxE3ER-ETNDNR, AP-CFxxxxE3ER-ETNDNRK ...
discontinued)
■ INTERFACE
Ethernet: 10BASE-T / 100BASE-TX automatically switched;
Conforms to IEEE 802 (10BASE-T) or IEEE 802.3 (100BASE-
TX)
• SD Card (Compatible with 73VR1100 Ver.5.03.xx or later)
Manufacturer: Hagiwara Solutions
Model No.: NSD6-004GH (B21SEI
IP address: 192.168.0.1 (factory default setting)
Subnet mask: 255.255.255.0 (factory default setting)
Default gateway: None (factory default setting)
CF Card slot: Type I; for use with the cards’ operating
voltage 3.3 V
(NSDA-004GT, NSDA-004GL ... discontinued)
SD/CF Conversion Adapter is required to use SD card. There
are some restrictions on using SD card. For details, refer to
the instruction manual.
• SD/CF Conversion Adapter (operation confirmed):
DeLOCK adaptor CF II to SDHC,SDXC
USB: Conforms to Version 1.1
■ DISPLAY
Model: 61796 (operation has been confirmed with the
adapter purchased in the year of 2016.)
62637 (operation has been confirmed with the
adapter purchased in the year of 2018.)
Note: Refer to the data sheets of the respective models.
Display device: 5.5-inch TFT LCD
Display colors: 256
Resolution: 320 × 240 pixels
Pixel pitch: 0.12 × 0.35 mm
Note: The backlight can be replaced in M-System factory.
The LCD must be replaced at the same time.
■ ALARM / RUN OUTPUT
PACKAGE INCLUDES...
• 73VR Application Software CD (model: 73VRPAC2)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
(For desktop type EU conformity: < 50 V AC)
30 V DC @ 0.5 A (resistive load)
• Mounting brackets (two)
(/HA: Not included for desktop type)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
GENERAL SPECIFICATIONS
Construction: Panel mount type or desktop type
Degree of protection: IP65; applicable to the front panel of
the recorder with single mounting according to the specified
panel cutout (/HA: Desktop type cannot be mounted on a
panel surface)
Mechanical life: 2 × 10 cycles (rate 300/min.)
7
External protection is recommended when driving an
inductive load.
RUN output contact: ON in normal conditions; OFF in errors
(CPU error, application errors)
■ CONNECTION
Alarm output contact: Specified in the application software
Power input, alarm output, RUN contact output: M3
separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
EXTERNAL INTERFACE
■ Modbus RTU
Configuration: Half-duplex, asynchronous, no procedure
Standard: Conforms to TIA/EIA RS-485-A
Max. transmission distance: 500 meters
Transfer rate: 38400 bps
Ethernet: RJ-45 Modular Jack
RS-485: Euro type connector terminal
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)
Data bit: 8
Applicable wire size: 0.2 to 2.5 mm or AWG 24 to AWG 12
2
Parity bit: Odd
for both stranded and single core wires. stripped length 7
mm. Use pin terminals with stranded wires.
■ MATERIALS
Stop bit: 1
Max. node number: 15 (except the master)
Transmission media:
Enclosure: Steel
Shielded twisted-pair cable (CPEV-S φ0.9)
Terminating resistor: incorporated
Bezel: Flame-resistant resin (black)
Front filter: Transparent resin
Isolation: Alarm output to RUN output to power to Ethernet
to FG or RS-485
■ INDICATORS
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 2/18
https://www.m-system.co.jp/
MODEL: 73VR1100
INSTALLATION
Power input
•AC:
Approx. 15 VA at 100 V
Approx. 20 VA at 240 V
•DC: 8 W or 340 mA
Operating temperature: 0 to 50°C (32 to 122°F)
Display quality (e.g. decreased contrast) may deteriorate
when the recorder is used for a long time in an environment
exceeding 50°C. However, it is only a temporary
phenomenon. When the recorder is back in normal
temperature, full legibility is recovered. No damage in
performance.
Operating humidity: 30 to 85 %RH (non-condensing)
Allowable dust particles: 0.1 mg/m
2
(no conductive particles)
Corrosive gas: Not allowed
Mounting: Panel flush mounting (except desktop type)
Panel cutout dimensions: 137 × 137 mm (5.39”× 5.39”)
Weight: 1.7 kg (3.7 lb)
Caution: Use of UPS (switching time: without delay, output:
sine waveforms) is recommended to prevent data loss or CF
card damage by a loss of power during recording.
PERFORMANCE
Calendar clock accuracy: Monthly deviation 3 minutes at
25°C
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(alarm output to RUN output to power or FG or RS-485)
AC powered:
2000 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)
DC powered:
1250 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)
STANDARDS & APPROVALS
EU conformity:
(M2 AC power of desktop type does not conform to EU
directive)
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Alarm output to RUN output to power to FG or Ethernet or
RS-485: Reinforced insulation (300 V)
RoHS Directive
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 3/18
https://www.m-system.co.jp/
MODEL: 73VR1100
APPLICATION SOFTWARE CD
■ 73VRPAC2 (included in the product package)
• 73VR1100 Builder Software: Model 73VR11BLD
Used to configure parameters on the PC.
- Parameter configurations can be downloaded to the recorder via Ethernet.
- Present setting on the 73VR1100 can be uploaded and displayed on the PC.
- Configuration files can be converted into CSV.
• 73VR Data Viewer: Model 73VRWV
Used to show and analyze recorded data on the PC.
- Data stored in the CF Card can be called up on the PC screen via the CF Card Reader.
- Data stored in the CF Card can be sent by FTP and called up on the PC screen.
- Various analyzing functions
- Data, alarm history and comment files can be converted into CSV.
• PC Recorder Software: Model MSR128-V6
The 73VR1100 data can be sampled and stored in real time via Ethernet by the MSR128-V6.
• Instruction Manuals
- 73VR1100 users manual
- 73VR11BLD users manual
- 73VRWV users manual
- MSR128-V6 users manual
PC REQUIREMENTS (provided by the user)
■ 73VR1100 Builder Software: Model 73VR11BLD
Operating system
Windows 7 Professional (32-bit) or Windows 10 (32-bit, 64-bit)
Note: Proper software functions may not be ensured under certain conditions.
1024 by 768 pixels or better resolution
Screen area
CD drive
Windows supported CD drive is used to install the software program.
Used to read/write the CF Card
Card reader
Mouse
Windows supported
LAN card
LAN card required to connect to Ethernet; 10BASE-T or 100BASE-T cable
■ 73VR Data Viewer: Model 73VRWV
Operating system
Windows 7 Professional (32-bit) or Windows 10 (32-bit, 64-bit)
Note: Proper software functions may not be ensured under certain conditions.
1024 by 768 pixels or higher
Screen area
Display color
65000 colors (16-bit)
Main memory (RAM) 2 GB recommended
CD drive
Card reader
Mouse
Windows supported CD drive is used to install the software program.
Used to read/write the CF Card
Windows supported (Certain functions of the 73VR may be compromised if the mouse’s software driver is
not Windows standard.)
LAN card
LAN card required to connect to Ethernet; 10BASE-T or 100BASE-T cable
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 4/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ PC Recorder Software: Model MSR128-V6
NORMAL MODE (storing rates ≥ 500 ms)
IBM PC/AT or compatible
HIGH SPEED MODE (storing rates 100 / 200 ms)*1
PC
Operating system
Windows XP SP1, SP2, SP3, Windows Vista Business (32-bit), Windows 7 Professional (32-bit) or
Windows 10 (32-bit, 64-bit)
Note: Proper software functions may not be ensured under certain conditions.
CPU
Pentium III 800 MHz or higher
1 GHz higher for Windows Vista, Windows 7,
Windows 10
Pentium IV 2.0 GHz or higher
Screen area
Display color
Video memory
Main memory
1024 by 768 pixels or better resolution
65000 colors (16-bit)
2 MB minimum; 4 MB recommended
4 MB minimum
256 MB recommended for Windows XP
512 MB recommended for Windows XP
1 GB recommended for Windows Vista, Windows 7, 1 GB recommended for Windows Vista, Windows 7,
Windows 10
Use an internal hard disk.*2
Windows 10
Use an internal hard disk.*2
Hard disk area
Printer
Max. approx. 100 MB required per day.
Max. approx. 500 MB required per day.
Use a printer for Windows. The programs use Standard System Fonts used in Windows.
Use a printer driver for Standard System Fonts.
Windows supported CD drive is used to install the software program.
CD drive
Card reader drive
Used with devices which save data in a CF Card
RS-232-C port (COM1 through COM5) supported LAN card by Windows
LAN card
Communication port
*1. The 73VR1100 or the 73VR21x cannot be used in High Speed Mode.
*2. External (e.g. SCSI) devices may impair appropriate performance.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 5/18
https://www.m-system.co.jp/
MODEL: 73VR1100
EXTERNAL VIEW
■ FRONT VIEW
(1) Touch Panel Screen
(2) Front Cover
(3) CF Card Slot
(7) USB Connector
(4) Eject Button
(6) CF Card Access Indicator LED
(5) Reset Button
■ REAR VIEW
(8) RS-485 Terminal Block
(14) Alarm Output Terminal
(9) LAN Port
ALM ALM
U V
(+) (–)
+
–
RUN
+
RUN FG
–
(
10) RUN Output Indicator LED
11) Power Indicator LED
12) Power Input Terminal
13) RUN Output Terminal
(
(
(
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 6/18
https://www.m-system.co.jp/
MODEL: 73VR1100
COMMUNICATION CABLE CONNECTIONS
■ R3-NM1, R5-NM1, R7M
R3-NM1
R5-NM1
R7M
R3-NM1
R5-NM1
R7M
73VR1100
RS-485
RS-485
Terminator
DA
DA
DB
DA
Terminator
DB
DB
1
*
TR
DG
FG
DG
SLD
FG
DG
SLD
FG
2
*
FG
■ PC RECORDER, 53U
73VR1100
Terminator
PC Recorder
53U
PC Recorder
53U
RS-485
RS-485
DA
DB
TR
DG
FG
T1
T2
T3
T4
T1
T2
1
1
*
*
T3
T4
2
*
FG
2
*
FG
*1. Internal terminating resistor is used when the device is at the extreme end of a transmission line.
*2. Install shield cables to all sections and ground them at a single point.
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
Ethernet
10BASE-T / 100BASE-TX
RJ-45 MODULAR JACK
DA
DB
TR
DG
FG
*
To I/O Devices
USB
RUN +
RUN –
ALM +
ALM –
U (+)
POWER
V (–)
FG
*Short across these terminals when the device is at the extreme end of a transmission line.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 7/18
https://www.m-system.co.jp/
MODEL: 73VR1100
EXTERNAL DIMENSIONS unit: mm [inch]
· Panel mount type
136.5 (5.37)
133 (5.24)
151.5 (5.96)
144 (5.67)
29.2
2 to 26 panel thickness
(.08 to 1.02)
(1.15)
Attach the mounting bracket either on the top/bottom or on the sides.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 8/18
https://www.m-system.co.jp/
MODEL: 73VR1100
· Desktop type
136.5 (5.37)
144 (5.67)
133 (5.24)
29.2
(1.15)
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 9/18
https://www.m-system.co.jp/
MODEL: 73VR1100
PANEL CUTOUT (unit: mm)
Usable panel thickness: 2 – 26 mm (0.08” – 1.02”)
■ SINGLE MOUNTING
■ VERTICAL CLUSTERED MOUNTING (max. 3 units)
137+2
137+2
0
0
L+2 (mm)
Number
0
2
3
282
426
4
570
175 min
5
714
6
858
■ HORIZONTAL CLUSTERED MOUNTING
7
1002
1146
1290
1434
8
9
10
n
(114
× n) – 6
L +2
Notes
0
1. Dimensional tolerance 3ꢀ unless otꢁerꢂise sꢃeciꢄieꢅ.
( 0.3 mm ꢄor < 10 mm)
2. Desktoꢃ tyꢃe cannot be mounteꢅ on a ꢃanel surꢄace.
one 72EM2-M4 station.
SOFTWARE FUNCTIONS
■ NUMBER OF INPUT PEN POINTS
High speed mode: 64 points
RS-485: 15 nodes
■ DATA STORING METHOD
Normal: Recording is manually initiated and stopped. Data
is continuously stored while the recording is on.
Auto: Recording is automatically initiated and stopped at a
predefined time.
Normal mode: 128 points
Function pen points are included in the above figures.
■ TYPE OF I/O DEVICES
High speed mode: R3-NE1
Event recording: The recorder detects an external event by
trigger signal, and stores preset number of samples (max.
1200 respectively) before and after the moment of event.
Remote trigger: Data is automatically recorded while the
external trigger condition (input) is true.
■ STORING RATE
Normal mode: R1M-GH2, R1M-J3, R1M-A1, R1M-D1, R1M-P4,
R1MS-GH3, R2M-2G3, R2M-2H3, RZMS-U9, R3-NE1, R3-NM1,
R5-NE1, R5-NM1, R7E, R7M, 53U, IT60RE, IT40SRE, IT50SRE,
IT60SRE
■ NUMBER OF I/O DEVICES
Ethernet
High speed mode: 100 msec.
High speed mode: 1 station
Normal mode: 500 msec., 1, 2, 5, 10 seconds, 1 minute, 10
Normal mode: 2 stations; Max. 15 nodes are connectable to
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 10/18
https://www.m-system.co.jp/
MODEL: 73VR1100
minutes (Actual storing rate depends upon the number of
I/O devices. Contact M-System for more information.)
[Example] Max. number of I/O devices that ensures 500
msec. storing intervals under the following conditions:
Data cycle priority on alarm, RS-485 connection, no trigger
or alarm setting
Peak (minimum) hold (tracking decreasing signal)
F value: F value
Anemoscope (16 directions)
Alarm: Alarm trip can be programmed for calculated results.
■ DATA DISPLAY FUNCTIONS
• Trend View
R1M-GH2: 10
Chart direction: Perpendicular or horizontal
Number of pens displayed: 2, 4, 6, 8 per view
Number of display views: 4
RZMS-U9: 2
R3-NE1: 1 (128 channels, analog input only)
■ DATA STORAGE
Chart speed:(Chart speed is described as number of pixels
to plot single data sample.)(pixel(s)/samples)
•4, 1, 1/5, 1/32
Data file: Stores momentary values in the storing rate and
their calculation result.
Alarm history file: Records time index information when
alarms are triggered and reset.
•1/160, 1/480 or 1/960 (Not selectable with 100 msec.
storing rate)
Oldest data is overwritten with new data when the number
of records reaches its limit.
Display rate:(Common setting to all views)
1, 2 or 5 sec.
Comment history file: Records comments written in trend
views with time index. Oldest data is overwritten with new
data when the number of records reaches 1000 files.
Configuration file: Stores the 73VR1100 setting.
File format: Binary
Pen thickness: Normal and wide
Digital indicator: Shows momentary value.
Alarm indicator: Shows alarm status of the channels
displayed on the screen.
Comment: Shows comments entered manually.
Scale: Linear and square root; Switchable to the engineering
unit scale.
Oldest measured data is overwritten with new data or data
recording is stopped when the card memory is full.
■ ALARM
• Bargraph View
• Analog Alarm
Bargraph direction: Perpendicular or horizontal
Number of pens displayed: 2, 4, 6, 8 per view
Number of display views: 4
Alarm setpoints: Max. 4 points per channel
Alarm type: High / Low
Deadband: Set in engineering unit values
Output: Remote output devices
Display rate:(Common setting to all views)
1, 2 or 5 sec.
• Discrete Alarm
Digital indicator: Shows momentary value.
Alarm indicator: Shows alarm status of the channels
displayed on the screen.
Alarm type: ON / OFF
Delay time: Selectable
Output: Remote output devices
Scale: Linear and square root;
• Data Storage: Trigger time, reset time, pen number and
tag name, alarm message
Switchable to the engineering unit scale.
• Overview
Number of stored alarm events: Depends upon the CF Card
capacity.
Number of pens displayed: 2, 4, 6, 8, 16 per view
Number of display views: 64
128 MB: 250 events
Display rate:(Common setting to all views)
1, 2, or 5 sec.
256 MB: 500 events
512 MB or 1 GB: 1000 events
Alarm indicator: Shows alarm status and date/time of the
last alarm trip and reset for the channels displayed on the
screen.
■ CALCULATION FUNCTIONS
Function pen points
High speed mode: 32 points
• Graphic View
Normal mode: 32 or 64 points selectable
Operations
Number of display views: 2
Display rate:(Common setting to all views)
1, 2 or 5 sec.
Arithmetic: Addition/subtraction, Multiplication, Division
Logical: AND, OR, NOT, XOR
Background image file format: .bmp
Background image size: 320 by 240 pixels
Background image color: 256
Mathematical: Square root extractor, Power
Accumulation: Analog accumulation, Pulse accumulation
(per time unit)
Number of components displayed: Max. 64 per view
• Retrieve View: Shows data stored in the CF Card.
Number of pens displayed: 2, 4, 6, 8 per view
Filter: Moving average, First order lag
Hold: Peak (maximum) hold (tracking increasing signal),
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 11/18
https://www.m-system.co.jp/
MODEL: 73VR1100
Number of display views: 4
Supported Function Codes
CODE NAME
Data search: Scrolling the chart, specifying a specific time
index, or searching by max./min. values.
• Alarm History View: Shows data stored in the alarm
history file.
FUNCTION
01
02
04
11
Read Coil Status
Reads DO
Read Input Status
Reads DI
Read Input Register
Reads Input Register
Fetch Communication
Event Counter
Reads Status Word and
Event Counter from
Comm. Event Counter
Number of displayed alarm events: 16
Number of display views: 1
Display update: Automatically updated by a new event
Data search: Scrolling the view or specifying a specific time
index.
Exception Response
CODE NAME
FUNCTION
Jump: Scroll the view to an alarm event to show the relevant
data on Retrieve View.
01
02
Illegal Function
Function Not supported
Illegal Data Address
Speci!ed address does
not exist
• Comment History View: Shows data stored in the
comment history file.
Supported Function Codes
Number of displayed alarm events: 16
Number of display views: 1
Data storing rate 100 msec.
ADDR. TYPE NAME
Data search: Scrolling the view or specifying a specific time
index.
Coil (0X)
1
2
3
Discrete output (pen 1, relay 1)
Discrete output (pen 1, relay 2)
Jump: Scroll the view to a comment to show the relevant
data on Retrieve View.
Discrete output (pen 1, relay 3)
(Unused with discrete alarm)
■ ETHERNET COMMUNICATION
4
Discrete output (pen 1, relay 4)
(Unused with discrete alarm)
Monitoring data and setup of the 73VR1100 is possible on
the PC connected via Ethernet.
:
:
255
Discrete output (pen 64, relay 3)
(Unused with discrete alarm)
• Dedicated Protocol
Real time communication: Transmits specific data to a host
PC installed with the PC Recorder Software (model:
MSR128). Max. 2 hosts.
256
257
Discrete output (pen 64, relay 4)
(Unused with discrete alarm)
Discrete output
(alarm output terminal)
FTP communication: Transmits data stored in the CF Card
using the FTP protocol to a host PC by the 73VR Data Viewer
(model: 73VRWV) installed in it. Data can be transmitted
even during recording.
Input
Status (1X)
1 thr. 64
Input or function data
(discrete)
Input
Register (3X)
1 thr.
128
I or Input or function data
(analog)
F
Download, Upload: Software configurations created on the
73VR1100 Configuration Builder (model: 73VR11BLD) can
be downloaded to the 73VR1100. The configuration set up
on the 73VR1100 can be uploaded and displayed on the
73VR11BLD.
Data storing rate 500 msec.
ADDR. TYPE NAME
Coil (0X)
1
2
3
Discrete output (pen 1, relay 1)
Discrete output (pen 1, relay 2)
Discrete output (pen 1, relay 3)
(Unused with discrete alarm)
• Modbus Protocol
Protocol: Modbus/TCP
4
Discrete output (pen 1, relay 4)
(Unused with discrete alarm)
Port No.: 502 (fixed)
IP address: Set on the recorder
:
:
Subnet mask: Set on the recorder
511
Discrete output (pen 128, relay 3)
(Unused with discrete alarm)
Default gateway: Set on the recorder
Max. number of 73VR1100 connected simultaneously: 2
512
513
Discrete output (pen 128, relay 4)
(Unused with discrete alarm)
Discrete output
(alarm output terminal)
Input
Status (1X)
1 thr.
128
Input or function data
(discrete)
Input
Register (3X)
1 thr.
256
I or Input or function data
(analog)
F
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 12/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ OTHER FUNCTIONS
• R3 Series Remote I/O
• Operation Lockout
SIGNAL TYPE
MODELS
With a password setting, unauthorized operations on the
Trend View, Bargraph View and Overview can be locked out.
• Data File Used Volume Information
A bargraph with % indication is provided on the screen to
show how much percent of the data file memory has been
used up.
DC voltage input
R3-SV4, R3-SV4A, R3-SV4B,
R3-SV4C, R3(Y)-SV8, R3-SV8A,
R3-SV8B, R3-SV8C, R3(S/Y)-SV8N,
R3-SV16N, R3Y-SV16
DC current input
R3-SS4, R3(Y)-SS8, R3(S/Y)-SS8N,
R3(Y)-SS16N
Thermocouple input R3-TS4, R3-TS8
0 – 49 % used: Green bargraph
RTD input
R3-RS4, R3(S)-RS4A, R3(Y)-RS8,
50 – 79 % used: Amber bargraph
R3-RS8A, R3-RS8B
R3-US4
80 – 100 % used: Red bargraph
Universal input
Discrete input
• Hot Swapping of the CF Card
R3(S/Y)-DA16, R3(Y)-DA16A,
The CF Card is hot swappable: removable during data
recording. However, there may be a slight disturbance in
storing rate when the card is inserted.
• Screen Saver
R3-DA16B, R3-DA32A, R3-DA64A
Discrete output
R3(Y)-DC16, R3-DC16A, R3-DC16B,
R3-DC16C, R3-DC32A, R3-DC32C,
R3-DC64A, R3-DC64C
Discrete I/O
R3(S)-DAC16*, R3(S)-DAC16A*
The backlight is automatically turned off if the screen is
untouched for a certain time period.
• Writing/Reading Setting
4 – 20mA input with R3(Y)-DS4, R3-DS8N, R3(Y)-DS8N
excitation supply
Potentiometer input R3-MS4, R3(Y)-MS8
The recorder’s present setting can be stored in a USB flash-
memory. Setting stored in the memory can be read in to the
73VR1100.
CT input
R3-CT4
AC current input with R3-CT4A**, R3-CT4B**, R3-CT4C,
clamp-on current
sensor
R3-CT8A**, R3-CT8B**, R3-CT8C
■ SELECTABLE REMOTE I/O MODULES
PT input
R3-PT4
• PC Recorder (R1, R2, RZ) Series
Zero-phase current R3-CZ4
input
SIGNAL TYPE
MODELS
DC voltage input
R1M-GH2, R1MS-GH3, R2M-2G3,
RZMS-U9
AC power input
R3-WT4, R3-WT4A, R3-WT4B,
R3-WTU
R3-PA4
Thermocouple input
R1M-GH2 R1MS-GH3, R2M-2H3,
RZMS-U9
High speed pulse
input
DC current input
RTD input
R1M-GH2 R1MS-GH3, RZMS-U9
R1M-J3, RZMS-U9
R1M-J3, RZMS-U9
R1M-A1
Speed/position input R3-PA2
Totalized pulse input R3-PA4A, R3-PA4B, R3(Y)-PA16,
R3(S)-PA8
Potentiometer input
Contact input
Strain gauge input
Alarm
R3-LC2
Contact output
Pulse input
R1M-D1
R3-AD4, R3-AR4, R3-AS4, R3-AS8,
R3-AT4, R3-AV4, R3-AV8
R1M-P4
Totalized pulse input
R1M-P4, R1M-A1
Gateway
R3-GC1, R3-GD1, R3-GE1,
R3-GFL1, R3-GM1
*
Only continuous output mode is available.
** Data range must be setup with the PC Con!gurator Software
R3CON and the dedicated cable.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 13/18
https://www.m-system.co.jp/
MODEL: 73VR1100
• R5 Series Remote I/O
• ETHERNET Tower Light
SIGNAL TYPE
DC voltage input
DC current input
Thermocouple input
RTD input
MODELS
SIGNAL TYPE
Discrete output
MODELS
R5-SV, R5T-SV
IT60RE, IT40SRE, IT50SRE,
IT60SRE
R5-SS, R5T-SS
R5-TS, R5T-TS
R5-RS, R5T-RS
Discrete input
R5-DA4, R5T-DA4, R5-DA16
R5-DC4, R5T-DC4, R5-DC16
R5-DS, R5T-DS
Discrete output
4 – 20 mA input with
excitation supply
Potentiometer input
CT input
R5-MS
R5T-CT
AC current input with
clamp-on current sensor
PT input
R5T-CTA*, R5T-CTB*
R5T-PT
* Data range must be setup with the PC Con!gurator Software
R5CON and the dedicated cable.
• R7M Series Remote I/O*
SIGNAL TYPE
DC voltage/current input
Thermocouple input
RTD input
MODELS
R7M-SV4
R7M-TS4
R7M-RS4
Potentiometer input
CT input
R7M-MS4
R7M-CT4E
R7M-DA16
Discrete input
Discrete output
R7M-DC16A, R7M-DC16B,
R7M-DC8C
Discrete input (Extension) R7M-EA8, R7M-EA16
Discrete output (Extension) R7M-EC8A, R7M-EC8B,
R7M-EC16A, R7M-EC16B
* Must be setup with R7X Con!gurator Software and the dedi-
cated cable.
• R7E Series Remote I/O
SIGNAL TYPE
DC voltage/current input
Thermocouple input
RTD input
MODELS
R7E-SV4
R7E-TS4
R7E-RS4
Potentiometer input
CT input
R7E-MS4
R7E-CT4E*
R7E-DA16
Discrete input
Discrete output
R7E-DC16A, R7E-DC16B
Discrete input (Extension) R7E-EA8, R7E-EA16
Discrete output (Extension) R7E-EC8A, R7E-EC8B,
R7E-EC16A, R7E-EC16B
* Must be setup with R7X Con!gurator Software and the dedi-
cated cable.
• Power Multimeter
TYPE
MODELS
Power multimeter
53U*
* Choose ‘Modbus’ option. Only 1 DO can be used for alarm
output.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 14/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ STORABLE TIME DURATION IN 1GB CF CARD
STORING
RATE
APPROXIMATE TIME DURATION
32 ch input
8 days, 8 hours
8 ch input
27 days, 16 hours
138 days
277 days
7 years, 222 days
10 years minimum
16 ch input
15 days, 8 hour
77 days
64 ch input
4 days, 8 hours
128 ch input
---
14 days
28 days, 8 hours
213 days
3 years, 172 days
0.1 seconds
0.5 seconds
1 second
10 seconds
1 minute
40 days
20 days, 16 hours
42 days
1 years, 55 days
6 years, 335 days
154 days
4 years, 83 days
10 years minimum
81 days, 16 hours
2 years, 86 days
10 years minimum
--- : Not Applicable
Note 1: Data are calculated ones, and thus not guaranteed.
Note 2: Assuming 4 bytes per data per channel.
Note 3: A year is calculated as 365 days.
SYSTEM CONFIGURATION EXAMPLES
■ R1M, R2M, RZMS
[Example 1]
Paperless Recorder
(model: 73VR1100)
RS-485
RS-485
PC Recorder
(model: R1M-GH
or R1MS-GH3)
PC Recorder
(model: R1M-A1)
PC Recorder
(model: R1M-D1)
PC Recorder
(model: R1M-P4)
PC Recorder
(model: RZMS-U9)
RS-232-C
Interlink / Reverse
Cable
PC Recorder
(model: R2M)
[Example 2]
Paperless Recorder
(model: 73VR1100)
Ethernet
100 Mbps
Hub / Switch
Ethernet
Communication Adaptor
(model: 72EM2-M4)
Communication Adaptor
(model: 72EM2-M4)
ETHERNET
ETHERNET
RS-485
RS-485
RUN
RUN
SEND
FIELD
SEND
FIELD
CNFG
CNFG
RS-485
RS-485
PC Recorder PC Recorder
(model: R1M-GH) (model: R1M-D1)
PC Recorder
(model: R1M-A1)
PC Recorder PC Recorder
(model: RZMS-U9) (model: RZMS-U9)
PC Recorder
(model: RZMS-U9)
Note 1: Use a dedicated network for the 73VR1100 and its input devices.
Note 2: The sampling rate depends upon the number of devices to be connected.
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 15/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ R3, R5 SERIES
Paperless Recorder
(model: 73VR1100)
Paperless Recorder
(model: 73VR1100)
RS-485
Ethernet
100 Mbps
Hub / Switch
Ethernet
I/O Modules
Network Module
(model: R3-NM1, R5-NM1)
I/O Modules
Network Module
(model: R3-NE1, R5-NE1)
Note 1: Use a dedicated network for the 73VR1100 and its input devices.
Note 2: The sampling rate depends upon the number of devices to be connected for the R3 series.
Note 3: Use of a switch/hub via straight type cables is recommended to connect the R3-NE1 or the R5-NE1 to the 73VR1100.
■ R7E
Paperless Recorder
(model: 73VR1100)
Ethernet
Hub / Switch
Ethernet
Modbus I/O Module
(model: R7E)
Modbus I/O Module
(model: R7E)
■ R7M
Paperless Recorder
(model: 73VR1100)
RS-485
Modbus I/O Module
(model: R7M)
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 16/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ 53U
Paperless Recorder
(model: 73VR1100)
RS-485
RS-485 (Modbus RTU)
Multi Power Monitor
(model: 53U)
■ IT60RE (R3 applied on input units)
Paperless Recorder
(model: 73VR1100)
Ethernet
Hub
Ethernet
Interface Module
(Model: R3-NE1)
Tower Light
(Model: IT60RE)
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 17/18
https://www.m-system.co.jp/
MODEL: 73VR1100
■ MSR128
• I/O devices connected to RS-485
• Transferring data from the CF Card
PC Recorder Software
(model: MSR128)
PC Recorder Software
(model: MSR128)
Card Reader
CF Card
Ethernet
100 Mbps
Hub / Switch
Paperless Recorder
(model: 73VR1100)
Ethernet
RS-485
Paperless Recorder
(model: 73VR1100)
PC Recorder
(model: R1M-GH)
PC Recorder
(model: R1M-D1)
PC Recorder
(model: R1M-A1)
RS-485
PC Recorder PC Recorder
(model: R1M-GH) (model: R1M-D1)
PC Recorder
(model: R1M-A1)
• I/O devices connected to Ethernet
PC Recorder Software
(model: MSR128)
Ethernet
100 Mbps
Hub / Switch
Ethernet
Paperless Recorder
(model: 73VR1100)
I/O Modules
(model: R3-NE1, R5-NE1)
Network Module
Note 1: Use a dedicated network for the 73VR1100 and its input devices.
Note 2: Use of a hub/switch via straight cables is recommended to connect the 73VR1100 to the PC.
Note 3: The storing intervals of 100 msec. and 200 msec. are not applicable to the above configuration.
Specifications are subject to change without notice.