CRP-221-AB [MSYSTEM]

Final Control Elements;
CRP-221-AB
型号: CRP-221-AB
厂家: M-SYSTEM    M-SYSTEM
描述:

Final Control Elements

文件: 总4页 (文件大小:113K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: CRP  
Final Control Elements  
[4] OPTIONS  
Adaptor  
blank: without  
SERVO-TOP VALVE ACTUATOR TYPE C  
(rotary type)  
/K: Adaptor for Kitamura Valve  
Functions & Features  
• Lightweight, compact design  
• Simple adjustments  
GENERAL SPECIFICATIONS  
Degree of protection: IP55  
• ISO standard flange  
Action: Direct or reverse; field selectable with DIP switches  
(factory set to “reverse”)  
Operation at abnormally low input: Open, close or stop; field  
selectable with DIP switches (factory set to “stop”)  
Detectable input drop level: 0.37 ±0.1 V DC; converted into  
voltage  
Wiring conduits: G 1/2 female thread (two)  
Terminal board: M3 screw (leadwire size 2 mm  
2
max.;  
torque 0.5 N·m)  
MODEL: CRP-[1]1-[2][3][4]  
Housing material: Aluminum alloy  
Drive: AC reversible motor (15-minute continuous rating)  
Insulation class: E (thermal protector incorporated; 120  
±5°C or 248 ±9°F)  
ORDERING INFORMATION  
• Code number: CRP-[1]1-[2][3][4]  
Specify a code from below for each [1] through [4].  
(e.g. CRP-241-AB/K)  
Power control element: Semiconductor switch  
Position detection: Potentiometer  
Span: 90 degrees (100 degrees max.)  
Deadband adjustment: 0.5 – 5.5 % (factory set to approx.  
1.5 %)  
[1] TORQUE, OPERATION TIME  
01: 68.6 N·m, 12 sec./90° (7 kgf·m)  
Re-start limiting timer: Approx. 1.5 seconds  
Mechanical limiter: Fixed to 90 degrees position  
Isolation: Input or output to power to ground  
Zero adjustment: 0 – 25 %  
(DISCONTINUED; replace with MODEL PRP.)  
03: 68.6 N·m, 24 sec./90° (7 kgf·m)  
(DISCONTINUED; replace with MODEL PRP.)  
11: 196 N·m, 12 sec./90° (20 kgf·m)  
(DISCONTINUED; replace with MODEL PRP.)  
13: 196 N·m, 24 sec./90° (20 kgf·m)  
(DISCONTINUED; replace with MODEL PRP.)  
22: 588 N·m, 18 sec./90° (60 kgf·m)  
24: 588 N·m, 36 sec./90° (60 kgf·m)  
Span adjustment: 50 - 100 %  
OUTPUT SPECIFICATIONS  
Operation Time & Torque(50 / 60 Hz, with no load)  
CRP-221: 18 / 15 sec. ±15 %; 588 N·m (434.0 ft·lbf)  
CRP-241: 36 / 30 sec. ±15 %; 588 N·m (434.0 ft·lbf)  
Position Signal: 4 – 20 mA DC  
SPAN  
1: 45° - 90°  
Load resistance: ≤ 300 Ω  
INSTALLATION  
Power input  
[2] POSITION SETPOINT INPUT  
Current  
AC: Operational voltage range: rating ±10 %, 50/60 Hz  
Power Consumption  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
Voltage  
Power code B  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
CRP-221: 253 VA (50 Hz), 259 VA (60 Hz)  
CRP-241: 215 VA (50 Hz), 198 VA (60 Hz)  
Power code C  
[3] POWER INPUT  
AC Power  
CRP-221: 303 VA (50 Hz), 273 VA (60 Hz)  
CRP-241: 273 VA (50 Hz), 182 VA (60 Hz)  
Power code G  
B: 100 V AC  
C: 110 V AC  
CRP-221: 280 VA (50 Hz), 188 VA (60 Hz)  
CRP-241: 320 VA (50 Hz), 238 VA (60 Hz)  
G: 200 V AC  
H: 220 V AC  
CRP SPECIFICATIONS  
ES-4827 Rev.10 Page 1/4  
http://www.m-system.co.jp/  
MODEL: CRP  
Power code H  
CRP-221: 394 VA (50 Hz), 249 VA (60 Hz)  
CRP-241: 425 VA (50 Hz), 291 VA (60 Hz)  
Operating temperature: -10 to +50°C (14 to 122 °F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Vibration: ≤ 2 G (19.6 m/s )  
2
Mounting position: All directions  
Weight: 15 kg (33.1 lb)  
PERFORMANCE  
Resolution:0.68° (CRP - 22) 0.45°(CRP - 24)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input or output  
or power to ground)  
FUNCTIONS  
Lock Detection  
When the valve stroke does not come into deadband range  
for longer than 2 minutes (approx.) due to motor locking or  
some other reasons, the CRP stops power supply to the  
motor.  
In order to reset the lock, apply 0 % and 100 % input  
repeatedly or turn the power supply off and on.  
Overload Protection  
In order to protect the motor from frequent control  
operations at high load (load rate ≥ 50 %), the CRP is  
equipped with a thermal protector in its motor.  
When the thermal protector is activated, the motor must be  
cooled down at least for 30 minutes before restarting.  
Electrical Storke Limits  
The valve operation can be limited within specific electrical  
limits without utilizing mechanical limit switches.  
Both limits are relative to the operation range adjusted with  
zero/span adj. The lower limit is fixed to 3.8 mA, while the  
higher limit is fixed to 20.2 mA.  
Manual Operation Handle  
The CRP is manual operated in 25 turns.  
CRP SPECIFICATIONS  
ES-4827 Rev.10 Page 2/4  
http://www.m-system.co.jp/  
MODEL: CRP  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–G 1/2 CONDUIT  
120 (4.72)  
Space required  
for removing cover.  
55  
(2.17)  
85 (3.35)  
133 (5.24)  
202 (7.95)  
164 (6.46)  
69  
68 (2.68)  
ø39 (1.54)  
MANUAL OPERATION  
(hexagonal 6 mm)  
(2.72)  
ø70f8  
• Without Adaptor for Kitamura Valve  
8–M10, 20 deep  
Use four(4) positions  
suitable for mounting.  
ø102 (4.02)  
ø125 (4.92)  
• With Adaptor for Kitamura Valve  
ø65 (2.56)  
4–M16, 24 deep  
100 (3.94)  
132 (5.20)  
ø80H10  
CRP SPECIFICATIONS  
ES-4827 Rev.10 Page 3/4  
http://www.m-system.co.jp/  
MODEL: CRP  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
min.  
Position  
Feedback  
Circuit  
max.  
Triac for  
Braking  
Mode  
Selector  
Compa-  
rator  
+
+
Triac  
Triac  
Limiter  
3
4
5
6
*
INPUT  
M
DEADBAND  
ADJ.  
1 2 3 4  
AC MOTOR  
POSITION  
OUTPUT  
FUSE  
U
V
1
2
POWER  
*Input shunt resistor incorporated for current input.  
Specifications are subject to change without notice.  
CRP SPECIFICATIONS  
ES-4827 Rev.10 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY