F2FL-B-R [MSYSTEM]

Super-mini Signal Conditioners F2 Series;
F2FL-B-R
型号: F2FL-B-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Super-mini Signal Conditioners F2 Series

文件: 总2页 (文件大小:96K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: F2FL  
Super-mini Signal Conditioners F2 Series  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SQUARE ROOT EXTRACTOR  
(non-isolated)  
Functions & Features  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Provides a DC output proportional to the root of input  
signal  
• Low-end cutout  
/C02: Polyurethane coating  
Typical Applications  
GENERAL SPECIFICATIONS  
Construction: Stand-alone; terminal access at the front  
• Converting differential pressure to flow  
Connection: Euro type connector terminal  
22.5 (.89)  
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
Housing material: Flame-resistant resin (black)  
Isolation: Input or output to power  
75  
(2.95)  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Low-end cutout: Approx. 4 – 8 % (output)  
107  
(4.21)  
mm (inch)  
8% or less  
MODEL: F2FL–[1]6–R[2]  
4% or more  
0
INPUT  
ORDERING INFORMATION  
• Code number: F2FL-[1]6-R[2]  
Specify a code from below for each of [1] and [2].  
(e.g. F2FL-66-R/Q)  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
• Specify the specification for option code /Q  
(e.g. /C01)  
INSTALLATION  
Current consumption  
[1] INPUT  
Current  
DC: Approx. 80 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN rail  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
B: 2 – 10 mA DC (Input resistance 500 Ω)  
C: 1 – 5 mA DC (Input resistance 1000 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
Voltage  
Weight: 150 g (0.33 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.2 % (input 1 – 100 %)  
6: 1 – 5 V DC (Input resistance 100 kΩ min.)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
OUTPUT  
Voltage  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input or output  
to power to ground)  
6: 1 – 5 V DC (Load resistance 10 kΩ min.)  
POWER INPUT  
DC Power  
R: 24 V DC  
STANDARDS & APPROVALS  
EU conformity:  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
EMC Directive  
F2FL SPECIFICATIONS  
ES-5445 Rev.6 Page 1/2  
http://www.m-system.co.jp/  
MODEL: F2FL  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EN 50581  
Approval:  
UL/C-UL general safety requirements  
(UL 3111-1, CAN/CSA-C22.2 No.1010-1)  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
DIN RAIL  
35mm wide  
1
2 3 4  
5
6 7 8  
22.5 (.89)  
107 (4.21)  
[1.5 (.06)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Sq. Root  
Extractor  
Low-end  
Cutout  
+
+
+
1
2
3
4
5
6
7
8
*
INPUT  
OUTPUT  
POWER  
*Input shunt resistor incorporated for current input.  
Specifications are subject to change without notice.  
F2FL SPECIFICATIONS  
ES-5445 Rev.6 Page 2/2  
http://www.m-system.co.jp/  

相关型号:

F2FL-B-R/Q

Super-mini Signal Conditioners F2 Series
MSYSTEM

F2FL-C-R

Super-mini Signal Conditioners F2 Series
MSYSTEM

F2FL-C-R/Q

Super-mini Signal Conditioners F2 Series
MSYSTEM

F2G02

SAW Bandpass Filter
ITF

F2G04

SAW Bandpass Filter F2G04
ITF

F2G05

SAW Bandpass Filter F2G05
ITF

F2G10

SAW Bandpass Filter F2G10
ITF

F2G12

SAW Bandpass Filter
ITF

F2G16

SAW Bandpass Filter
ITF

F2G17

SAW Bandpass Filter F2G17
ITF

F2G18

SAW Bandpass Filter F2G18
ITF

F2G1A

SAW Bandpass Filter F2G1A
ITF