MODEL: KS2TR2
Plug-in Signal Conditioners K-UNIT
[2] OPTIONS
blank: none
/Q: Options other than the above (specify the specification)
TEMPERATURE INPUT LIMIT ALARM
(digital adjustments; dual alarm trip)
Functions & Features
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
• Providing relay contact closures at preset DC input levels
• Dual (Hi/Lo) trip
/SET: Preset according to the Ordering Information Sheet
(No. ESU-3606)
• Front digital displays
• Programmable with front keys
GENERAL SPECIFICATIONS
Construction: Panel flush mounting, plug-in
Connection: M3.5 screw terminals
Typical Applications
• Various alarm applications
50 (1.97)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to SET1 to SET2 to power
Time constant for the input filter (P-dF): 5.0 to 900.0 sec. (0
– 63 %)
70 (2.76)
Alarm relay switching delay time (P-d1, P-d2): 1 to 10 sec.;
programmable independently for each setpoint
Programming: Front key
110 (4.33)
mm (inch.)
Setpoint adjustment (ST1, ST2): -5 to +105 %;
programmable independently for each setpoint
Deadband (hysteresis) (HYS1, HYS2): 0 – 102 %;
programmable independently for each setpoint
Burnout: Upscale or downscale or no burnout
Cold junction compensation (CJM): ON or OFF; for
thermocouple input only; CJC sensor incorporated
Power ON delay (P-d0): 0 to 20 sec.
MODEL: KS2TR2–1–[1][2]
ORDERING INFORMATION
• Code number: KS2TR2-1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. KS2TR2-1-R/Q)
• Specify the specification for option code /Q
(e.g. /SET)
Read rate: 0.5 sec.
Temperature unit (P-F): °C, °F
Alarm mode (P-A1, P-A2): Programmable independently for
each setpoint; See Table below.
TEMPERATURE INPUT
Thermocouple input
Param.
Code
Alarm Modes
Latching
Hold*
Trip
Operation
Set Value
Relay & LED
Behavior in
Tripped Conditions
K(CA), E(CRC), J(IC), T(CC), B(RH), R, S, P(Platinel Ⅱ),
C(WRe 5-26), N
(P-A1)
(P-A2)
RTD input
0
1
No alarm
High
----
----
----
Absolute value
Without
LED ON
Coil energized
JPt 100 (JIS ’89) , Pt 100 (JIS ’97, IEC)
2
3
4
5
6
7
8
Low
High
Low
High
Low
High
Low
Absolute value
Absolute value
Absolute value
Absolute value
Absolute value
Absolute value
Absolute value
Without
With
LED ON
Coil energized
OUTPUT
1: Relay; SPDT or transfer contact
LED ON
Coil energized
With
LED ON
Coil energized
Without
Without
With
LED ON
Coil de-energized
[1] POWER INPUT
AC Power
LED ON
Coil de-energized
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
LED ON
Coil de-energized
47 – 66 Hz)
DC Power
With
LED ON
Coil de-energized
R: 24 V DC
*Without latching hold function, the unit is tripped upon starting operation when
the unit is set to Low alarm.
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
With the function, the unit is NOT tripped until the temperature goes once above
and then below the setpoint.
KS2TR2 SPECIFICATIONS
ES-3606 Rev.6 Page 1/4
https://www.m-system.co.jp/
MODEL: KS2TR2
same time. DO NOT connect both contacts at the same
time.
DISPLAY
Display: 4 digits of 10 mm (.39”) height, 7-segment LED
Scaling range: -1999 to 9999 counts
Measured Value (PV)/Alarm (SET1) display: Red LEDs
Alarm (SET2) parameter display: Green LEDs
PV display at abnormal input: Over range or under range
displayed
Maximum switching voltage: 220 V AC or 30 V DC
Maximum switching power: 660 VA or 90 W
Minimum load: 10 V DC @1 mA
Mechanical life: 2 × 107 cycles with no loads
For maximum relay life with inductive loads, external
protection is recommended.
Front LEDs
Power indicator: Green LED turns on while the power is
turned on.
INSTALLATION
Power consumption
Measured Value (PV) indicator: Green LED turns on when PV
display is set.
•AC:
Alarm SET1 indicator: Red LED turns on when the Alarm
SET1 is in tripped conditions.
≤ 5 VA at 100 V
≤ 6 VA at 200 V
Alarm SET2 Indicator: Red LED turns on when the Alarm
SET2 is in tripped conditions.
≤ 6 VA at 264 V
•DC: ≤ 2.5 W
Engineering unit indication: Sticker label attached; ℃, °F,
etc.
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting with attached
mounting bracket, surface or DIN rail
Weight: 200 g (0.44 lb)
INPUT SPECIFICATIONS
• Thermocouple
Thermocouple type and temperature range
J (IC) : (0 to 400°C or 32 to 752°F)
J (IC) : (0 to 800°C or 32 to 1472°F)
K (CA) : (0 to 400°C or 32 to 752°F)
K (CA) : (0 to 800°C or 32 to 1472°F)
K (CA) : (0 to 1200°C or 32 to 2192°F)
R : (0 to 1600°C or 32 to 2912°F)
PERFORMANCE
Display accuracy
•Thermocouple: ±0.5 % FS ± 1 digit ± 3°C (5.4°F)
±1 % FS ± 1 digit ± 3°C (5.4°F) for T, E (≤ -100°C, ≤ -148
°F)
±5 % FS ± 1 digit ± 3°C (5.4°F) for B (0 – 500°C, 32 –
932°F)
B (RH) : (0 to 1800°C or 32 to 3272°F)
S : (0 to 1600°C or 32 to 2912°F)
±1 % FS ± 1 digit ± 3°C (5.4°F) for R (0 – 400°C, 32 –
752°F)
T (CC) : (-199 to 200°C or -328 to 392°F)
T (CC) : (-150 to 400°C or -238 to 752°F)
E (CRC) : (0 to 800°C or 32 to 1472°F)
E (CRC) : (-199 to 800°C or -328 to 1472°F)
N : (0 to 1300°C or 32 to 2372°F)
P (Platinel Ⅱ) : (0 to 1300°C or 32 to 2372°F)
C (WRe 5-26) : (0 to 2300°C or 32 to 4172°F)
Input resistance: ≥ 1 MΩ
(In case of type B thermocouple the accuracy near 0°C may
be degraded due to the characteristic of the sensor.)
•RTD: ±0.5 % FS ± 1 digit
Setpoint accuracy: Display accuracy ± 0.1 % FS
Trip point repeatability: Included in the setpoint accuracy
Cold junction compensation error: ±3°C at 25 ±5°C (±5.4°F
at 77 ±9°F)
Burnout sensing: Approx. 0.3 μA
Burnout response: Approx. 10 sec.
Line voltage effect: Included in the display accuracy
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(input to SET1 or SET2 to power)
■ RTD
RTD type and temperature range:
Pt 100 (JIS '97, IEC): (-150 to +850°C or -238 to +1562°F)
JPt 100 (JIS '89): (-150 to +600°C or -238 to +1112°F)
Sensing current: Approx. 0.3 mA
500 V AC @1 minute (SET1 to SET2)
Maximum leadwire resistance: 20 Ω per wire
STANDARDS & APPROVALS
EU conformity:
OUTPUT SPECIFICATIONS
■ Relay Contact: SPDT relays
EMC Directive
220 V AC @3 A (cos ø = 1)
EMI EN 61000-6-4
30 V DC @3 A (resistive load)
EMS EN 61000-6-2
Caution: N.O. and N.C. contacts could be conductive at the
Low Voltage Directive
KS2TR2 SPECIFICATIONS
ES-3606 Rev.6 Page 2/4
https://www.m-system.co.jp/
MODEL: KS2TR2
EN 61010-1
Installation Category II (power)
Measurement Category II (output)
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
H. Alarm SET1 Indicator LED
J. Alarm SET2 Indicator LED
A. Measured Value (PV) /
G. Power Indicator LED
Alarm SET1 Display
B. Measured Value (PV)
Indicator LED
C. Alarm SET2 / Parameter Display
D. SELECT Key
F. DOWN Key
E. UP Key
Component Name
Ref.
Function
A
B
Measured Value (PV) / Alarm SET1 Display Displaying either of Measured Value (PV) or Alarm Setpoint Value (SET1)
LED turns on when the Measured Value (PV) is displayed.
Measured Value (PV) Indicator LED
Alarm SET2 / Parameter Display
SELECT Key
Displaying either of Alarm Setpoint Value (SET2) or parameter type code.
Used for confirming current setpoints and switching between parameter blocks.
C
D
E
F
Pressing the key increases display values.
UP Key
They change continuously when it is kept pressed.
Pressing the key decreases display values.
DOWN Key
They change continuously when it is kept pressed.
LED turns on while the power is turned on.
Power Indicator LED
Alarm SET1 Indicator LED
Alarm SET2 Indicator LED
G
H
J
LED turns on when the Alarm SET1 is in tripped conditions.
LED turns on when the Alarm SET2 is in tripped conditions.
KS2TR2 SPECIFICATIONS
ES-3606 Rev.6 Page 3/4
https://www.m-system.co.jp/
MODEL: KS2TR2
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
CLAMP
110 (4.33)
(top & bottom)
7.5
(.3)
71.5 (2.81)
1.5 (.06) PACKING
7.8 (.31)
48 (1.89)
DIN RAIL
35mm wide
8
7
6
5
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
9
10 11
1
2
MOUNTING
BRACKET
1 1–M3.5
SCREW
PANEL
t
[3.5] (.14)
40 (1.57)
50 (1.97)
1 ≤ t ≤ 8
(.04 ≤ t ≤.31)
PANEL CUTOUT unit: mm
■PANEL CUTOUT
+0.5
45 0
63 MIN.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RTD
THERMOCOUPLE
B
B
A
4
5
6
11 N.C.
10 N.O. SET1
RY
T/C
+
A/D
Converter
+
comp.
leadwire
–
9
3
2
1
7
8
COM
–
Digital
Computation
N.C.
RY
CJC
Sensor
N.O. SET2
COM
Display/
Setting
U(+)
POWER
V(–)
Base Socket
Specifications are subject to change without notice.
KS2TR2 SPECIFICATIONS
ES-3606 Rev.6 Page 4/4
https://www.m-system.co.jp/
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明