MODEL: KTS  
7: R (Usable range -50 to +1760°C, -58 to +3200°F)  
Plug-in Signal Conditioners K-UNIT  
8: S (Usable range -50 to +1760°C, -58 to +3200°F)  
N: N (Usable range -270 to +1300°C, -454 to +2372°F)  
0: Specify  
THERMOCOUPLE TRANSMITTER  
Functions & Features  
• Accepting direct input from a thermocouple and providing  
a standard process signal  
[2] OUTPUT  
Current  
• 7-segment linearization  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Burnout protection  
• High-accuracy cold junction compensation  
• Isolation up to 2000 V AC  
• Fast response type available  
• High-density mounting  
Typical Applications  
• High-accuracy cold junction compensation benefits narrow  
span measurements  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
• 0.1 μA burnout sensing enables long distance  
transmission with minimum offset drifts  
• Electric furnace (isolation)  
• No burnout type can connect to a single T/C in parallel  
with a recorder  
50  
(1.97)  
[3] POWER INPUT  
AC Power  
80  
(3.15)  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
123  
(4.84)  
mm (inch)  
MODEL: KTS–[1][2]–[3][4]  
DC Power  
S: 12 V DC  
ORDERING INFORMATION  
• Code number: KTS-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. KTS-2A-B/BL/Q)  
R: 24 V DC  
[4] OPTIONS (multiple selections)  
Response Time (0 – 90 %)  
blank: Standard (≤ 0.5 sec.)  
/K: Fast Response (Approx. 25 msec.)  
Burnout  
• Temperature range (e.g. 0 – 800°C)  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
blank: Upscale burnout  
/BL: Downscale burnout  
[1] INPUT THERMOCOUPLE  
/BN: No burnout  
1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)  
2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)  
3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)  
4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)  
5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)  
6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)  
CJC Sensor  
blank: With Cold Junction Compensation Sensor  
/N: Without Cold Junction Compensation Sensor  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
KTS SPECIFICATIONS  
ES-3531 Rev.12 Page 1/3  
http://www.m-system.co.jp/  
MODEL: KTS  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Note: The described accuracy may be partially not satisfied  
when the temperature ranges below 0°C. Consult factory.  
/C02: Polyurethane coating  
/C03: Rubber coating  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Offset: Max. 1.5 times span  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
At burnout: Downscale ≤ -10 %, Upscale ≥ 110 %  
Linearization: Standard  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
DC: Operational voltage range: rating ±10 %  
ripple 10 %p-p max., approx. 2.6 W (110 mA at 24 V)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Cold junction compensation (CJC): CJC sensor attached to  
the input terminals as standard; No CJC optional (B  
thermocouple is without CJC as standard.)  
Weight: 350 g (0.77 lb)  
INPUT SPECIFICATIONS  
Minimum span: 3 mV  
Offset: Max. 1.5 times span  
Input resistance: 30 kΩ min.  
Burnout sensing: 0.1 μA  
PERFORMANCE in percentage of span  
Accuracy: ±0.3 % (at over 400°C or 750°F for R, S  
and PR; over 770°C or 1420°F for B)  
Cold junction compensation error  
Minimum span (in °C)  
(PR): min. span 370°C  
K (CA): min. span 75°C  
E (CRC): min. span 50°C  
J (IC): min. span 60°C  
T (CC): min. span 75°C  
B (RH): min. span 780°C  
R: min. span 360°C  
(at 20°C ±10°C or 68°F ±18°F; with CJC sensor)  
K, E, J, T, N: ±0.5°C or ±0.9°F  
S, R, PR: ±1°C or ±1.8°F  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
(at over 400°C or 750°F for R, S and PR;  
over 770°C or 1420°F for B)  
Burnout response: ≤ 10 sec.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
S: min. span 380°C  
N: min. span 110°C  
Minimum span (in °F)  
(PR): min. span 670°F  
K (CA): min. span 140°F  
E (CRC): min. span 90°F  
J (IC): min. span 110°F  
T (CC): min. span 140°F  
B (RH): min. span 1410°F  
R: min. span 650°F  
S: min. span 690°F  
N: min. span 200°F  
KTS SPECIFICATIONS  
ES-3531 Rev.12 Page 2/3  
http://www.m-system.co.jp/  
MODEL: KTS  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
6
5
4
3
2–  
4.5 (.18) dia.  
MTG HOLE  
15 (.59) deep  
7
8
1
2
8–  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
123 (4.84)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
*
CJC SENSOR  
(model: CJM)  
6
3
5
8
4
1
7
2
*Deleted with Option /N  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
comp. leadwire  
T / C  
Z
S
Isolation  
+
Low Drift  
Amplifier  
Output  
Driver  
+
+
3
Linearizer  
1
2
7
8
OUTPUT  
POWER  
metal leg  
U(+)  
V(–)  
4
5
6
*
CJC  
**  
SENSOR  
CJC Sensing  
Volt. Generator  
model: CJM  
Base Socket  
* Deleted with Option /N.  
**Deleted with Option /N or B thermocouple.  
Specifications are subject to change without notice.  
KTS SPECIFICATIONS  
ES-3531 Rev.12 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY