MODEL: M1EAXV-2
2 Channel Super-mini Signal Conditioners
with Display M1E-2 Series
NO. OF CHANNELS
2: 2 channels
INPUT – Field-selectable
◆ DC Input
DC ALARM
(2 channels, PC programmable, dual or quad alarm trip)
• Current input: 0 - 50 mA DC
• Voltage input: -1000 - +1000 mV DC
• Voltage input: -10 - +10 V DC
Functions & Features
• Provides relay outputs at preset DC input levels
• Quad or dual trip
• 2 Channels
• Front LCD display indicating values in scaled engineering
unit range is used to program the module
• Adjustable deadband (hysteresis)
• ON delay time selectable
[1] OUTPUT
2: 4 points; N.O. or make contact
3: 4 points; N.C. or break contact
5: 2 points; SPDT or transfer contact
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
POWER INPUT
• Settable with front buttons
DC Power
• Enclosed relays
R: 24 V DC
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Typical Applications
• Annunciator
[2] OPTIONS
blank: none
• Various alarm applications
/Q: With options (specify the specification)
36 (1.42)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
99
(3.90)
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-5995)
125 (4.92)
RELATED PRODUCTS
mm (inch)
• Installation base (model: M1E-BS2)
Note: The !gure shows the combination
of the unit and the base.
• M1EA configurator software (model: M1EACFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual (EM-5994) for the M1EA configurator for
applicable cable types.
MODEL: M1EAXV–2-[1]-R[2]
ORDERING INFORMATION
• Code number: M1EAXV-2-[1]-R[2]
Specify a code from below for each of [1] and [2].
(e.g. M1EAXV-2-2-R/Q)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
• Specify the specification for option code /Q
(e.g. /C01/SET)
• Connected to base with connector
• Base
M2.6 screw terminals (torque: 0.5 N·m)
Applicable solderless terminal size (M3)
Screw terminal: Nickel-plated steel
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 1/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
Housing material: Flame-resistant resin (black)
Isolation:
•Wide Spans (V)
Input range: -10 – +10 V DC
Minimum span: 1 V
• Output code 2, 3: Ch1 input to Ch2 input to 1L1 or 1L2
alarm output to 1L3 or 1L4 alarm output to 2L1 or 2L2 alarm
output to 2L3 or 2L4 alarm output to power
• Output code 5: Ch1 input to Ch2 input to 1L1 alarm output
to 1L2 alarm output to 2L1 alarm output to 2L2 alarm
output to power
Input resistance: 1 MΩ minimum
The measurement available for -5 - +105% of input setting
range.
OUTPUT SPECIFICATIONS
Relay rating: 100 V AC @ 0.5 A (cos ø = 1)
120 V AC @ 0.5 A (cos ø = 1)
Configuration: Program with front buttons or Via PC.
Programmable features include: Refer to the parameter list.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
■Recommended solderless terminal size - M3 (unit: mm)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 1 mA
3max
4min
3.2 dia.
Mechanical life: 5 × 10 cycles
7
Alarm Trip Operation
• Example Quad N.O. contacts (LL, L, H, HH)
12max
(mm)
L1
L2
L3
L4
ON OFF
ON OFF
OFF ON
OFF ON
DISPLAY
Display functions: Displays and sets measured range,
engineering unit
Input
%
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)
Number of pixels: 68 × 95 (horizontal × vertical)
Character color: Yellow (reversing display of the current
value and the alarm setting value when alarm is tripped)
Display life: Approx. 50000 hours
0
50
100
LL
L
H
HH
Trip operation in power failure
Output code 2: All relays turn OFF.
Output code 3: All relays turn ON.
Output code 5: Terminals 13 – 15, 16 – 18, 6 – 12,
1 – 7 turn ON.
(Expected time for the Display brightness to be reduced to
50 % when the Display is used continuously with brightness
setting 2 in 25 ℃)
Display type: OEL display
INSTALLATION
Power consumption
Display digit: Negative 5 digits, positive 6 digits (-99999 to
999999)
•DC: ≤ 6 W
Decimal point position: Selectable
Operating temperature: -5 to +55°C (23 to 131°F)
Storage temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 10 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
INPUT SPECIFICATIONS
Input ranges are shown below.
For setting change of the input range and setting value,
refer to the operating manual (EM-5995-B).
■ DC Current
Weight: 150 g (0.33 lb) except base
PERFORMANCE in percentage of FS input
Accuracy (display accuracy, setting accuracy):
± (0.1% of FS + 1 digit)
Input resistance: Incorporated (28 Ω)
Input range: 0 - 50 mA DC
Minimum span: 2 mA
See CALCULATION EXAMPLES OF OVERALL ACCURACY.
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time (Filter time constant: 0 sec.): ≤ 0.5 sec.
(0 – 100 % at 90 % setpoint)
The measurement available for -5 - +105% of input setting
range.
■ DC Voltage
•Narrow Spans (mV)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
Input range: -1000 – +1000 mV DC
Minimum span: 100 mV
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 2/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
• Output code 2, 3: 1500 V AC @ 1 minute (Ch1 input to
Ch2 input to 1L1 or 1L2 alarm output to 1L3 or 1L4 alarm
output to 2L1 or 2L2 alarm output to 2L3 or 2L4 alarm
output to power to ground)
• Output code 5: 1500 V AC @ 1 minute (Ch1 input to Ch2
input to 1L1 alarm output to 1L2 alarm output to 2L1 alarm
output to 2L2 alarm output to power to ground
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Range -10 – +10 V, Input Setting -5 – +5 V
• Accuracy = Input Range Span (20 V) ÷ Input Span Setting
(10 V) × 0.1 % = ±0.2 % + 1 digit
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Pollution Degree 2
• Output code 2, 3
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
1L1 or 1L2 alarm output to 1L3 or 1L4 alarm output to 2L1
or 2L2 alarm output to 2L3 or 2L4 alarm output: Basic
insulation (300 V)
• Output code 5
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
1L1 alarm output to 1L2 alarm output to 2L1 alarm output
to 2L2 alarm output: Basic insulation (300 V)
RoHS Directive
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 3/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
EXTERNAL VIEW
Display
Up Button
Down Button
Set Button
Mode Button
Configurator Jack
■ COMPONENT FUNCTION
COMPONENT
Display
FUNCTION
Indicates present values, setting values and abnormal information.
Two types of present values are displayed respectively at the upper and lower parts according to setting.
Mode button
Set button
Shifts from Measuring mode to each setting mode.
The destination changes depending on how long the button is held down.
Pressing Mode button for ≥ 2 seconds returns to Measuring mode from each setting mode..
Shifts the setting value of each setting parameter item to a setting changeable state.
When at setting changeable state, used to move through the digits of setting value and to enter (save) the set-
ting value.
Cancels Ch1’s and Ch2’s alarm latches in Measuring mode (hold down for ≥ 2 seconds).
Up button
Shifts through setting parameter items and to increase or select the setting value.
Cancels Ch1’s latched alarm in Measuring mode (hold down for ≥ 2 seconds).
Down button
Congurator Jack
Shifts through setting parameter items and to decrease or select the setting value.
Cancels Ch2’s latched alarm in Measuring mode (hold down for ≥ 2 seconds).
Used to perform conguration with M1EA congurator software (model: M1EACFG).
When using the software, set the Lockout setting of the unit to ‘Lock’.
Refer to the operating manual (EM-5995-B) for detailed procedures.
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 4/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
TERMINAL ASSIGNMENTS
1
6
2
7
3
8
4
9
5
10
11
16
12
17
13
18
14
19
15
20
• OUTPUT CODE: 2, 3
• OUTPUT CODE: 5
No. FUNCTION
No. FUNCTION
No. FUNCTION
No. FUNCTION
1
2
COM4 (2L3, 2L4)
2L3 Alarm output
11
12
13
14
15
16
17
18
19
20
2L1 Alarm output
1
2
COM4 (2L2)
11
12
13
14
15
16
17
18
19
20
N.O. (2L1)
N.C. (2L1)
COM1 (1L1)
N.O. (1L1)
N.C. (1L1)
COM2 (1L2)
N.O. (1L2)
N.C. (1L2)
Power +
2L2 Alarm output
COM1 (1L1, 1L2)
1L1 Alarm output
1L2 Alarm output
COM2 (1L3, 1L4)
1L3 Alarm output
1L4 Alarm output
Power +
N.O. (2L2)
3
Ch1 Input voltage +
Ch1 Input current +
Ch1 Input –
3
Ch1 Input voltage +
Ch1 Input current +
Ch1 Input –
4
4
5
5
6
COM3 (2L1, 2L2)
2L4 Alarm output
Ch2 Input voltage +
Ch2 Input current +
Ch2 Input –
6
COM3 (2L1)
7
7
N.C. (2L2)
8
8
Ch2 Input voltage +
Ch2 Input current +
Ch2 Input –
9
9
10
Power –
10
Power –
* Base does not come with the unit. Please order separately.
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 5/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
PARAMETER LIST
The following parameters can be set or checked, by the front button operation, or from the PC by using M1EA conguration
software (model: M1EACFG).
MODE
ITEM SETTING PARAMETER
RANGE
UNIT
—
INITIAL VALUE
Lock
Ch1 setting
01
11
Lockout setting
Ch1 Input range
Lock / Unlock
0 – 50 mA
-1000 – +1000 mV
-10 – +10 V
—
0 – 50 mA
12
13
Ch1 0 % input setting
0.00 – 48.00
-1000.0 – 900.0
-10.000 – 9.000
mA
mV
V
4.00
Ch1 100 % input setting
2.00 – 50.00
-900.0 – 1000.0
-9.000 – 10.000
mA
mV
V
20.00
14
15
16
Ch1 0 % input scaling
Ch1 100 % input scaling
Ch1 Input decimal point
-99999 – 999999
-99999 – 999999
—
—
—
0.00
100.00
No decimal point
The number of decimal places : 1 – 5
2 places of decimals
17
30
31
32
33
34
40
41
Ch1 Unit (INP Scaling)
Ch1 L1 alarm enable
Ch1 L1 alarm setpoint
Ch1 L1 trip action
Choose from 68 types
Disable / Enable
*
—
—
—
—
—
—
—
—
%
Enable
20.00
Low
-99999 – 999999
High / Low
*
Ch1 L1 deadband
0 – 999999
*
0.01
Ch1 L1 coil at alarm
Ch1 L2 alarm enable
Ch1 L2 alarm setpoint
Energized / De-energized
Disable / Enable
Energized
Enable
-99999 – 999999
*
80.00 (2 points alarm)
30.00 (4 points alarm)
42
Ch1 L2 trip action
High / Low
—
High (2 points alarm)
Low (4 points alarm)
43
44
50
51
52
53
54
60
61
62
63
64
70
71
72
79
80
81
89
Ch1 L2 deadband
Ch1 L2 coil at alarm
Ch1 L3 alarm enable
Ch1 L3 alarm setpoint
Ch1 L3 trip action
0 – 999999
*
—
—
0.01
Energized / De-energized
Disable / Enable
Energized
Enable
70.00
High
—
-99999 – 999999
High / Low
*
—
—
Ch1 L3 deadband
Ch1 L3 coil at alarm
Ch1 L4 alarm enable
Ch1 L4 alarm setpoint
Ch1 L4 trip action
0 – 999999
*
—
0.01
Energized / De-energized
Disable / Enable
—
Energized
Enable
80.00
High
—
-99999 – 999999
High / Low
*
—
—
Ch1 L4 deadband
Ch1 L4 coil at alarm
0 – 999999
*
—
0.01
Energized / De-energized
—
Energized
0
Ch1 Alarm ON-delay time 0 – 999
Ch1 Power ON-delay time 0 – 999
sec.
sec.
—
5
Ch1 Latching alarm
Disable / Enable
0 – 30
Disable
0
Ch1 Filter time constant
sec.
%
Ch1 Input Zero ne adjust -5.000 – 5.000
Ch1 Input Span ne adjust 95.000 – 105.000
0.000
100.000
Cancel
%
Ch1 Alarm test
—
—
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 6/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
MODE
ITEM SETTING PARAMETER
111 Ch2 Input range
RANGE
UNIT
—
INITIAL VALUE
0 – 50 mA
Ch2 setting
0 – 50 mA
-1000 – +1000 mV
-10 – +10 V
112 Ch2 0 % input setting
113 Ch2 100 % input setting
0.00 – 48.00
-1000.0 – 900.0
-10.000 – 9.000
mA
mV
V
4.00
2.00 – 50.00
-900.0 – 1000.0
-9.000 – 10.000
mA
mV
V
20.00
114 Ch2 0 % input scaling
115 Ch2 100 % input scaling
116 Ch2 Input decimal point
-99999 – 999999
-99999 – 999999
—
—
—
0.00
100.00
No decimal point
The number of decimal places : 1 – 5
2 places of decimals
117 Ch2 Unit (INP Scaling)
130 Ch2 L1 alarm enable
131 Ch2 L1 alarm setpoint
132 Ch2 L1 trip action
Choose from 68 types
Disable / Enable
*
—
—
—
—
—
—
—
—
%
Enable
20.00
Low
-99999 – 999999
High / Low
*
133 Ch2 L1 deadband
0 – 999999
*
0.01
134 Ch2 L1 coil at alarm
140 Ch2 L2 alarm enable
141 Ch2 L2 alarm setpoint
Energized / De-energized
Disable / Enable
Energized
Enable
-99999 – 999999
*
80.00 (2 points alarm)
30.00 (4 points alarm)
142 Ch2 L2 trip action
High / Low
—
High (2 points alarm)
Low (4 points alarm)
143 Ch2 L2 deadband
144 Ch2 L2 coil at alarm
150 Ch2 L3 alarm enable
151 Ch2 L3 alarm setpoint
152 Ch2 L3 trip action
153 Ch1 L3 deadband
154 Ch2 L3 coil at alarm
160 Ch2 L4 alarm enable
161 Ch2 L4 alarm setpoint
162 Ch2 L4 trip action
163 Ch2 L4 deadband
164 Ch2 L4 coil at alarm
0 – 999999
*
—
—
0.01
Energized / De-energized
Disable / Enable
Energized
Enable
70.00
High
—
-99999 – 999999
High / Low
*
—
—
0 – 999999
*
—
0.01
Energized / De-energized
Disable / Enable
—
Energized
Enable
80.00
High
—
-99999 – 999999
High / Low
*
—
—
0 – 999999
*
—
0.01
Energized / De-energized
—
Energized
0
170 Ch2 Alarm ON-delay time 0 – 999
171 Ch2 Power ON-delay time 0 – 999
sec.
sec.
—
5
172 Ch2 Latching alarm
Disable / Enable
0 – 30
Disable
0
179 Ch2 Filter time constant
sec.
%
180 Ch2 Input Zero !ne adjust -5.000 – 5.000
181 Ch2 Input Span !ne adjust 95.000 – 105.000
0.000
100.000
Cancel
Lock
%
189 Ch2 Alarm test
01 Lockout setting
—
—
Lock / Unlock
—
Advanced
201 Display setting
Upper: choose from 14 types*
Lower: choose from 15 types*
—
Upper: Ch1 ALARM
(Scaling)
Lower: Ch2 ALARM
(Scaling)
202 Channel enable
Choose from 3 types
—
Ch1 enable
Ch2 enable
203 Brightness
1 (darkest) — 4 (brightest)
0 (always on), 1 — 60
OFF / RESET
—
min
—
4
204 Display timeout
205 Reset all settings
206 Version indication
10
OFF
—
—
—
01
Lockout setting
Lock / Unlock
—
Lock
* For details, refer to the operating manual (EM-5995-B).
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 7/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
125 (4.92)
[4 (.16)]
45 (1.77)
36 (1.42)
1
6
2
7
3
8
4
9
5
10
DIN RAIL
35mm wide
11 12 13 14 15
16
18 19 20
17
* Base does not come with the unit.
Please order separately.
MOUNTING REQUIREMENTS unit: mm [inch]
2–M4 SCREW
* Mounting requirements for base.
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 8/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ OUTPUT CODE 2: N.O. RELAY
Channel 1
+
RY
RY
Isolation
1L2 OUTPUT
1L1 OUTPUT
COM1
15
14
13
18
17
16
3
+
INPUT
Low Drift
Amplifier
4
VOLTAGE
INPUT
CURRENT
5
–
28Ω
–
RY
RY
1L4 OUTPUT
1L3 OUTPUT
COM2
Digital
Computation
Circuit
Isolation
RY
RY
Channel 2
+
2L2 OUTPUT
2L1 OUTPUT
COM3
12
11
6
8
9
+
–
INPUT
VOLTAGE
Low Drift
Amplifier
INPUT
CURRENT
10
RY
RY
–
28Ω
7
2L4 OUTPUT
2L3 OUTPUT
COM4
2
1
CONFIGURATOR
JACK
Display
Circuit
+
19
20
POWER
–
Front
Button
Base
■ OUTPUT CODE 3: N.C. RELAY
Channel 1
1L2 OUTPUT
15
14
13
18
17
16
1L1 OUTPUT
COM1
1L4 OUTPUT
1L3 OUTPUT
COM2
Channel 2
2L2 OUTPUT
2L1 OUTPUT
COM3
12
11
6
7
2L4 OUTPUT
2L3 OUTPUT
COM4
2
1
M1EAXV-2 SPECIFICATIONS
ES-5995 Rev.2 Page 9/10
https://www.m-system.co.jp/
MODEL: M1EAXV-2
■ OUTPUT CODE 5: SPDT RELAY
Channel 1
+
Isolation
N.C.
15
14
13
18
17
16
3
+
RY
RY
INPUT
VOLTAGE
Low Drift
Amplifier
N.O.
1L1 OUTPUT
1L2 OUTPUT
4
INPUT
CURRENT
COM1
N.C.
5
–
–
28Ω
N.O.
Digital
Computation
Circuit
COM2
Isolation
Channel 2
+
N.C.
12
11
6
RY
RY
8
9
N.O.
2L1 OUTPUT
+
–
Low Drift
Amplifier
INPUT
VOLTAGE
INPUT
CURRENT
COM3
N.C.
10
–
28Ω
7
2L2 OUTPUT
2
N.O.
CONFIGURATOR
JACK
COM4
1
Display
Circuit
+
–
19
20
POWER
Front
Button
Base
• Relay Protection
· AC Powered
· DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Diode, Varistor or
CR Circuit
Varistor or Spark
Quenching Circuit
LOAD
LOAD
U
Specifications are subject to change without notice.