M2EAXDY-3M2/Q [MSYSTEM]

Super-mini Signal Conditioners with Display Mini-M M2E Series;
M2EAXDY-3M2/Q
型号: M2EAXDY-3M2/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Super-mini Signal Conditioners with Display Mini-M M2E Series

文件: 总7页 (文件大小:180K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M2EAXDY  
5: 2 points; SPDT or transfer contact  
Super-mini Signal Conditioners with  
Display Mini-M M2E Series  
[2] POWER INPUT  
AC Power  
TWO-WIRE TRANSMITTER ALARM  
(PC programmable, dual or quad alarm trip)  
Functions & Features  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
DC Power  
• Quad or dual trip  
R: 24 V DC  
• Settable with front button  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
P: 110 V DC  
• ON delay time selectable  
• Hi/Lo trip and energized/de-energized coil independently  
selectable for each setpoint  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
• Enclosed relays  
• Relays can be powered by 200 V AC and 100 V DC  
• Segment linearization and square root extraction  
configurable  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
Typical Applications  
• Annunciator  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Various alarm applications  
/C02: Polyurethane coating  
/C03: Rubber coating  
29.5  
(1.16)  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
EX-FACTORY SETTING  
83  
(3.27)  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-5169)  
Default setting will be used if not otherwise specified.  
Up  
Mo  
de  
Do  
wn  
124  
Se  
t
(4.88)  
RELATED PRODUCTS  
• M2EA configurator software (model: M2EACFG)  
mm (inch)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual (EM-5151) for the M2EA configurator for  
applicable cable types.  
MODEL: M2EAXDY–[1]-[2][3]  
ORDERING INFORMATION  
• Code number: M2EAXDY-[1]-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. M2EAXDY-2-M2/Q)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
• Specify the specification for option code /Q  
(e.g. /C01/S01/SET)  
Connection: M3 screw terminals (torque 0.8 N·m)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Housing material: Flame-resistant resin (gray)  
Isolation: input to L1 or L4 alarm output to L2 or L3 alarm  
output to power  
INPUT – Field-selectable  
Current  
4 – 20 mA DC (Input resistance 250 Ω)  
(Selectable within 0 – 20 mA DC)  
(for output code 5, L3 alarm output and L4 alarm output is  
not available)  
Configuration: Program with front buttons or Via PC.  
Programmable features include: Refer to the parameter list.  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
[1] OUTPUT  
2: 4 points; N.O. or make contact  
3: 4 points; N.C. or break contact  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 1/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
Maximum switching power: 480 VA or 150 W  
Minimum load: 5 V DC @ 10 mA  
Mechanical life: 5 × 10 cycles  
DISPLAY  
Display functions: Displays and sets measured range,  
7
engineering unit  
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)  
Number of pixels: 68 × 95 (horizontal × vertical)  
Character color: Yellow (reversing display of the current  
value and the alarm setting value when alarm is tripped)  
Display life: Approx. 60000 hours  
Alarm Trip Operation Terminal No. in parentheses  
• Example Quad N.O. contacts (LL, L, H, HH)  
ON OFF  
ON OFF  
L1 (3–6)  
L2 (5–7)  
L3 (5–8)  
L4 (3–9)  
(Expected time for the Display brightness to be reduced to  
50 % when the Display is used continuously with brightness  
setting 2 in 25 ℃)  
OFF ON  
OFF ON  
Display type: OEL display  
Input  
%
Display digit: Negative 5 digits, positive 6 digits (-99999 to  
999999)  
0
50  
100  
LL  
L
H
HH  
Decimal point position: Selectable  
Trip operation in power failure  
Output code 2 : All relays turn OFF.  
Output code 3 : All relays turn ON.  
SUPPLY OUTPUT  
Output code 5 : Terminals 3 – 9, 5 – 8 turn ON.  
SUPPLY OUTPUT (across the terminals 1 – 2)  
Output voltage: 24 – 28 V DC with no load  
19 V DC minimum at 20 mA  
LINEARIZATION  
Linearization Types  
Current rating: ≤ 22 mA DC  
Permissible load resistance:  
Linear: Proportional to the input  
Square root: The input is square root extracted.  
User's table: Segment linearization  
LR (Ω) ≤ (19 – Min. Operational Voltage)V ÷ 0.02 A  
Shortcircuit Protection  
Current limited: 35 mA max.  
Calibration points: Max. 128 points; the input % and  
linearized value in scaling are specified in pairs.  
Selectable range: -7.5 to +107.5 % as input %; -99999 to  
+999999 as linearized values  
Protected time duration: No limit  
INPUT SPECIFICATIONS  
DC Current  
Low-end Cutout:Low-end cutout (Low Cut) point  
selectable within the range of 0 to 100 %.  
Input resistance: Incorporated (250 Ω)  
Input range: 0 - 20 mA DC  
With linear or segment linearization,  
the output signal is forcibly set to 0 % for the input lower  
than the low-cut point. With the square root extraction, the  
output signal is linear to the input when the latter is lower  
than the low-cut point.  
Minimum span: 1 mA DC  
The measurement available for -7.5 - +107.5% of input  
setting range.  
• Linear or User Table  
Square Root  
OUTPUT SPECIFICATIONS  
Quad Alarm  
Relay rating: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Low-end cutout  
point  
Low-end cutout  
point  
Maximum switching voltage: 250 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
0
0
input percent  
input percent  
0.2%  
0.2%  
Mechanical life: 5 × 10  
7
cycles  
DUAL ALARM  
Relay rating: 100 V AC @ 4 A (cos ø = 1)  
120 V AC @ 4 A (cos ø = 1)  
INSTALLATION  
Power Consumption  
AC:  
240 V AC @ 2 A (cos ø = 1)  
30 V DC @ 4 A (resistive load)  
≤ 7 VA at 100 V  
Maximum switching voltage: 250 V AC or 125 V DC  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 2/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
≤ 10 VA at 200 V  
≤ 12 VA at 264 V  
DC: ≤ 4 W  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 10 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Accuracy (display accuracy, setting accuracy): differs  
depending on the linearization type.  
Linear: ±(0.08 % of FS + 1 digit)  
Square root extraction (1 % or more of input): ±(0.15 % of  
FS + 1 digit)  
Segment linearization:  
±(0.08 % of FS + 1 digit) [gain ≤ 1]  
±(0.08 % x gain of FS + 1 digit) [gain > 1]  
See CALCULATION EXAMPLES OF OVERALL ACCURACY.  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time (Filter time constant: 0 sec.): ≤ 0.5 sec.  
(0 – 100 % at 90 % setpoint)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute (input to L1 or L4  
alarm output to L2 or L3 alarm output to power to ground)  
(for output code 5, L3 alarm output and L4 alarm output is  
not available)  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
[Example] Input Range: 0 – 20 mA, Input Setting: 4 – 20 mA  
(when the linearization type is linear)  
• Accuracy = Input Range Span (20 mA) ÷ Input Span  
Setting (16 mA) × 0.08 % = ±0.1 % + 1 digit  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (output)  
Installation Category II (power)  
Pollution Degree 2  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
L1 or L4 alarm output to L2 or L3 alarm output:  
Basic insulation (300 V)  
RoHS Directive  
EN 50581  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 3/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
EXTERNAL VIEW  
Display  
PERCENT  
50.00  
%
L4  
L3  
L2  
L1  
80.00  
70.00  
30.00  
20.00  
Up Button  
Mode Button  
Set Button  
Down Button  
Up  
Mode  
Configurator Jack  
Down  
Set  
COMPONENT  
Display  
FUNCTION  
Indicates present values, setting values and abnormal information. Two types of present values at upper  
and lower are displayed by setting.  
Mode button  
Set button  
Used to shift from measuring mode to each setting mode. Destination to shift is changed by the time press-  
ing and holding the button. Used to return from each setting mode to measuring mode. (press and hold for  
2 sec. or more)  
Used to change setting value of setting parameter. When at setting changeable state, used to enter (save)  
the setting value. Used to move on through digits of setting value for input scaling at setting changeable  
state.  
Used to release latching alarm in measuring mode (hold down more than 2 seconds).  
Up button  
Used to shift through setting parameter, and to increase or select setting value.  
Used to shift through setting parameter, and to decrease or select setting value.  
Down button  
Con!gurator Jack  
Used to con!gure with M2EA con!gurator software (model: M2EACFG). At the same time, set the lockout  
setting of the unit to ‘lock.  
Refer to the operating manual (EM-5169-B) for detailed procedures.  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 4/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
PARAMETER LIST  
MODE  
ITEM SETTING PARAMETER  
RANGE  
UNIT  
INITIAL VALUE  
Basic setting  
01  
12  
13  
14  
15  
16  
Lockout setting  
Lock / Unlock  
mA  
mA  
Lock  
0 % input setting  
100 % input setting  
0 % input scaling  
100 % input scaling  
Input decimal point  
0.00 – 19.00  
4.00  
1.00 – 20.00  
20.00  
-99999 – 999999  
-99999 – 999999  
No decimal point  
The number of decimal places : 1 – 5  
0.00  
100.00  
2 places of decimals  
17  
24  
Unit (INP Scaling)  
Low cut  
Choose from 68 types  
Enable / Disable  
0.00 – 100.00  
*
%
Disable  
0.00  
25  
Low cut point  
%
30  
31  
32  
33  
34  
40  
41  
L1 alarm enable  
L1 alarm setpoint  
L1 trip action  
Enable  
Enable / Disable  
-99999 – 999999  
High / Low  
20.00  
Low  
L1 deadband  
0 – 999999  
0.01  
L1 coil at alarm  
L2 alarm enable  
L2 alarm setpoint  
Energized / De-energized  
Enable / Disable  
Energized  
Enable  
-99999 – 999999  
80.00 (2 points alarm)  
30.00 (4 points alarm)  
42  
L2 trip action  
High / Low  
High (2 points alarm)  
Low (4 points alarm)  
43  
44  
50  
51  
52  
53  
54  
60  
61  
62  
63  
64  
70  
71  
72  
89  
79  
80  
81  
01  
91  
L2 deadband  
0 – 999999  
0.01  
L2 coil at alarm  
L3 alarm enable  
L3 alarm setpoint  
L3 trip action  
Energized / De-energized  
Enable / Disable  
-99999 – 999999  
High / Low  
Energized  
Enable  
70.00  
High  
L3 deadband  
0 – 999999  
0.01  
L3 coil at alarm  
L4 alarm enable  
L4 alarm setpoint  
L4 trip action  
Energized / De-energized  
Enable / Disable  
-99999 – 999999  
High / Low  
Energized  
Enable  
80.00  
High  
L4 deadband  
0 – 999999  
0.01  
L4 coil at alarm  
Alarm ON-delay time  
Power ON-delay time  
Latching alarm  
Alarm test  
Energized / De-energized  
0 – 999  
Energized  
sec.  
sec.  
0
0 – 999  
5
Enable / Disable  
Disable  
Cancel  
Option  
Filter time constant  
Input Zero !ne adjust  
Input Span !ne adjust  
Lockout setting  
Display setting  
0 – 30  
sec.  
%
0
-5.000 – 5.000  
95.000 – 105.000  
Lock / Unlock  
0.000  
%
100.000  
Lock  
Advanced  
Upper: choose from 3 types  
Lower: choose from 5 types  
1 (darkest) – 4 (brightest)  
0 (always on), 1 – 60  
OFF / RESET  
*
Upper: INPUT (Scaling)  
Lower: ALARM  
*
92  
93  
94  
95  
01  
Brightness  
min.  
4
Display timeout  
Reset all settings  
Version indication  
Lockout setting  
10  
OFF  
Lock / Unlock  
Lock  
Linearization  
100 Linearization  
Linear, Square root, User’s table  
2 – 128  
Linear  
2
166 Number of points  
Table  
167 –  
422  
-7.50 – 107.50 (X)  
-99999 – 999999 (Y)  
% (X)  
— (Y)  
X001 -7.50  
Y001 -7.50  
X002 107.50  
Y002 107.50  
01  
Lockout setting  
Lock / Unlock  
Lock  
* For detailed types, refer to the operating manual (EM-5169-B).  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 5/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
6 (.23)  
3
2
5
1
4
2–4.2x5  
(.17x.20)  
6
MTG HOLE  
6 (.24) deep  
DIN RAIL  
35mm wide  
9
8
7
11–M3  
SCREW  
11 10  
22 (.87)  
29 (1.14)  
94 (3.70)  
124 (4.88)  
29.5 (1.16)  
8
[4 (.16)]  
(.31)  
• When mounting, no extra space is needed between units.  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 6/7  
http://www.m-system.co.jp/  
MODEL: M2EAXDY  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
OUTPUT CODE 2: N.O. Relay  
OUTPUT CODE 3:  
N.C. Relay  
2-WIRE  
TRANSMITTER  
RY  
24V DC  
Supply  
Shortcircui  
Portection  
9
6
L4 OUTPUT  
L1 OUTPUT  
COM  
9
6
3
8
7
5
L4 OUTPUT  
L1 OUTPUT  
COM  
+
+
1
2
RY  
Digital  
Computation  
Circuit  
200Ω  
3
+
4
MONITOR  
V
(1 – 5V DC)  
RY  
RY  
50Ω  
8
L3 OUTPUT  
L2 OUTPUT  
COM  
L3 OUTPUT  
L2 OUTPUT  
COM  
7
CONFIGURATOR  
JACK  
5
Display  
Circuit  
10  
11  
U(+)  
POWER  
CONTROL  
SW  
V(–)  
Base Socket  
OUTPUT CODE 5: SPDT Relay  
2-WIRE  
TRANSMITTER  
24V DC  
Supply  
Shortcircui  
Portection  
9
6
N.C.  
N.O.  
COM  
N.C.  
N.O.  
COM  
U(+)  
+
+
1
2
RY  
RY  
L1 OUTPUT  
Digital  
Computation  
Circuit  
200Ω  
3
+
4
MONITOR  
V
(1 – 5V DC)  
50Ω  
8
7
CONFIGURATOR  
JACK  
L2 OUTPUT  
POWER  
5
Display  
Circuit  
10  
CONTROL  
SW  
11 V(–)  
Base Socket  
Relay Protection  
• AC Powered  
• DC Powered  
Inductive  
Load (Coil)  
Inductive  
Load (Coil)  
Varistor or Spark  
Quenching Circuit  
Diode, Varistor or  
CR Circuit  
LOAD  
LOAD  
U
When 24V DC is Not Used  
No Connection  
1
2
4
+
200Ω  
50Ω  
INPUT  
Specifications are subject to change without notice.  
M2EAXDY SPECIFICATIONS  
ES-5169 Rev.1 Page 7/7  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY