M3LT-R4/B/UL [MSYSTEM]

Space-saving Signal Conditioners M3-UNIT Series;
M3LT-R4/B/UL
型号: M3LT-R4/B/UL
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Signal Conditioners M3-UNIT Series

文件: 总4页 (文件大小:139K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M3LT  
Space-saving Signal Conditioners M3-UNIT Series  
POWER INPUT  
DC Power  
R4: 10 – 32 V DC  
THERMOCOUPLE TRANSMITTER  
(field- and PC-configurable)  
(Operational voltage range 9 - 36 V, ripple 10 %p-p max.)  
Functions & Features  
• Accepts a thermocouple input and provides an isolated,  
linearized DC signal  
[1] CONFIGURATION OPTIONS  
A: PC and field configurable  
• Easy ‘One-Step Cal’ calibration using the front three  
control buttons without needing a PC; PC software is also  
usable.  
B: Field configurable  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
• Both input and output type and range are configurable  
• Front control button function can be locked  
• Cold junction compensation  
blank: CE marking  
/UL: UL approval, CE marking  
Other Options  
• Linearization and burnout  
blank: none  
18 (.71)  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
106  
(4.17)  
/C02: Polyurethane coating  
/C03: Rubber coating (UL not available)  
110.5 (4.35)  
mm (inch)  
RELATED PRODUCTS  
• PC configurator software (model: M3CFG)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
MODEL: M3LT–R4/[1][2]  
ORDERING INFORMATION  
• Code number: M3LT-R4/[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. M3LT-R4/A/UL/Q)  
• Specify the specification for option code /Q  
(e.g. /C01)  
GENERAL SPECIFICATIONS  
Construction: Small-sized front terminal structure  
• Orders will be shipped at default factory settings (K, 0 –  
1000°C input/4 – 20 mA output)  
Connection: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm)  
2
Housing material: Flame-resistant resin (gray)  
Isolation: Input to output to power  
Overrange output: -15 to +115 %  
Zero adjustment: -15 to +15 % (front)  
Span adjustment: 85 to 115 % (front)  
Burnout: Upscale (default), downscale or no burnout  
selectable  
INPUT – Field-selectable  
Thermocouple  
(PR), K (CA), E (CRC), J (IC), T (CC), B (RH), R, S, C (WRe 5-26),  
N, U, L, P (Platinel II)  
OUTPUT – Field-selectable  
Current  
Linearization: Standard  
Cold junction compensation: CJC sensor attached to the  
input terminals  
0 – 20 mA DC  
Voltage  
Status indicator LED: Tri-color (green/amber/red) LED;  
Blinking patterns indicate operation status of the  
transmitter.  
-2.5 – +2.5 V DC  
-10 – +10 V DC  
Configuration:  
PC Configurator: (Model: M3LTCFG) via Windows PC  
M3LT SPECIFICATIONS  
ES-2661 Rev.13 Page 1/4  
http://www.m-system.co.jp/  
MODEL: M3LT  
connected to th front jack.  
INSTALLATION  
Power consumption  
DC: Approx. 3 W  
Programmable features include:  
• I/O type and range  
• Zero and span adjustments  
Operating temperature: -25 to +65°C (-13 to +149°F)  
Max. 55°C (131°F) for UL approval  
Operating humidity: 0 to 95 %RH (non-condensing)  
Mounting: DIN rail  
• Burnout action  
• User’s T/C table setting  
(max. 300 points, input emf specified within  
-100 – +1000 mV)  
Weight: 100 g (0.22 lb)  
• Others  
(Refer to the instruction manual)  
‘One-Step Cal’ calibration: With I/O type and the full-scale  
range configured via the internal DIP switches, precise 0 %  
and 100 % ranges are calibrated via the front control  
buttons with a help of LED. Also I/O calibration and fine  
adjustment are available with a PC.  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
PERFORMANCE  
Accuracy: See Table 1 and refer to calculation examples of  
overall accuracy.  
Cold junction compensation error:  
±0.5°C at 25 ±10°C  
±0.9°F at 77 ±18°F  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span  
at -5 to +55°C [23 to 131°F]  
Response time: ≤ 0.9 sec. (0 – 90 %)  
Burnout response: ≤ 10 sec.  
INPUT SPECIFICATIONS  
Thermocouple: See table 1  
Input resistance: ≥ 1 MΩ  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to output or power to ground)  
500 V AC @ 1 minute (output to power)  
Burnout sensing: 130 nA ± 10 %  
Temperature range: See Table 1.  
OUTPUT SPECIFICATIONS  
■ DC Current  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
[Example 1]  
Maximum range: 0 – 20 mA DC  
Minimum span: 1 mA  
Input: K thermocouple, 0 – 1000°C, Output: 4 – 20 mA DC  
1) Absolute value accuracy (Table 1): 0.25°C  
2) CJC error (0.5°C) added: 0.75°C  
Conformance range: 0 – 24 mA DC  
(Negative overrange current below 0 mA is not available.)  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
3) 0.75°C ÷ 1000°C × 100 = 0.075 %  
4) 0.075 % < 0.1 % of span. ➠ 0.1 % is selected.  
5) Output span 16 mA (= 20 mA – 4 mA)  
Max. span 20 mA  
Load resistance: Output drive 12 V maximum  
DC Voltage  
Output span ≥ 1/10 of max. span ➠ No need of adding  
0.2 %.  
Narrow Spans  
Maximum range: -2.5 – +2.5 V DC  
Minimum span: 250 mV  
6) Overall accuracy equals ±0.1 % of span  
[Example 2]  
Conformance range: -3 – +3 V DC  
Wide Spans  
Input: K thermocouple, 50 – 150°C, Output: 2.0 – 2.5 V DC  
1) Absolute value accuracy (Table 1): 0.25°C  
2) CJC error (0.5°C) added: 0.75°C  
Maximum range: -10 – +10 V DC  
Minimum span: 1 V  
3) 0.75°C ÷ (150 – 50)°C × 100 = 0.75 %  
4) 0.75 %> 0.1 % of span. ➠ 0.75 % is selected.  
5) Output span 0.5 V (= 2.5 V – 2.0 V)  
Max. span 5 V  
Conformance range: -11.5 – +11.5 V DC  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
Output span ≤ 1/10 of max. span ➠ Add 0.2 %.  
6) Overall accuracy equals ±0.95 % of span (0.75 + 0.2)  
Load resistance: Output drive 1 mA maximum  
M3LT SPECIFICATIONS  
ES-2661 Rev.13 Page 2/4  
http://www.m-system.co.jp/  
MODEL: M3LT  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
Approval:  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.1010-1)  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
LED1 (LD1)  
10 11 12  
LED2 (LD2)  
Configuration DIP SW  
7
8
9
LED3 (LD3)  
MODE Button  
UP Button  
4 3 2 1  
OFF  
ON  
DOWN Button  
SW1  
Configurator Jack  
SW2  
SW3  
8 7 6 5 4 3 2 1  
OFF  
ON  
4
5
6
4 3 2 1  
OFF  
ON  
The DIP switch setting is required to select output types before setting a precise output range using the PC configurator  
software.  
For detailed information on the configuration and calibration, refer to the instruction manual.  
INPUT TYPE, RANGE & ACCURACY  
INPUT TYPE, RANGE & ACCURACY  
Table 8  
Thermocouple  
°C  
°F  
MIN.  
SPAN  
MAXIMUM  
RANGE  
CONFORMANCE  
RANGE  
MIN.  
SPAN  
MAXIMUM  
RANGE  
CONFORMANCE  
RANGE  
ACCURACY*1  
ACCURACY*1  
(PR)  
20  
20  
20  
0 to 1760  
0 to 1760  
1ꢀ00  
0ꢀ25  
0ꢀ20  
36  
36  
36  
32 to 3200  
32 to 3200  
1ꢀ80  
0ꢀ45  
0ꢀ36  
K (CA)  
E (CRC)  
-270 to +1370  
-270 to +1000  
-150 to +1370  
-170 to +1000  
-454 to +2498  
-454 to +1832  
-238 to +2498  
-274 to +1832  
J (IC)  
20  
20  
20  
-210 to +1200  
-270 to +400  
100 to 1820  
-180 to +1200  
-170 to +400  
400 to 1760  
0ꢀ25  
0ꢀ25  
0ꢀ75  
36  
36  
36  
-346 to +2192  
-454 to +752  
212 to 3308  
-292 to +2192  
-274 to +752  
752 to 3200  
0ꢀ45  
0ꢀ45  
1ꢀ35  
T (CC)  
B (RH)  
R
20  
20  
20  
-50 to +1760  
-50 to +1760  
0 to 2315  
200 to 1760  
0 to 1760  
0 to 2315  
0ꢀ50  
0ꢀ50  
0ꢀ80  
36  
36  
36  
-58 to +3200  
-58 to +3200  
32 to 4199  
392 to 3200  
32 to 3200  
32 to 4199  
0ꢀ90  
0ꢀ90  
1ꢀ44  
S
C (WRe 5-26)  
N
20  
20  
20  
20  
-270 to +1300  
-200 to +600  
-200 to +900  
0 to 1395  
-130 to +1300  
-200 to +600  
-200 to +900  
0 to 1395  
0ꢀ30  
0ꢀ20  
0ꢀ25  
0ꢀ25  
36  
36  
36  
36  
-454 to +2372  
-328 to +1112  
-328 to +1652  
32 to 2543  
-202 to +2372  
-328 to +1112  
-328 to +1652  
32 to 2543  
0ꢀ54  
0ꢀ36  
0ꢀ45  
0ꢀ45  
U
L
P(Platinel II)  
*1ꢀ [Accuracy + Cold Junction Compensation Error 0ꢀ5°C (0ꢀ9°F)] or 0ꢀ1ꢁ oꢂ spanꢃ whichever is greaterꢀ  
Iꢂ the selected output span equals to or narrower than the one-tenth oꢂ the maximum spanꢃ add 0ꢀ2ꢁꢀ  
M3LT SPECIFICATIONS  
ES-2661 Rev.13 Page 3/4  
http://www.m-system.co.jp/  
MODEL: M3LT  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 11 12  
7
8
9
DIN RAIL  
35mm wide  
4
5
6
110.5 (4.35)  
[5 (.20)]  
CJC SENSOR  
(model: CJM)  
18 (.71)  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
STATUS  
CONTROL BUTTONS  
ext. leadwire  
T / C  
DIP SW  
10  
7
Isolation  
+
Output  
Computation  
Output  
Driver  
+
+
+
4
Low Drift  
Amplifier  
& Burnout  
OUTPUT  
POWER  
8
*
5
6
11  
12  
9
CJC  
SENSOR  
CONFIGURATOR  
JACK  
* The CJC Sensor is secured to the terminal 6.  
Loosen only the terminal 4 – 5 and connect the T/C extension wires.  
Specifications are subject to change without notice.  
M3LT SPECIFICATIONS  
ES-2661 Rev.13 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

M3LU-M2/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/A/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/B/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/A/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-R4/B/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM