M6NXAS-S2-R/Q [MSYSTEM]
Screw Terminal Ultra-Slim Signal Conditioners M6N Series;型号: | M6NXAS-S2-R/Q |
厂家: | M-SYSTEM |
描述: | Screw Terminal Ultra-Slim Signal Conditioners M6N Series |
文件: | 总4页 (文件大小:161K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M6NXAS
Screw Terminal Ultra-Slim Signal Conditioners M6N Series
POWER INPUT
DC Power
R: 24 V DC
DC ALARM
(PC programmable)
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Functions & Features
• 7.5-mm wide ultra-slim design
• Low profile allows the M6N module mounted in a 120-mm
deep panel
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
• Provides a relay contact output at preset DC input levels
• PC programmable
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• High-density mounting
• Power and status indicator LEDs
7.5 (.30)
/C02: Polyurethane coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7828)
102
(4.02)
RELATED PRODUCTS
• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
102
(4.02)
mm (inch)
MODEL: M6NXAS–[1]–R[2]
GENERAL SPECIFICATIONS
Connection
ORDERING INFORMATION
• Code number: M6NXAS-[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. M6NXAS-Z1-R/Q)
Input and output: M3 screw terminal (torque 0.5 N·m)
Power input: Via the Installation Base (model: M6NBS)
or M3 screw terminal (torque 0.5 N·m)
Recommended solderless terminal: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
• Input range (e.g. 4 – 20 mA DC)
• Specify the specification for option code /Q
(e.g. /C01/SET)
Applicable wire size: 0.2 – 2.5 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Blinking patterns indicate
different operating status of the transmitter.
Alarm monitor LED: Red LED turns on when the alarm is
tripped.
[1] INPUT
Current
Z1: Range 0 – 50 mA DC (Input resistance 24.9 Ω)
Voltage
S1: Range -1000 – +1000 mV DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
(Configurator software is used to change input over the
described range of the selected suffix code.
For changing between suffix codes, set the Input Range
Selector on the side of unit before software adjustment.)
Programming: Downloaded from PC
Input type and range
Input fine adjustments
Alarm setpoint (input %)
Trip action (High or Low)
Relay coil (energized or de-energized)
Power ON delay time (0 to 999 sec.)
Alarm ON delay time (0 to 999 sec.)
Hysteresis (deadband) (input %)
Alarm test, and others
OUTPUT
Relay; SPDT or transfer contact
M6NXAS SPECIFICATIONS
ES-7908 Rev.7 Page 1/4
http://www.m-system.co.jp/
MODEL: M6NXAS
For detailed information, refer to the users manual for the
PC configurator.
Alarm Trip Operation Terminal No. in parentheses
• Setting Example
Hi alarm (coil energized at alarm) or
Lo alarm (coil de-energized at alarm)
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
(3–2)ON
Output
Factory default setting
(3–4)ON
Alarm setpoint: 80 %
Input
(%)
Trip action: High
0
50
100
Relay coil at alarm: Energized
Power ON delay time: 5 sec.
Setpoint
Trip operation in power failure: Terminals 3 – 4 turn ON.
Alarm ON delay time: 0 sec.
Hysteresis (deadband) : 1.0 %
■Recommended solderless terminal (unit: mm (inch))
INSTALLATION
Power consumption: Approx. 0.5 W
5.5 max.
(.22)
4 min.
(.16)
3.2 (.13) dia.
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6NBS) or DIN rail
Weight: 65 g (2.3 oz)
PERFORMANCE in percentage of span
Setpoint accuracy (trip point accuracy) : ±0.05 %
Setpoint accuracy is inversely proportional to the input
span.
INPUT SPECIFICATIONS
■ DC Current: Input resistor incoporated
(If not specified, the input range is 4 – 20 mA DC.)
Input range: 0 – 50 mA DC
[Example] Input type 0 – 50 mA, Input range 4 – 20 mA
Max. Input Range (50 mA) ÷ Span (16 mA) × 0.05 %
= ±0.16 %
Minimum span: 2 mA
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
■ DC Voltage
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: ≤ 0.2 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
•Code S1 (narrow spans)
Input range: -1000 – +1000 mV DC
Minimum span: 100 mV
•Code S2 (wide spans)
Input range: -10 – +10 V DC
Minimum span: 1 V
STANDARDS & APPROVALS
EU conformity:
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
S1: 0 – 100 mV DC
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
S2: 1 – 5 V DC
Low Voltage Directive
EN 61010-1
OUTPUT SPECIFICATIONS
■ Relay Output
Measurement Category II (output)
Pollution Degree 2
Relay rating:
Input or power to output: Reinforced insulation (300 V)
Input to power: Basic insulation (300 V)
RoHS Directive
250 V AC @2 A (cos ø = 1)
30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @100 mA
EN 50581
Mechanical life: 5 × 10 cycles (rate 180/min.)
6
M6NXAS SPECIFICATIONS
ES-7908 Rev.7 Page 2/4
http://www.m-system.co.jp/
MODEL: M6NXAS
EXTERNAL VIEW
FRONT VIEW (with the cover open)
SIDE VIEW
5
6
7
8
Power LED
Alarm Monitor LED
Input Selector
Status Indicator LED
Configurator Jack
v
I
1
2
3
4
The DIP switch setting is required to select input types
before setting a precise input range using PC Configurator
Software (model: M6CFG).
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCREWDRIVER
INSERTION ANGLE
: approx. 55°
*
WIRE INSERTION ANGLE
: approx. 35°
8–M3
SCREW TERMINAL
DIN RAIL HOOK
5
6
7
8
DIN RAIL
35mm wide
1
2
3
4
[1 (.04)]
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
7.5 (.30)
102 (4.02)
*Screwdriver stem diameter: 6 mm (.24”) or less
• When mounting, no extra space is needed between units.
M6NXAS SPECIFICATIONS
ES-7908 Rev.7 Page 3/4
http://www.m-system.co.jp/
MODEL: M6NXAS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS ALARM
IND. LED MONITOR LED
INPUT
SELECTOR
N.C.
4
2
3
Digital
Ry
+
–
Computation
5
N.O. OUTPUT
COM
Low Drift
Amplifier
24.9 Ω
INPUT
6
POWER LED
1
+
7
8
POWER
–
CONFIGURATOR
JACK
POWER
■ Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
LOAD
LOAD
U
Diode, Varistor or
CR Circuit
Varistor or CR Circuit
Specifications are subject to change without notice.