M6SXAT-8-R/Q [MSYSTEM]

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series;
M6SXAT-8-R/Q
型号: M6SXAT-8-R/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series

文件: 总5页 (文件大小:169K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M6SXAT  
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series  
OUTPUT  
Relay; SPDT or transfer contact  
THERMOCOUPLE ALARM  
(PC programmable)  
POWER INPUT  
Functions & Features  
DC Power  
• Maintenance-free tension clamp connection  
• 5.9-mm wide ultra-slim design  
• Low profile allows the M6S module mounted in a 120-mm  
deep panel  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
[2] OPTIONS  
blank: none  
• PC programmable  
• Linearization and upscale and downscale burnout  
protection  
/Q: With options (specify the specification)  
• High-density mounting  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Power and status indicator LEDs  
5.9 (.23)  
/C02: Polyurethane coating  
RELATED PRODUCTS  
94  
(3.70)  
• PC configurator software (model: M6CFG)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
102  
(4.02)  
mm (inch)  
GENERAL SPECIFICATIONS  
Connection  
MODEL: M6SXAT–[1]–R[2]  
Input and output: Tension clamp  
Power input: Via the Installation Base (model: M6SBS)  
or Tension clamp  
ORDERING INFORMATION  
• Code number: M6SXAT-[1]-R[2]  
Specify a code from below for each [1] and [2].  
(e.g. M6SXAT-2-R/Q)  
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm  
2
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
• Temperature range (e.g. 0 – 1000°C)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Burnout: Upscale standard; downscale or no burnout  
optional by programming  
In case of upscale standard, the alarm operates as if the  
input signal has exceeded over the range.  
Linearization: Standard  
[1] INPUT THERMOCOUPLE  
1: (PR)  
Cold Junction Compensation: CJC sensor incorporated  
Power LED: Green light turns on when the power is supplied.  
Status indicator LED: Orange LED; Blinking patterns indicate  
different operating status of the transmitter.  
Alarm monitor LED: Red LED turns on when the alarm is  
tripped.  
2: K (CA)  
3: E (CRC)  
4: J (IC)  
5: T (CC)  
6: B (RH)  
7: R  
Programming: Downloaded from PC  
Input type and range  
8: S  
N: N  
Input fine adjustments  
0: Specify (Please provide a emf table.)  
(Configurator software is used to change the input type and  
precise range.)  
User’s Thermocouple table  
Burnout (Upscale, downscale or no burnout)  
Alarm setpoint (input %)  
M6SXAT SPECIFICATIONS  
ES-7992 Rev.4 Page 1/5  
http://www.m-system.co.jp/  
MODEL: M6SXAT  
Trip action (High or Low)  
INSTALLATION  
Relay coil (energized or de-energized)  
Power ON delay time (0 to 999 sec.)  
Alarm ON delay time (0 to 999 sec.)  
Hysteresis (deadband) (input %)  
Alarm test, and others  
Power consumption: Approx. 0.5 W  
Operating temperature: -20 to +55°C (-4 to +131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Installation Base (model: M6SBS) or DIN rail  
Weight: 65 g (2.3 oz)  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
PERFORMANCE in percentage of span  
Setpoint accuracy (trip point accuracy):  
Accuracy in Table 1 + Cold junction compensation error  
Cold junction compensation error:  
Factory default setting  
Alarm setpoint: 80 %  
Trip action: High  
Relay coil at alarm: Energized  
Power ON delay time: 5 sec.  
Alarm ON delay time: 0 sec.  
Hysteresis (deadband) : 1.0 %  
Burnout: Upscale  
±3°C at 25 ±10°C  
±5.4°F at 77 ±18°F  
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span  
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)  
Burnout response time: ≤ 1 sec.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
INPUT SPECIFICATIONS  
Input resistance: 1 MΩ min.  
Burnout sensing: ≤ 0.1 μA  
Temperature range: See Table 1.  
If not specified, the input range is shown below.  
1 PR: 0 – 1600°C  
CALCULATION EXAMPLES OF SETPOINT ACCURACY  
[Example] K thermocouple, 0 – 1000°C  
Absolute value accuracy (Table 1): 0.25°C  
CJC error (3°C) added: 3.25°C  
2 K: 0 – 1000°C  
3 E: 0 – 500°C  
4 J: 0 – 500°C  
Setpoint accuracy = 3.25°C ÷ 1000°C × 100 = 0.33 %  
Table 1.  
5 T: 0 – 300°C  
6 B: 500 – 1600°C  
7 R: 500 – 1600°C  
C
8 S: 0 – 1600°C  
THERMOCOUPLE  
MIN.  
MAXIMUM  
RANGE  
CONFORMANCE  
RANGE  
ACCURACY  
SPAN  
N N: 0 – 1000°C  
(PR)  
K (CA)  
E (CRC)  
J (IC)  
T (CC)  
B (RH)  
R
20  
20  
20  
20  
20  
20  
20  
20  
20  
0 to 1760  
0 to 1760  
1.00  
0.25  
0.20  
0.25  
0.25  
0.75  
0.50  
0.50  
0.30  
-270 to +1370 -150 to +1370  
-270 to +1000 -170 to +1000  
-210 to +1200 -180 to +1200  
-270 to +400 -170 to +400  
100 to 1820 400 to 1760  
-50 to +1760 200 to 1760  
OUTPUT SPECIFICATIONS  
Relay Output  
Relay rating:  
250 V AC @2 A (cos ø = 1)  
30 V DC @2 A (resistive load)  
Maximum switching voltage: 250 V AC or 125 V DC  
Maximum switching power: 500 VA or 60 W  
Minimum load: 5 V DC @100 mA  
S
-50 to +1760  
0 to 1760  
N
-270 to +1300 -130 to +1300  
F
THERMOCOUPLE  
MIN.  
MAXIMUM  
RANGE  
CONFORMANCE  
RANGE  
ACCURACY  
SPAN  
Mechanical life: 5 × 10 cycles (rate 180/min.)  
6
(PR)  
K (CA)  
E (CRC)  
J (IC)  
T (CC)  
B (RH)  
R
36  
36  
36  
36  
36  
36  
36  
36  
36  
32 to 3200  
32 to 3200  
1.80  
0.45  
0.36  
0.45  
0.45  
1.35  
0.90  
0.90  
0.54  
Alarm Trip Operation Terminal No. in parentheses  
-454 to +2498 -238 to +2498  
-454 to +1832 -274 to +1832  
-346 to +2192 -292 to +2192  
-454 to +752 -274 to +752  
212 to 3308 752 to 3200  
-58 to +3200 392 to 3200  
• Setting Example  
Hi alarm (coil energized at alarm) or  
Lo alarm (coil de-energized at alarm)  
(3–2)ON  
Output  
(3–4)ON  
Input  
(%)  
S
-58 to +3200  
32 to 3200  
0
50  
100  
Setpoint  
N
-454 to +2372 -202 to +2372  
Trip operation in power failure: Terminals 3 – 4 turn ON.  
M6SXAT SPECIFICATIONS  
ES-7992 Rev.4 Page 2/5  
http://www.m-system.co.jp/  
MODEL: M6SXAT  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (output)  
Pollution Degree 2  
Input or power to output: Reinforced insulation (300 V)  
Input to power: Basic insulation (300 V)  
RoHS Directive  
EN 50581  
EXTERNAL VIEW  
(With the cover open)  
Power LED  
Alarm Monitor LED  
Status Indicator LED  
Configurator Jack  
M6SXAT SPECIFICATIONS  
ES-7992 Rev.4 Page 3/5  
http://www.m-system.co.jp/  
MODEL: M6SXAT  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
SCREWDRIVER  
*
INSERTION ANGLE  
: approx. 35°  
WIRE INSERTION ANGLE  
: approx.35°  
TEST PROBE  
max. 2 (.08) dia.  
5
6
7
8
DIN RAIL HOOK  
DIN RAIL  
35mm wide  
1
2
3
4
SCREWDRIVER  
INSERTION ANGLE  
: approx. 40°  
[0.5 (.02)]  
5.9 (.23)  
102 (4.02)  
• When mounting, no extra space is needed between units.  
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
STATUS ALARM  
CJC  
LED  
MONITOR LED  
SENSOR  
comp. leadwire  
+
4
2
3
NC  
T/C  
Digital  
Computation  
+
5
6
Ry  
Low Drift  
Amplifier  
OUTPUT  
NO  
-
COM  
POWER LED  
1
+
7
8
POWER  
POWER  
JACK  
CONFIGURATOR  
Relay Protection  
• AC Powered  
• DC Powered  
Inductive  
Load (Coil)  
Inductive  
Load (Coil)  
LOAD  
LOAD  
U
Diode, Varistor or  
CR Circuit  
Varistor or CR Circuit  
M6SXAT SPECIFICATIONS  
ES-7992 Rev.4 Page 4/5  
http://www.m-system.co.jp/  
MODEL: M6SXAT  
Specifications are subject to change without notice.  
M6SXAT SPECIFICATIONS  
ES-7992 Rev.4 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

M6SXAT-N-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAT-N-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V2-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V2-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V2-R/UL

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V3-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V3-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1V3-R/UL

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1Z1-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1Z1-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXF1-S1Z1-R/UL

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM