MAT2-4404MY [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MAT2-4404MY |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总5页 (文件大小:175K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MAT2
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[3] MAXIMUM DISCHARGE CURRENT
M: 20kA (8/20 μsec.)
H: 40kA (8/20 μsec.)
LIGHTNING SURGE PROTECTOR
[4] ALARM OUTPUT
A: With
FOR THREE-PHASE POWER SUPPLY
Functions & Features
Y: Without
• Connected in parallel between the power and earth lines
regardless of load current
• Applicable to single phase 2/3-wire and threephase 3/4-
wire system
GENERAL SPECIFICATIONS
Construction: Standalone; terminal access at the front
Degree of protection: IP20 (If the solderless terminals are
covered with insulation tubes.)
• High discharge current capacity 20 kA or 40 kA (8/20 μs)
• Degraded head element is automatically separated from
the power lines by the incorporated thermal breaker, and
the LED lamp (turns off) and the relay contact alerts the
failure status.
Surge protection type: Voltage limiting type one-port SPD
Connection
Line: M5 screw terminal (torque: 2.5 N·m)
Alarm output: Tension clamp
• Complies with IEC 61643-1 Class II
Applicable wire size
Typical Applications
Line: See the drawing below.
• Low-voltage distribution board
• Combination with installation for large load current
Alarm output: 0.13 to 1.5 mm
2, stripped length 8 mm
Screw terminal
Line: Nickel-plated steel
50 [1.97]
Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Alarm output: SPDT relay contact trips when the thermal
breaker operates.
OUTPUT TERMINAL A1 – C
98
[3.86]
Normal: Open
Failure or power off: Close
OUTPUT TERMINAL A2 – C
60 [2.36]
Normal: Close
mm [inch]
Failure or power off: Open
Rated load:
MODEL: MAT2–[1][2][3][4]
250 V AC @1 A (resistive load)
24 V DC @1 A (resistive load)
Safety function: Thermal breaker incorporated
Monitor LED: Green LED turns on during normal condition
and turns off during failure condition, power off or the
thermal breaker operating.
ORDERING INFORMATION
• Code number: MAT2-[1][2][3][4]
Specify a code from below for each of [1] through [4].
(e.g. MAT2-2403MY)
• Applicable Solderless Terminal Size
diameter d
d : M5 use
B ≤ 13.0 mm
[1] OPERATIONAL VOLTAGE
240: 240 V AC
F ≥ 7.0 mm
(F ≥ 8.2 mm for sharing terminals)
T ≤ 1.8 mm
440: 440 V AC
F
[2] POWER SYSTEM
3: Single-phase 2/3-wire, Three-phase 3-wire
(Select ‘240’ for ‘Operational voltage’ code.)
4: Single-phase 2/3-wire, Three-phase 3/4-wire
MAT2 SPECIFICATIONS
ES-8149 Rev.12 Page 1/5
https://www.m-system.co.jp/
MODEL: MAT2
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail
Weight: 300 g (0.66 lb)
PERFORMANCE
Response time: ≤ 3 nanoseconds (≤ 20 nanoseconds for N to PE)
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output)
Dielectric strength: 2000 V AC @1 minute (line to alarm output)
Surge protection: IEC 61643-1 Class II
EN 61643-11 Class II
VOLTAGE
PROTECTION
LEVEL
MAX. CONTINUOUS
OPERATING VOLTAGE
(Uc)
DISCHARGE
VOLTAGE
(Vmin)
OPERATIONAL VOLTAGE RANGE *1
(50 / 60Hz)
MODEL
(Up)
1-phase/2-wire, 3-phase/3-wire: 90 – 240V AC
1-phase/3-wire: 90 / 180 – 120 / 240V AC
3-phase/4-wire: 170 – 240V AC
Between lines: 240V AC Between lines: 400V
N to PE: 320V AC N to PE: 550V
MAT2-240
MAT2-440
1500V
2500V
1-phase/2-wire, 3-phase/3-wire: 240 – 440V AC
1-phase/3-wire: 200 / 400 – 220 / 440V AC
3-phase/4-wire: 350 – 440V AC
Between lines: 440V AC Between lines: 780V
N to PE: 550V
N to PE: 320V AC
MAX. LEAKAGE CURRENT @Uc
MODEL
ALARM OUTPUT
WITH
28mA *2
2mA
WITHOUT
6mA *3
2mA
1 to 2
Line to Line
MAT2-240
Other sections
N to PE
N to PE
10µA
10µA
1 to 2
22mA
2mA
6mA
Line to Line
MAT2-440
Other sections
2mA
10µA
10µA
*1. MAT2 is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED and the alarm
output are not guaranteed.
*2. Approx. 12mA @100V AC
*3. Approx. 3mA @100V AC
MODEL
MAT2-xM
MAT2-xH
MAX. DISCHARGE CURRENT (Imax)
20kA (8/20µsec)
NOMINAL DISCHARGE CURRENT (In)
10kA (8/20µsec)
40kA (8/20µsec)
20kA (8/20µsec)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61643-11
RoHS Directive
MAT2 SPECIFICATIONS
ES-8149 Rev.12 Page 2/5
https://www.m-system.co.jp/
MODEL: MAT2
CONNECTION EXAMPLES
■ INSTALLATION EXAMPLES: Three-phase 4-wire connection
1) : Protective device of the switchgear
2) : Circuit breaker
3) : Main earth terminal or busbar
4) : MAT2
5) : Earth conductor
1)
L1
L2
L3
PE
N
Residual
Current
Circuit
Breaker
5)a and/or 5)b
6) : Protected device
EB : Main's earth electrode
ED : Switchgear's earth electrode
N
*1
2)
4)
*1
1
2
3
*2
*2
5)a
5)b
N
PE
*3
*3
*4
*4
6)
3)
EB
ED
*1. The circuit breaker must be installed.
Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used.
The rated interrupting capacity of the circuit breaker must be greater than the highest amount of current that could be available in the circuit.
Install MCCB (rated current 20 – 30A) that has element for each phase.
Or RCD with time-delay overcurrent protection is recommended. Recommended sensitivity current rating: 30mA
*2. Cable length between the branch point and the earthing: 0.5 meters or less recommended
*3. The protected device's metal enclosure must be cross-wired to the earth terminal of the MAT2. If the protected device has no earth terminal,
earth only the MAT2.
*4. In order to protect an electronic circuit such as measuring equipment or communication equipment, we recommend to use surge protectors
which have serial impedance incorporated such as M-System's models MAX, MMA, MAH.
MAT2 SPECIFICATIONS
ES-8149 Rev.12 Page 3/5
https://www.m-system.co.jp/
MODEL: MAT2
■ CONNECTION EXAMPLES BY POWER SYSTEMS
Abnormal voltages appearing in case of a light load or a fault earth loop must be within the maximum continuous operational voltage when
selecting the MAT2 models.
Three phase/3-wire (delta connection)
Single-phase/2-wire
POWER SYSTEM
Generator or transformer
Generator or transformer
Protected
device
Protected
device
(N)
G
G
(N)
*3
*1
Circuit breaker
Circuit breaker
CONNECTION
*1
1
2
3
1
2
3
*1
SPD
C
SPD
C
*1
N
PE
A1 A2
N
PE
A1 A2
Alarm output
SPD
Alarm output
SPD
Power System (example)
Power System (example)
Three-phase/3-wire 220V AC
Three-phase/3-wire 400V AC
EXAMPLE
Single-phase/2-wire 110V AC
Single-phase/2-wire 220V AC
MAT2
MAT2
–
240x
240x
MAT2–240x
–
MAT2–4404x
Single-phase/2-wire
(three-phase delta connection
earthed in the middle of phases)
Three-phase/4-wire (star connection)
POWER SYSTEM
Single-phase/3-wire
Generator or transformer
Generator or transformer
*3
Protected
device
Protected
device
*4
N
G
G
*2
Circuit breaker
N
Circuit breaker
*2
CONNECTION
*1
1
2
3
1
2
3
*1
SPD
C
SPD
C
N
PE
A1 A2
N
PE
A1 A2
Alarm output
SPD
Alarm output
SPD
Power System (example)
Power System (example)
Single-phase/2-wire 110V AC
Single-phase/2-wire 220V AC
MAT2
–240x
Three-phase/4-wire 220V AC
Three-phase/4-wire 400V AC
MAT2
–
–
2404x
4404x
MAT2
–4404x
MAT2
EXAMPLE
Single-phase/3-wire 220/110V AC
Single-phase/3-wire 400/200V AC
MAT2
MAT2
–240x
–4404x
*1. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, connect between terminal 2 and N of the MAT2.
*2. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, install a four-pole (three-pole plus neutral)
circuit breaker.
*3. For 440V AC three-phase/3-wire system, use a residual current circuit breaker with overcurrent protection.
*4. For single-phase/2-wire system, connect lines to terminal 1 and 2 of the MAT2. For single-phase/3-wire system, connect the neutral line to terminal 2
of the MAT2.
■ ALARM OUTPUT
When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required.
MAT2 SPECIFICATIONS
ES-8149 Rev.12 Page 4/5
https://www.m-system.co.jp/
MODEL: MAT2
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
80 [3.15]
60 [2.36]
50 [1.97]
15 [.59] 15 [.59]
5–M5 SCREW
TERMINAL COVER
*
1
2
3
DIN RAIL
35mm wide
SPECIFICATION
MONITOR LED
N
PE
(3.4 [.13])
ALARM OUTPUT **
15 [.59]
TERMINAL
45°
(WIRE INSERTION ANGLE)
12.5 [.49]
A2
A1
C
*
Open/close type.
** Only for ‘Alarm output’ code ‘A’.
SCHEMATIC CIRCUITRY
1
2
3
Monitor LED
ѳ
ѳ
Alarm
Output
Circuit
ѳ
ѳ
N
PE
C
A1 A2
ѳ
: Thermal breaker
Note: Terminals C, A1 & A2 are available for ‘Alarm output’ code ‘A.’
The schematic shows the relay contact status of a thermal trip or
power off.
Specifications are subject to change without notice.
MAT2 SPECIFICATIONS
ES-8149 Rev.12 Page 5/5