MODEL: MAT3  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
[2] ALARM OUTPUT  
A: With  
Y: Without  
LIGHTNING SURGE PROTECTOR  
GENERAL SPECIFICATIONS  
Construction: Standalone; terminal access at the front  
Degree of protection: IP20 (If the solderless terminals are  
covered with insulation tubes.)  
FOR THREE-PHASE POWER SUPPLY  
Functions & Features  
• Connected in parallel between the power and earth lines  
regardless of load current  
Surge protection type: Voltage limiting type one-port SPD  
Connection  
• Applicable to single phase 2/3-wire and threephase 3/4-  
wire system  
Line: M5 screw terminal (torque: 2.5 N·m)  
Alarm output: Tension clamp  
• High discharge current capacity 20 kA or 40 kA (8/20 μs)  
• Degraded head element is automatically separated from  
the power lines by the incorporated thermal breaker, and  
the LED lamp (turns off) and the relay contact alerts the  
failure status.  
Applicable wire size  
Line: See the drawing below.  
Alarm output: 0.13 to 1.5 mm2, stripped length 8 mm  
Screw terminal  
• Complies with IEC 61643-11 Class II  
Line: Nickel-plated steel  
Alarm output: Tin-plated copper alloy  
Housing material: Flame-resistant resin (black)  
Alarm output: SPDT relay contact trips when the thermal  
breaker operates.  
Typical Applications  
• Low-voltage distribution board  
• Combination with installation for large load current  
OUTPUT TERMINAL A1 – C  
50 (1.97)  
Normal: Open  
Failure or power off: Close  
OUTPUT TERMINAL A2 – C  
Normal: Close  
98  
Failure or power off: Open  
(3.86)  
Rated load:  
250 V AC @1 A (resistive load)  
24 V DC @1 A (resistive load)  
Safety function: Thermal breaker incorporated  
Monitor LED: Green LED turns on during normal condition  
and turns off during failure condition, power off or the  
thermal breaker operating.  
60 (2.36)  
mm (inch)  
MODEL: MAT3–240[1]M[2]  
• Applicable Solderless Terminal Size  
diameter d  
d : M5 use  
ORDERING INFORMATION  
• Code number: MAT3-240[1]M[2]  
Specify a code from below for each of [1] and [2].  
(e.g. MAT3-2403MY)  
B ≤ 13.0 mm  
F ≥ 7.0 mm  
(F ≥ 8.2 mm for sharing terminals)  
T ≤ 1.8 mm  
F
OPERATIONAL VOLTAGE  
240: 240 V AC  
[1] POWER SYSTEM  
3: Single-phase 2/3-wire, Three-phase 3-wire  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 5 to 95 %RH (non-condensing)  
Mounting: DIN Rail  
4: Single-phase 2/3-wire, Three-phase 3/4-wire  
Weight: 300 g (0.66 lb)  
MAXIMUM DISCHARGE CURRENT  
M: 20kA (8/20 μsec.)  
MAT3 SPECIFICATIONS  
ES-8164 Rev.3 Page 1/5  
http://www.m-system.co.jp/  
MODEL: MAT3  
PERFORMANCE  
Response time: ≤ 3 nanoseconds (≤ 20 nanoseconds for N to PE)  
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output)  
Dielectric strength: 2000 V AC @1 minute (line to alarm output)  
Surge protection: IEC 61643-11 Class II  
EN 61643-11 Class II  
VOLTAGE  
PROTECTION  
LEVEL  
MAX. CONTINUOUS  
OPERATING VOLTAGE  
(Uc)  
DISCHARGE  
VOLTAGE  
(Vmin)  
OPERATIONAL VOLTAGE RANGE *1  
(50 / 60Hz)  
MODEL  
(Up)  
1-phase/2-wire, 3-phase/3-wire: 90 – 240V AC  
1-phase/3-wire: 90 / 180 – 120 / 240V AC  
3-phase/4-wire: 170 – 240V AC  
Between lines: 240 V AC Between lines: 400V  
N to PE: 320 V AC N to PE: 680V  
MAT3-240  
1500  
MAX. LEAKAGE CURRENT @Uc  
MODEL  
ALARM OUTPUT  
WITH  
28mA *2  
2mA  
WITHOUT  
6mA *3  
2mA  
1 to 2  
Line to Line  
MAT3-240  
Other sections  
N to PE  
10µA  
10µA  
*1. MAT3 is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED and the alarm  
output are not guaranteed.  
*2. Approx. 12mA @100V AC  
*3. Approx. 3mA @100V AC  
MODEL  
MAX. DISCHARGE CURRENT (Imax)  
20kA (8/20µsec)  
NOMINAL DISCHARGE CURRENT (In)  
10kA (8/20µsec)  
MAT3-240xMx  
STANDARDS & APPROVALS  
EU conformity:  
Low Voltage Directive  
EN 61643-11  
RoHS Directive  
EN 50581  
MAT3 SPECIFICATIONS  
ES-8164 Rev.3 Page 2/5  
http://www.m-system.co.jp/  
MODEL: MAT3  
CONNECTION EXAMPLES  
INSTALLATION EXAMPLES: Three-phase 4-wire connection  
1)  
1) : Protective device of the switchgear  
2) : Circuit breaker  
3) : Main earth terminal or busbar  
4) : MAT3  
5) : Earth conductor  
L1  
L2  
L3  
PE  
N
Residual  
Current  
Circuit  
Breaker  
5)a and/or 5)b  
6) : Protected device  
EB : Main's earth electrode  
ED : Switchgear's earth electrode  
N
2)  
*1  
1
2
3
*2  
4)  
5)a  
5)b  
N
PE  
*3  
*4  
6)  
3)  
EB  
ED  
*1. The circuit breaker or the fuse as disconnectors must be installed.  
Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used.  
The rated interrupting capacity of the circuit breaker must be greater than the highest amount of current that could be available in the circuit.  
Install MCCB (rated current 20 30A) that has element for each phase.  
Or RCD with protection from nuisance tripping against transit voltages type or time-delay overcurrent protection type is recommended.  
Recommended sensitivity current rating: 30mA  
*2. Cable length between the branch point and the earthing: 0.5 meters or less recommended  
*3. The protected device's metal enclosure must be cross-wired to the earth terminal of the MAT3. If the protected device has no earth terminal,  
earth only the MAT3.  
*4. In order to protect an electronic circuit such as measuring equipment or communication equipment, we recommend to use surge protectors  
which have serial impedance incorporated such as M-System's models MAX, MMA, MAH.  
MAT3 SPECIFICATIONS  
ES-8164 Rev.3 Page 3/5  
http://www.m-system.co.jp/  
MODEL: MAT3  
CONNECTION EXAMPLES BY POWER SYSTEMS  
Abnormal voltages appearing in case of a light load or a fault earth loop must be within the maximum continuous operational voltage when  
selecting the MAT3 models.  
Three phase/3-wire (delta connection)  
Single-phase/2-wire  
POWER SYSTEM  
Power  
Power  
(N)  
Protected  
device  
Protected  
device  
(N)  
G
G
Circuit breaker  
Circuit breaker  
1
2
3
1
2
3
CONNECTION  
Alarm output  
Alarm output  
A2  
A1  
C
A2  
A1  
C
SPD1  
*1  
SPD1  
*1  
N
PE  
N
PE  
SPD1  
Power System (example)  
Power System (example)  
Three-phase/3-wire 220V AC  
SPD1  
MAT3 240xMx  
EXAMPLE  
Single-phase/2-wire 110V AC  
Single-phase/2-wire 220V AC  
MAT3  
MAT3  
240xMx  
240xMx  
Single-phase/2-wire  
(three-phase delta connection  
earthed in the middle of phases)  
POWER SYSTEM  
Three-phase/4-wire (star connection)  
Single-phase/3-wire  
Power  
N
Power  
Protected  
device  
*3  
Protected  
device  
G
G
Circuit breaker  
N
Circuit breaker *2  
1
2
3
CONNECTION  
Alarm output  
1
2
3
A2  
A1  
C
SPD1  
*1  
Alarm output  
A2  
A1  
C
SPD1  
N
PE  
N
PE  
SPD1  
Power System (example)  
Power System (example)  
Three-phase/4-wire 220V AC  
SPD1  
MAT3 2404Mx  
EXAMPLE  
Single-phase/2-wire 110V AC  
MAT3  
MAT3  
240xMx  
240xMx  
Single-phase/3-wire 220/110V AC  
*1. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, connect between terminal 2 and N of the MAT3.  
*2. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, install a four-pole (three-pole plus neutral)  
circuit breaker.  
*3. For single-phase/2-wire system, connect lines to terminal 1 and 2 of the MAT3. For single-phase/3-wire system, connect the neutral line to terminal 2  
of the MAT3.  
ALARM OUTPUT  
When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required.  
MAT3 SPECIFICATIONS  
ES-8164 Rev.3 Page 4/5  
http://www.m-system.co.jp/  
MODEL: MAT3  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
80 (3.15)  
60 (2.36)  
50 (1.97)  
15 (.59) 15 (.59)  
5–M5 SCREW  
TERMINAL COVER  
*
1
2
3
DIN RAIL  
35mm wide  
SPECIFICATION  
MONITOR LED  
N
PE  
[3.4 (.13)]  
ALARM OUTPUT **  
15 (.59)  
TERMINAL  
45°  
(WIRE INSERTION ANGLE)  
12.5 (.49)  
A2  
A1  
C
*
Open/close type.  
** Only for ‘Alarm output’ code ‘A’.  
SCHEMATIC CIRCUITRY  
1
2
3
Monitor LED  
ѳ
ѳ
Alarm  
Output  
Circuit  
ѳ
ѳ
N
PE  
C
A1 A2  
ѳ: Thermal breaker  
Note: Terminals C, A1 & A2 are available for ‘Alarm output’ code ‘A.’  
The schematic shows the relay contact status of a thermal trip  
or power off.  
Specifications are subject to change without notice.  
MAT3 SPECIFICATIONS  
ES-8164 Rev.3 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY