MODEL: MAT3
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[2] ALARM OUTPUT
A: With
Y: Without
LIGHTNING SURGE PROTECTOR
GENERAL SPECIFICATIONS
Construction: Standalone; terminal access at the front
Degree of protection: IP20 (If the solderless terminals are
covered with insulation tubes.)
FOR THREE-PHASE POWER SUPPLY
Functions & Features
• Connected in parallel between the power and earth lines
regardless of load current
Surge protection type: Voltage limiting type one-port SPD
Connection
• Applicable to single phase 2/3-wire and threephase 3/4-
wire system
Line: M5 screw terminal (torque: 2.5 N·m)
Alarm output: Tension clamp
• High discharge current capacity 20 kA or 40 kA (8/20 μs)
• Degraded head element is automatically separated from
the power lines by the incorporated thermal breaker, and
the LED lamp (turns off) and the relay contact alerts the
failure status.
Applicable wire size
Line: See the drawing below.
Alarm output: 0.13 to 1.5 mm2, stripped length 8 mm
Screw terminal
• Complies with IEC 61643-11 Class II
Line: Nickel-plated steel
Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Alarm output: SPDT relay contact trips when the thermal
breaker operates.
Typical Applications
• Low-voltage distribution board
• Combination with installation for large load current
OUTPUT TERMINAL A1 – C
50 (1.97)
Normal: Open
Failure or power off: Close
OUTPUT TERMINAL A2 – C
Normal: Close
98
Failure or power off: Open
(3.86)
Rated load:
250 V AC @1 A (resistive load)
24 V DC @1 A (resistive load)
Safety function: Thermal breaker incorporated
Monitor LED: Green LED turns on during normal condition
and turns off during failure condition, power off or the
thermal breaker operating.
60 (2.36)
mm (inch)
MODEL: MAT3–240[1]M[2]
• Applicable Solderless Terminal Size
diameter d
d : M5 use
ORDERING INFORMATION
• Code number: MAT3-240[1]M[2]
Specify a code from below for each of [1] and [2].
(e.g. MAT3-2403MY)
B ≤ 13.0 mm
F ≥ 7.0 mm
(F ≥ 8.2 mm for sharing terminals)
T ≤ 1.8 mm
F
OPERATIONAL VOLTAGE
240: 240 V AC
[1] POWER SYSTEM
3: Single-phase 2/3-wire, Three-phase 3-wire
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 95 %RH (non-condensing)
Mounting: DIN Rail
4: Single-phase 2/3-wire, Three-phase 3/4-wire
Weight: 300 g (0.66 lb)
MAXIMUM DISCHARGE CURRENT
M: 20kA (8/20 μsec.)
MAT3 SPECIFICATIONS
ES-8164 Rev.3 Page 1/5
http://www.m-system.co.jp/
MODEL: MAT3
PERFORMANCE
Response time: ≤ 3 nanoseconds (≤ 20 nanoseconds for N to PE)
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output)
Dielectric strength: 2000 V AC @1 minute (line to alarm output)
Surge protection: IEC 61643-11 Class II
EN 61643-11 Class II
VOLTAGE
PROTECTION
LEVEL
MAX. CONTINUOUS
OPERATING VOLTAGE
(Uc)
DISCHARGE
VOLTAGE
(Vmin)
OPERATIONAL VOLTAGE RANGE *1
(50 / 60Hz)
MODEL
(Up)
1-phase/2-wire, 3-phase/3-wire: 90 – 240V AC
1-phase/3-wire: 90 / 180 – 120 / 240V AC
3-phase/4-wire: 170 – 240V AC
Between lines: 240 V AC Between lines: 400V
N to PE: 320 V AC N to PE: 680V
MAT3-240
1500
MAX. LEAKAGE CURRENT @Uc
MODEL
ALARM OUTPUT
WITH
28mA *2
2mA
WITHOUT
6mA *3
2mA
1 to 2
Line to Line
MAT3-240
Other sections
N to PE
10µA
10µA
*1. MAT3 is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED and the alarm
output are not guaranteed.
*2. Approx. 12mA @100V AC
*3. Approx. 3mA @100V AC
MODEL
MAX. DISCHARGE CURRENT (Imax)
20kA (8/20µsec)
NOMINAL DISCHARGE CURRENT (In)
10kA (8/20µsec)
MAT3-240xMx
STANDARDS & APPROVALS
EU conformity:
Low Voltage Directive
EN 61643-11
RoHS Directive
EN 50581
MAT3 SPECIFICATIONS
ES-8164 Rev.3 Page 2/5
http://www.m-system.co.jp/
MODEL: MAT3
CONNECTION EXAMPLES
■ INSTALLATION EXAMPLES: Three-phase 4-wire connection
1)
1) : Protective device of the switchgear
2) : Circuit breaker
3) : Main earth terminal or busbar
4) : MAT3
5) : Earth conductor
L1
L2
L3
PE
N
Residual
Current
Circuit
Breaker
5)a and/or 5)b
6) : Protected device
EB : Main's earth electrode
ED : Switchgear's earth electrode
N
2)
*1
1
2
3
*2
4)
5)a
5)b
N
PE
*3
*4
6)
3)
EB
ED
*1. The circuit breaker or the fuse as disconnectors must be installed.
Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used.
The rated interrupting capacity of the circuit breaker must be greater than the highest amount of current that could be available in the circuit.
Install MCCB (rated current 20 – 30A) that has element for each phase.
Or RCD with protection from nuisance tripping against transit voltages type or time-delay overcurrent protection type is recommended.
Recommended sensitivity current rating: 30mA
*2. Cable length between the branch point and the earthing: 0.5 meters or less recommended
*3. The protected device's metal enclosure must be cross-wired to the earth terminal of the MAT3. If the protected device has no earth terminal,
earth only the MAT3.
*4. In order to protect an electronic circuit such as measuring equipment or communication equipment, we recommend to use surge protectors
which have serial impedance incorporated such as M-System's models MAX, MMA, MAH.
MAT3 SPECIFICATIONS
ES-8164 Rev.3 Page 3/5
http://www.m-system.co.jp/
MODEL: MAT3
■ CONNECTION EXAMPLES BY POWER SYSTEMS
Abnormal voltages appearing in case of a light load or a fault earth loop must be within the maximum continuous operational voltage when
selecting the MAT3 models.
Three phase/3-wire (delta connection)
Single-phase/2-wire
POWER SYSTEM
Power
Power
(N)
Protected
device
Protected
device
(N)
G
G
Circuit breaker
Circuit breaker
1
2
3
1
2
3
CONNECTION
Alarm output
Alarm output
A2
A1
C
A2
A1
C
SPD1
*1
SPD1
*1
N
PE
N
PE
SPD1
Power System (example)
Power System (example)
Three-phase/3-wire 220V AC
SPD1
MAT3 240xMx
EXAMPLE
Single-phase/2-wire 110V AC
Single-phase/2-wire 220V AC
MAT3
MAT3
–
240xMx
–
–240xMx
Single-phase/2-wire
(three-phase delta connection
earthed in the middle of phases)
POWER SYSTEM
Three-phase/4-wire (star connection)
Single-phase/3-wire
Power
N
Power
Protected
device
*3
Protected
device
G
G
Circuit breaker
N
Circuit breaker *2
1
2
3
CONNECTION
Alarm output
1
2
3
A2
A1
C
SPD1
*1
Alarm output
A2
A1
C
SPD1
N
PE
N
PE
SPD1
Power System (example)
Power System (example)
Three-phase/4-wire 220V AC
SPD1
MAT3 2404Mx
EXAMPLE
Single-phase/2-wire 110V AC
MAT3
MAT3
–
240xMx
240xMx
–
Single-phase/3-wire 220/110V AC
–
*1. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, connect between terminal 2 and N of the MAT3.
*2. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, install a four-pole (three-pole plus neutral)
circuit breaker.
*3. For single-phase/2-wire system, connect lines to terminal 1 and 2 of the MAT3. For single-phase/3-wire system, connect the neutral line to terminal 2
of the MAT3.
■ ALARM OUTPUT
When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required.
MAT3 SPECIFICATIONS
ES-8164 Rev.3 Page 4/5
http://www.m-system.co.jp/
MODEL: MAT3
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
80 (3.15)
60 (2.36)
50 (1.97)
15 (.59) 15 (.59)
5–M5 SCREW
TERMINAL COVER
*
1
2
3
DIN RAIL
35mm wide
SPECIFICATION
MONITOR LED
N
PE
[3.4 (.13)]
ALARM OUTPUT **
15 (.59)
TERMINAL
45°
(WIRE INSERTION ANGLE)
12.5 (.49)
A2
A1
C
*
Open/close type.
** Only for ‘Alarm output’ code ‘A’.
SCHEMATIC CIRCUITRY
1
2
3
Monitor LED
ѳ
ѳ
Alarm
Output
Circuit
ѳ
ѳ
N
PE
C
A1 A2
ѳ: Thermal breaker
Note: Terminals C, A1 & A2 are available for ‘Alarm output’ code ‘A.’
The schematic shows the relay contact status of a thermal trip
or power off.
Specifications are subject to change without notice.
MAT3 SPECIFICATIONS
ES-8164 Rev.3 Page 5/5
http://www.m-system.co.jp/
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明