MD7AST-24FG/Q [MSYSTEM]

Lightning Surge Protectors for;
MD7AST-24FG/Q
型号: MD7AST-24FG/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for

文件: 总4页 (文件大小:127K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MD7AST  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
[2] SHIELD TERMINAL (line / earth)  
FF: Floating / Floating  
FG: Floating / Grounding  
LIGHTNING SURGE PROTECTOR FOR  
[3] OPTIONS  
blank: none  
STANDARD SIGNAL LINE  
(ultra-slim; life monitor)  
/Q: With options (specify the specification)  
Functions & Features  
• High discharge current capacity 20 kA (8 / 20 μs), 1 kA (10  
/ 350 μs)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Ultra-thin 7-mm-wide module can be mounted  
in high density  
• Excellent protection employing multi-stage SPD circuits  
• DIN rail mounting and grounding  
• Shield terminal provided  
/C02: Polyurethane coating  
GENERAL SPECIFICATIONS  
Construction: Slim-sized front terminal structure  
Degree of protection: IP20  
• Life monitor function helps you to decide when you should  
replace the surge protector; reduces maintenance and  
prevents downtime  
Connection: Euro terminal block (torque 0.3 N·m)  
• Incorporated battery  
Applicable wire size: 0.2 – 2.5 mm  
2, stripped length 8 mm  
• Pressing CHK (Check) button confirms with  
LEDs the degradation and life span of the surge protection  
circuits  
Grounding: DIN Rail  
Housing material: Flame-resistant resin (black)  
Indicators: Activated by CHK (Check) button  
BAT: Green LED  
ALM: Red LED  
Degradation judged: When the leakage current at the  
voltage limiter exceeds approx. 7.5 μA.  
Life time judged: When the count of the discharge element  
discharging reaches the expected life span.  
CHK button: Push button; momentary  
7 [.28]  
95  
[3.74]  
Battery: Lithium; No recharge or replacement available.  
Battery life: 10 years (when used ≤ 2 minutes/month)  
100  
[3.94]  
INSTALLATION  
mm [inch]  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)  
Oxide film on the surface of an aluminium DIN rail may  
lower the electric conductivity between this module and the  
ground. Use a steel or copper rail.  
MODEL: MD7AST–[1][2][3]  
Weight: 70 g (2.5 oz)  
ORDERING INFORMATION  
• Code number: MD7AST-[1][2][3]  
Specify a code from below for each of [1] through [3].  
(e.g. MD7AST-24FF/Q)  
• Specify the specification for option code /Q  
(e.g. /C01)  
[1] NOMINAL VOLTAGE  
24: 24 V DC  
60: 60 V DC  
MD7AST SPECIFICATIONS  
ES-8067 Rev.5 Page 1/4  
https://www.m-system.co.jp/  
MODEL: MD7AST  
PERFORMANCE  
MODEL NO.  
NOMINAL VOLTAGE  
MD7AST-24  
MD7AST-60  
FG  
SHLD TERMINAL  
Line to Line  
FF  
FG  
FF  
Max. continuous  
operating voltage  
(Uc)  
30V  
70V  
Line to Earth  
Line to SHLD  
SHLD to Earth  
±±60V  
±±60V  
±±60V  
±±60V  
short  
±±60V  
short  
±±60V  
Voltage protection Line to Line  
level (Up)  
@6kV (±.2 / 50 µs)  
60V  
±±5V  
Line to Earth  
±ꢀ00V  
±ꢀ00V  
±ꢀ00V  
short  
Line to SHLD  
±±200V  
±ꢀ00V  
±ꢀ00V  
short  
±±200V  
±ꢀ00V  
SHLD to Earth  
Leakage current  
@Uc  
Line to Line  
≤ 5µA  
≤ 5µA  
≤ 5µA  
≤ 5µA  
≤ 4 nsec.  
≤ 20 nsec.  
Other sections  
Line to Line  
Response time  
≤ 4 nsec.  
≤ 20 nsec.  
Other sections  
Max. discharge current (Imax)  
Nominal current (IN)  
20kA (ꢀ / 20 µs), ±.0kA (±0 / 350 µs)  
250mA  
Internal series resistance  
Surge protection  
4.7Ω ±±0% per line  
±0Ω ±±0% per line  
IEC 6±643-2± Categories C±, C2, D±  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL VIEW  
CHK Check Button  
ALM Indicator LED  
BAT Indicator LED  
MD7AST SPECIFICATIONS  
ES-8067 Rev.5 Page 2/4  
https://www.m-system.co.jp/  
MODEL: MD7AST  
CONNECTION EXAMPLES  
4 – 20mA Field-mount  
Transmitter Surge Protector  
Surge Side  
Protected Side Current Loop Supply  
+
+
4
5
8
1
2
*4  
FG  
(model: MD6x)  
(SHLD)  
DIN RAIL  
ADAPTOR  
*3  
Crossover Wire  
*1  
DIN RAIL  
*2  
*1.Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.  
Use a steel or copper rail.  
*2.Be sure to ground the DIN rail. Recommended grounding resistance ≤100Ω  
*3.Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.  
Ground only the surge protector when the protected device has no ground terminal.  
*4.Shield wiring method is an example. Proceed according to the system requirements.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
8–M3 EURO  
TERMINAL  
WIRE INSERTION ANGLE: approx. 20°  
8
6
5
4
8
DIN RAIL  
ADAPTOR  
6
5
DIN RAIL  
4
(35 mm wide)  
1
2
3
7
1
2
3
7
(1.5 [.05])  
100 [3.94]  
7
[.28]  
MD7AST SPECIFICATIONS  
ES-8067 Rev.5 Page 3/4  
https://www.m-system.co.jp/  
MODEL: MD7AST  
SCHEMATIC CIRCUITRY  
SHIELD TERMINAL  
SCHEMATIC CIRCUITRY  
APPLICATIONS  
Line to SHLD: MD7AST-xFF  
Floating  
Standard type  
To protect a device having  
isolation between Signal  
and Earth.  
When SHLD should be  
floating against the earth.  
(single-end grounding)  
Surge Side  
Protected Side  
Earth to SHLD:  
Floating  
Series Resistance  
+
+
4
5
1
Voltage Limiter  
Leak. Curr.  
Detector  
DISCHARGE  
ELEMENT  
2
BAT  
(green)  
DISCHARGE  
ELEMENT  
CHK  
Check  
Button  
ALM  
(red)  
6
8
3
7
Surge  
Counter  
CT  
Battery  
DIN RAIL ADAPTOR  
(for grounding)  
(SHLD)  
DIN RAIL  
Grounding  
Line to SHLD: MD7AST-xFG  
Floating  
To protect a device having  
isolation between Signal  
and Earth.  
When SHLD should be  
grounded. (single- or both-  
end grounding)  
Surge Side  
Protected Side  
Earth to SHLD:  
Grounding  
Series Resistance  
+
+
4
5
1
Voltage Limiter  
DISCHARGE  
ELEMENT  
Leak. Curr.  
Detector  
2
BAT  
(green)  
CHK  
Check  
Button  
ALM  
(red)  
6
8
3
7
Surge  
Counter  
CT  
Battery  
DIN RAIL ADAPTOR  
(for grounding)  
(SHLD)  
DIN RAIL  
Grounding  
Specifications are subject to change without notice.  
MD7AST SPECIFICATIONS  
ES-8067 Rev.5 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

MD7AST-60FF

Lightning Surge Protectors for
MSYSTEM

MD7AST-60FF/Q

Lightning Surge Protectors for
MSYSTEM

MD7AST-60FG

Lightning Surge Protectors for
MSYSTEM

MD7AST-60FG/Q

Lightning Surge Protectors for
MSYSTEM

MD7DP

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7DP-12

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7DP-24

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7F-20P-2.54DS

2.54mm Pitch Bottom Entry Type Connector
HRS

MD7F-20P-2.54DS(55)

Board Connector, 20 Contact(s), 1 Row(s), Male, Right Angle, Solder Terminal, ROHS COMPLIANT
HRS

MD7F-20P-2.54DS(56)

Board Connector, 20 Contact(s), 1 Row(s), Male, Right Angle, Solder Terminal, ROHS COMPLIANT
HRS

MD7FB

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7FB-FF0

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM