MD7DP-24 [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MD7DP-24
型号: MD7DP-24
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总2页 (文件大小:111K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MD7DP  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
LIGHTNING SURGE PROTECTOR FOR  
DC POWER SUPPLY  
(max. 1.2 A; ultra-slim)  
GENERAL SPECIFICATIONS  
Construction: Slim-sized front terminal structure  
Degree of protection: IP20  
Functions & Features  
• High discharge current capacity 20 kA (8/20 μs), 1 kA  
(10/350 μs)  
Connection: Euro terminal block (torque 0.3 N·m)  
Applicable wire size: 0.2 – 2.5 mm2, stripped length 8 mm  
• Ultra-thin 7-mm-wide module can be mounted  
in high density  
Grounding: DIN Rail  
Housing material: Flame-resistant resin (black)  
Monitor LED: Green LED turns ON when the voltage is  
supplied; OFF when the safety fuse is blown.  
• Excellent protection employing multi-stage SPD circuits  
• DIN rail mounting and grounding  
• Shield terminal provided  
INSTALLATION  
DC power supply: Max. output current 1.2 A  
Caution: Use a DC power source with the overload current  
protection function.  
7 [.28]  
Operating temperature: -25 to +85°C (-13 to +185°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)  
Oxide film on the surface of an aluminium DIN rail may  
lower the electric conductivity between this module and the  
ground. Use a steel or copper rail.  
95  
[3.74]  
98  
[3.86]  
Weight: 70 g (2.5 oz)  
mm [inch]  
PERFORMANCE  
LINE TO LINE  
LINE TO  
EARTH  
MODEL: MD7DP-[1][2]  
MD7DP-12 MD7DP-24  
Max. continuous  
operating voltage (Uc)  
14V  
27V  
160V  
1200V  
≤ 5µA  
ORDERING INFORMATION  
• Code number: MD7DP-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. MD7DP-24/Q)  
Voltage protection level  
(Up) @4kV (1.2 / 50 µs)  
150V  
170V  
Leakage current @Uc  
Response time  
≤ 6mA  
≤ 6mA  
≤ 4 nsec.  
≤ 4 nsec. ≤ 20 nsec.  
20kA (8 / 20 µs)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Max. discharge current  
(Imax)  
1.0kA (10 / 350 µs)  
1.2A  
Nominal current (IN)  
Internal series resistance  
Surge protection  
≤ 0.8Ω including return  
IEC 61643-21 Categories C1, C2, D1  
[1] NOMINAL VOLTAGE  
12: 12 V DC  
24: 24 V DC  
STANDARDS & APPROVALS  
EU conformity:  
[2] OPTIONS  
EMC Directive  
blank: none  
EMI EN 61000-6-4  
/Q: With options (specify the specification)  
EMS EN 61000-6-2  
RoHS Directive  
MD7DP SPECIFICATIONS  
ES-8052 Rev.8 Page 1/2  
https://www.m-system.co.jp/  
MODEL: MD7DP  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
8–M3 EURO  
TERMINAL  
WIRE INSERTION ANGLE: approx. 20°  
8
6
5
4
8
DIN RAIL  
ADAPTOR  
6
5
DIN RAIL  
4
(35 mm wide)  
MONITOR LED  
1
2
3
7
1
2
3
7
(1.5 [.06])  
98 [3.86]  
7
[.28]  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
*2  
DC Power  
Supply  
(protected)  
Electronic  
Protected  
Device  
Protected  
Side  
Surge  
Side  
Surge  
Side  
*1  
MD7DP  
*1  
MD7DP  
Side  
(protected)  
*3  
+
+
1
4
+
+
4
1
SAFETY  
FUSE  
SAFETY  
FUSE  
MONITOR LED  
MONITOR LED  
POWER  
INPUT  
VOLTAGE INDICATOR  
LIMITER CIRCUIT  
DISCHARGE  
ELEMENT  
DISCHARGE  
ELEMENT  
INDICATOR VOLTAGE  
CIRCUIT LIMITER  
2
3
7
5
6
8
5
6
8
2
3
7
DIN RAIL ADAPTOR  
(for grounding)  
DIN RAIL ADAPTOR  
(for grounding)  
FG  
FG  
*6  
*6  
Crossover Wire  
Crossover Wire  
*4  
*4  
DIN RAIL  
DIN RAIL  
*5  
*5  
Grounding  
Grounding  
*1. The MD7DP is not applicable to protect two-wire transmitters. To protect two-wire transmitters,  
model MD7ST designed to yield only small leakage current is suitable.  
Confirm the polarity of the terminals when connecting this module to a protected device.  
*2. Use a DC power source with the overload current protection function. (maximum output current 1.2A)  
*3. Install a current limiting element (capacity 1.2A) when the output current exceeds 1.2A.  
*4. Oxide coating of an aluminium rail may lower the electric conductivity between this module and the ground.  
Use a steel or copper rail.  
*5. Be sure to ground the DIN rail. Recommended grounding resistance ≤100  
*6. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.  
Ground only the surge protector when the protected device has no ground terminal.  
Specifications are subject to change without notice.  
MD7DP SPECIFICATIONS  
ES-8052 Rev.8 Page 2/2  
https://www.m-system.co.jp/  

相关型号:

MD7F-20P-2.54DS

2.54mm Pitch Bottom Entry Type Connector
HRS

MD7F-20P-2.54DS(55)

Board Connector, 20 Contact(s), 1 Row(s), Male, Right Angle, Solder Terminal, ROHS COMPLIANT
HRS

MD7F-20P-2.54DS(56)

Board Connector, 20 Contact(s), 1 Row(s), Male, Right Angle, Solder Terminal, ROHS COMPLIANT
HRS

MD7FB

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7FB-FF0

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7FB-FF0/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7FB-FG0

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7FB-FG0/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MD7IC18120GNR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-1880 MHz, 30 W Avg., 28 V
NXP

MD7IC18120NR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-1880 MHz, 30 W Avg., 28 V
NXP

MD7IC1812GNR1

RF/MICROWAVE NARROW BAND HIGH POWER AMPLIFIER
NXP

MD7IC1812NR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-2170 MHz, 1.3 W Avg., 28 V
NXP