MDP-24-1/A33 [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MDP-24-1/A33
型号: MDP-24-1/A33
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总4页 (文件大小:138K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MDP-24-1  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
LIGHTNING SURGE PROTECTOR FOR  
/C03: Rubber coating (UL not available)  
STANDARD SIGNAL LINE & PULSE USE  
Functions & Features  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
• Designed specifically for 4 – 20mA DC and  
pulse signal line including both 4-wire and 2-wire  
transmitters  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
• Absorbs surges only without affecting instrumentation  
signal  
• No interruption of signal by unplugging surge protector  
element  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Application Examples  
• Protects two-wire transmission lines  
• Protects electronic instruments’ I/O  
Weight:  
120 g (0.26 lb), standard  
145 g (0.32 lb), with DIN rail mounting adapter  
23.5 [.93]  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
Line to line: 30 V  
Lot.NO  
N1430B  
100  
[3.94]  
PAN  
 J
MADEIN  
Line to earth: ±140 V  
M•STER  
MODEL  
Voltage protection level (Up):  
• @ 1 kV (100 A)  
80 [3.15]  
mm [inch]  
Line to line: 40 V  
Line to earth: ±650 V  
• @ 2 kV (1 kA)  
MODEL: MDP–24–1[1]  
Line to line: 45 V  
Line to earth: ±800 V  
Response time:  
ORDERING INFORMATION  
• Code number: MDP-24-1[1]  
Specify a code from below for [1].  
(e.g. MDP-24-1/A33/CE/Q)  
Line to line: ≤ 4 nsec.  
Line to earth: ≤ 20 nsec.  
Leakage current:  
Line to line: ≤ 5 μA @ 30 V DC  
Line to earth: ≤ 5 μA @ ±140 V DC  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Nominal current (I ): 100 mA  
N
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Internal series resistance: 20 Ω ±10 % (including return)  
Capacitance @ 1 MHz:  
Line to line: ≤ 1000 pF  
/A33: With adapter (model A-33)  
Standards & Approvals (must be specified)  
/N: Without CE or UL  
Line to earth: ≤ 100 pF  
Surge protection: IEC 61643-21 Categories C1, C2, D1  
/CE: CE marking  
/UL: UL approval, CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
MDP-24-1 SPECIFICATIONS  
ES-8119 Rev.22 Page 1/4  
https://www.m-system.co.jp/  
MODEL: MDP-24-1  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
Approval:  
Protectors for Data Communications and Fire  
Alarm Circuits (UL 497B)  
CONNECTION EXAMPLES  
PROTECTING TWO-WIRE SIGNAL LINES  
PROTECTING ELECTRONIC INSTRUMENTS’ I/O  
CENTRAL  
STATION  
Transmitter  
(protected device)  
Receiver  
(protected device)  
CURRENT LOOP SUPPLY  
(protected device)  
Signal  
Line  
M-RESTER  
M-RESTER  
M-RESTER  
FROM  
FIELD  
*1  
+
+
+
+
U
V
P+  
P–  
S+  
S–  
S+  
S–  
P+  
P–  
U
V
+
IN  
P+  
P–  
S+  
S–  
*2  
*2  
G
G
G
G
G
G
*1. Install a circuit protector when the transmitter output current exceeds 100mA.  
*2. The M-RESTER is designed in particular to protect signal lines.  
To protect power supply lines, install other types of surge protectors.  
FIELD  
2-WIRE TRANSMITTER  
(protected device)  
M-RESTER  
+
P+  
P–  
S+  
S–  
CABLE  
TO  
CENTRAL  
STATION  
G
G
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
MDP-24-1 SPECIFICATIONS  
ES-8119 Rev.22 Page 2/4  
https://www.m-system.co.jp/  
MODEL: MDP-24-1  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
STANDARD  
80 [3.15]  
53 [2.09]  
2–5 [.20] dia.  
MTG HOLE  
23.5 [.93]  
27 [1.06]  
HEAD ELEMENT  
P+  
P–  
BASE  
4–M4 TERMINAL SCREW  
S+  
S–  
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
[.33]  
80 [3.15]  
53 [2.09]  
(3.3 [.13])  
27 [1.06]  
23.5 [.93]  
DIN RAIL  
35mm wide  
P+  
P–  
4–M4 TERMINAL SCREW  
S+  
S–  
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MOUNTING REQUIREMENTS unit: mm [inch]  
2–M4 SCREW  
25 [.97] min.  
MDP-24-1 SPECIFICATIONS  
ES-8119 Rev.22 Page 3/4  
https://www.m-system.co.jp/  
MODEL: MDP-24-1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
20Ω  
+ S  
P +  
ELEMENT  
Discharge  
Elements  
*
SURGE  
SIDE  
PROTECT  
SIDE  
ZD  
– S  
P –  
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
*The zenor diode has polarity.  
Zero-cross signal cannot be connected.  
Specifications are subject to change without notice.  
MDP-24-1 SPECIFICATIONS  
ES-8119 Rev.22 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

MDP-24-1/CE

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-24-1/N

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-24-1/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-24-1/UL

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-3

Interconnection Device
POMONA

MDP-4R

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-4R/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-4R/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-5

暂无描述
POMONA

MDP-65-1

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/CE

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM