MDP-PA [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDP-PA |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总4页 (文件大小:126K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDP-PA
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
LIGHTNING SURGE PROTECTOR FOR
PROFIBUS-PA
Functions & Features
INSTALLATION
• Designed specifically for the network
• No interruption of transmission signal by unplugging the
head element module
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN
rail mounting adapter
Lot.NO
4
PERFORMANCE
Max. continuous operating voltage (Uc):
M•STER
MODEL
Line to line: 27 V
Line to earth: ±160 V
SHLD to earth: ±160 V
Voltage protection level (Up):
• @ 2 kV (1 kA)
MODEL: MDP–PA[1]
Line to line: ±60 V
ORDERING INFORMATION
• Code number: MDP-PA[1]
Specify a code from below for [1].
(e.g. MDP-PA/A33/Q)
Line to earth: ±600 V
SHLD to earth: ±600 V
Response time:
Line to line: ≤ 4 nsec.
• Specify the specification for option code /Q
(e.g. /C01)
Line or SHLD to earth: ≤ 20 nsec.
Leakage current:
Line to line: ≤ 5 μA @ ±27 V
Line to earth: ≤ 5 μA @ ±160 V
SHLD to earth: ≤ 5 μA @ ±160 V
Max. discharge current (Imax): 5000 A (8 / 20 μs)
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
Nominal current (I ): 500 mA
N
/A33: With adapter (model A-33)
Other Options
Internal series resistance: ≤ 3.3 Ω including return
Capacitance @ 1 MHz:
blank: none
Line to line: ≤ 1500 pF
/Q: Option other than the above (specify the specification)
Line to earth: ≤ 100 pF
SHLD to earth: ≤ 100 pF
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Surge protection: IEC 61643-21 Categories C1, C2
/C02: Polyurethane coating
/C03: Rubber coating
APPLICABLE NETWORK
PROFIBUS-PA , Foundation Fieldbus and other networks
complied with IEC 61158-2
Note 1: This unit is not approved for classified locations.
Note 2: Power supply to the bus must be limited to 500 mA
or less.
MDP-PA SPECIFICATIONS
ES-8207 Rev.9 Page 1/4
http://www.m-system.co.jp/
MODEL: MDP-PA
CONNECTION EXAMPLES
■ CONNECTION DIAGRAM
M-RESTER
Protected Device
+
A
C
B
1
3
2
PA
BUS
–
*1
SHLD
*2
G
G
Cross wiring
Grounding
≤ 100Ω
*1. Cross wire to the surge protector’s ‘G’ terminal when grounding the shield wire.
If the shield wire is not to be grounded, connect it to ‘B’ terminal.
*2. Follow instructions provided with the protected device whether ‘2’ terminal
should be connected or not. However, if the shield terminal of the protected
device is not isolated from PA BUS, DO NOT connect ‘2’ terminal to the
protected device.
■ NETWORK CONFIGURATION
M-RESTER
*1
G
G
G
G
Crossover Wire
Protected
Devices
(Nodes)
M-RESTER
G
G
G
Protected
Devices
(Nodes)
Crossover Wire
*1. Fieldbus devices complying with IEC 61158-2 operate by a supply voltage between
9V and 32V DC.
Take the MDP-PA’s internal series resistance into consideration when determining the
cable distance if there is a large current flow on the bus line.
When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),
install the MDP-PA by each group of devices. Insert the MDP-PA at the surge side of the network.
For detailed information on the network, refer to that provided by PROFIBUS International or
Fieldbus Foundation.
MDP-PA SPECIFICATIONS
ES-8207 Rev.9 Page 2/4
http://www.m-system.co.jp/
MODEL: MDP-PA
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ STANDARD
80 (3.15)
2–5 (.20) dia.
31.5 (1.24)
MTG HOLE
53 (2.09)
27 (1.06)
HEAD ELEMENT
3
2
1
BASE
6–M4 TERMINAL SCREW
C
B
A
GROUND TERMINAL (G)
(used as mounting bracket)
■ WITH DIN RAIL MOUNTING ADAPTER
8.5
(.33)
[3.3 (.13)]
80 (3.15)
53 (2.09)
27 (1.06)
31.5 (1.24)
DIN RAIL
35mm wide
3
2
1
6–M4 TERMINAL SCREW
C
B
A
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MDP-PA SPECIFICATIONS
ES-8207 Rev.9 Page 3/4
http://www.m-system.co.jp/
MODEL: MDP-PA
MOUNTING REQUIREMENTS unit: mm (inch)
2–M4 SCREW
33 (1.30) min.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
1.5 W
+
+
–
A
1
3
PA BUS
PA BUS
1.5 W
– C
HEAD
ELEMENT
Surge
Side
Protected
Device Side
Discharge
Element
Voltage
Limiter
SHIELD B
2
SHIELD
BASE
G
GROUND TERMINAL
(used as mounting attachment)
Specifications are subject to change without notice.
MDP-PA SPECIFICATIONS
ES-8207 Rev.9 Page 4/4
http://www.m-system.co.jp/