MMAJ-20030LY [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MMAJ-20030LY
型号: MMAJ-20030LY
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总3页 (文件大小:127K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MMAJ  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
[4] ALARM OUTPUT  
A: With  
Y: Without  
LIGHTNING SURGE PROTECTOR  
GENERAL SPECIFICATIONS  
Construction: Wall-mounted, front terminals; terminal cover  
FOR POWER SUPPLY USE  
(fast response: 3 nsec.)  
provided  
Functions & Features  
Surge protection type: Surge energy limiting type two-port  
• Designed to protect equipment from induced  
lightning surges entering through power supply cables  
• High discharge current capacity type with a  
maximum of 20 kA is available.  
SPD  
Connection  
Line: M4 screw terminal (torque: 1.2 N·m)  
Alarm output: Tension clamp  
• Degraded head element is automatically separated from  
the power lines by the incorporated thermal breaker, and  
the LED lamp (turns off) and the relay contact alert the  
failure status.  
Applicable wire size: 0.33 to 1.5 mm  
(6 to 7 mm exposed)  
Screw terminal: Nickel-plated steel  
2
2
Housing material: Steel plate t = 1.2 (black)  
Alarm output: SPDT relay contact trips when the thermal  
breaker operates.  
• Conforms to IEC 61643-1 Class II, III  
88  
(3.46)  
Normal  
Output terminal A1 – C: Open  
Output terminal A2 – C: Close  
Surge  
Side  
Protect  
Thermal breaker operating or power off  
Output terminal A1 – C: Close  
Side  
80  
(3.15)  
U
u
v
V
Output terminal A2 – C: Open  
PE  
Monitor  
A2  
A1  
C
Rated load:  
ALM  
139  
250 V AC @1 A (cos ø = 1)  
(5.47)  
24 V DC @1 A (resistive load)  
mm (inch)  
Maximum switching voltage: 250 V AC or 24 V DC  
Maximum switching power: 250 VA or 24 W  
Minimum load: 5 V DC @ 20 mA  
MODEL: MMAJ-[1][2][3][4]  
Safety function: Thermal breaker incorporated  
Monitor LED: Green LED; ON in normal conditions OFF in  
failure conditions (power off or thermal breaker operating)  
ORDERING INFORMATION  
• Code number: MMAJ-[1][2][3][4]  
Specify a code from below for each [1] through [4].  
(e.g. MMAJ-10020MA)  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface  
[1] OPERATIONAL VOLTAGE  
100: 100 V / 110 V / 120 V AC  
Weight: 1.6 kg (3.5 lb)  
200: 200 V / 220 V / 240 V AC  
[2] LOAD CURRENT  
10: 10 A  
20: 20 A  
30: 30 A  
[3] MAXIMUM DISCHARGE CURRENT  
L: 10 kA  
M: 20 kA  
MMAJ SPECIFICATIONS  
ES-8155 Rev.3 Page 1/3  
http://www.m-system.co.jp/  
MODEL: MMAJ  
PERFORMANCE  
Surge protection: IEC 61643-1 Class II, III  
MMAJ-100xxx  
132V AC  
MMAJ-200xxx  
Max. Continuous Operating Voltage (Uc)  
Operational Volatge Range *1  
264V AC  
85 – 132V AC  
170 – 264V AC  
Line to line: 190V  
Line to earth: 300V  
Line to line: 380V  
Line to earth: 450V  
Discharge Voltage (Vmin)  
Voltage Protection Level (Up)  
Leakage Current @ Uc  
900V  
1500V  
Line to line: Without Alarm 6mA, With Alarm 20mA  
Line to earth:  
MMAJ-xxL: 5kA  
MMAJ-xxM: 10kA  
Nominal Discharge Current (In)  
MMAJ-x10: 10A  
MMAJ-x20: 20A  
MMAJ-x30: 30A  
Max. Load Current *2  
Voltage Drop  
≤1V  
MMAJ-10010: -56 dB  
MMAJ-10020: -56 dB  
MMAJ-10030: -40 dB  
MMAJ-20010: -53 dB  
MMAJ-20020: -53 dB  
MMAJ-20030: -40 dB  
Surge Energy Attenuation Ratio @8/20 µs  
(Line to earth)  
Response Time (Line to line)  
Insulation Resistance  
Dielectric Strength  
3 nsec.  
≥100MΩ with 500V DC (line to alarm output to housing)  
2000V AC @1 minute (line to alarm output to housing)  
*1. MMAJ is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED  
and the alarm output are not guaranteed.  
*2. Refer to Derating Curve  
■ DERATING CURVE  
100  
10A  
20A  
30A  
50  
0
-5  
0
20  
40  
55 60  
Ambient Air Temperature (°C)  
MMAJ SPECIFICATIONS  
ES-8155 Rev.3 Page 2/3  
http://www.m-system.co.jp/  
MODEL: MMAJ  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
4 – M4 SLOT  
Surge Protect  
Side  
Side  
U
u
v
V
Monitor  
PE  
A2  
A1  
C
ALM  
66 (2.60)  
75 (2.95)  
77 (3.03)  
88 (3.46)  
22  
117 (4.61)  
(0.87)  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Protect Side  
Protected Device  
Surge Side  
U
u
u
Monitor LED  
ѳ
ѳ
*1  
A2  
A1  
C
Alarm  
Output  
Circuit  
ѳ
U
ѳ
V
v
v
PE  
*3  
G
*2  
Crossover wire  
ѳ
: Thermal breaker  
*1. Sections enclosed with broken line are applicable for “alarm output” option.  
The schematic shows the relay contact status of a thermal trip or power off.  
*2. Be sure to make a cross-wire. If the protected device has no earth terminal, earth only the MMAJ.  
*3. “PE” stands for “Protective Earth”. Besides “PE” M-RESTER has a terminal called “G”,  
both terminals are for grounding.  
Specifications are subject to change without notice.  
MMAJ SPECIFICATIONS  
ES-8155 Rev.3 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY