R3-AV4S/Q [MSYSTEM]
Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE;型号: | R3-AV4S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE 输入元件 |
文件: | 总4页 (文件大小:132K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-AV4
Remote I/O R3 Series
CAUTION
■UNUSED INPUT CHANNELS
Set the unused channels to the ranges other than 1 - 5 V.
Otherwise, set them as "Unused" with PC Configurator
software: R3CON. Unused channels left open with 1 – 5 V
setting are equal to the input lower than -15 %, which sets a
data abnormality at the PLC or the host device.
Open circuit with the input range set to ±10 V means 50 %
of the full-scale. An alarm setpoint must be set to a value
that does not trip an unwanted alarm.
DC VOLTAGE INPUT ALARM MODULE
(4 points, isolated)
27.5 [1.08]
130
[5.12]
GENERAL SPECIFICATIONS
Connection
109
[4.29]
mm [inch]
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
MODEL: R3–AV4[1][2]
Isolation: Input 1 to input 2 to input 3 to input 4 to internal
bus or internal power
ORDERING INFORMATION
• Code number: R3-AV4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-AV4W/CE/Q)
Input range: Selectable with the side DIP SW
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response
failure);
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
4: 4
Green in normal operating conditions.
[1] COMMUNICATION MODE
S: Single
INPUT SPECIFICATIONS
■ Narrow Span: -1 – +1 V, 0 – 1 V DC
Input resistance: 100 kΩ min.
■ Wide Span: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
W: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Input resistance: 1 MΩ min.
/CE: CE marking
Other Options
INSTALLATION
blank: none
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
R3-AV4 SPECIFICATIONS
ES-8435 Rev.7 Page 1/4
https://www.m-system.co.jp/
MODEL: R3-AV4
■ALARM ON DELAY TIME
PERFORMANCE
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all four points.
■POWER ON DELAY TIME
Conversion accuracy: Refer to the table at the end of this
section.
Conversion rate: 80 / 40 / 20 / 10 msec. selectable
Data allocation: 1
Current consumption: 60 mA
(0.0 to 99.0 sec.; factory set to 5.0)
Temp. coefficient: ±0.015 % /°C (±0.008 %/°F)
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.
■ALARM HOLD TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is
reset in shorter time.
Conversion accuracy
This setting is common to all four points.
RATE
80 msec. 40 msec. 20 msec. 10 msec.
RANGE
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
0ꢀ1ꢁ
0ꢀ.ꢁ
0ꢀꢂꢁ
-10 – +10 V
-5 – +5 V
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
-1 – +1 V
0 – 10 V
0 – 5 V
1 – 5 V
0 – 1 V
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀ.ꢁ
0ꢀꢃꢁ
0ꢀꢃꢁ
0ꢀꢂꢁ
0ꢀ1ꢁ
0ꢀ05ꢁ
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
ALARM SETTING
The following parameters are programmable using the PC
Configurator Software (model: R3CON).
■ALARM TRIP POINT (-15.00 to +115.00 %;
factory set to A1: 80.00, A2: 60.00, A3: 40.00, A4: 20.00)
Four alarm setpoints are selectable per each input.
■ALARM TYPE
(High or Low; factory set to A1: High, A2: High, A3: Low,
A4: Low)
High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes
above the setpoint.
Low alarm: An alarm is set when the input signal goes below
the setpoint.
■DEADBAND (HYSTERESIS)
(0.00 to 100.00 %; factory set to 5.00)
Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.
R3-AV4 SPECIFICATIONS
ES-8435 Rev.7 Page 2/4
https://www.m-system.co.jp/
MODEL: R3-AV4
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
ERR LED
Functions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SW3
ON
SW2
SW1
Range
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)
or
Input 4 (SW2)
Conv.
Rate
Input 1 (SW1)
or
Input 3 (SW2)
ON
ON
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. One (1) word (16 bit) data is transmitterd to the PLC or the host device via
the R3 network module.
15
0
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Input 1
Input 2
Input 3
Input 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
R3-AV4 SPECIFICATIONS
ES-8435 Rev.7 Page 3/4
https://www.m-system.co.jp/
MODEL: R3-AV4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Input Circuit
INTERNAL BUS A
Communication
Circuit
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
1
2
INTERNAL BUS B*
WIDE SPAN
NARROW SPAN
WIDE SPAN
INPUT 1
INPUT 2
INPUT 3
INPUT 4
Control
Circuit
11
12
3
INTERNAL POWER
Input Circuit
Input Circuit
Input Circuit
5
4
10
15
20
13
14
6
NARROW SPAN
WIDE SPAN
7
16
17
8
NARROW SPAN
WIDE SPAN
9
18
19
NARROW SPAN
* For dual redundant communication.
Note: Connect either wide or narrow span terminals for each channel.
Specifications are subject to change without notice.