R3-DAC16AS [MSYSTEM]
Remote I/O R3 Series DISCRETE INPUT OUTPUT MODULE;型号: | R3-DAC16AS |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DISCRETE INPUT OUTPUT MODULE 输入元件 输出元件 |
文件: | 总7页 (文件大小:179K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-DAC16A
Remote I/O R3 Series
CAUTION
• This unit is not designed to be used with the following
types of interface modules (models: R3-NC2, R3-NEIP1, R3-
NFx, R3-NLx).
DISCRETE INPUT OUTPUT MODULE
(Di & Do 8 points each; internal power)
Typical Applications
• Output completion status data is compatible with interface
modules (models: R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-
NFL1, R3-NM1, R3-NM4, R3-NP1) of firmware version V2.00
or higher, and interface modules (models: R3-NM3, R3-
NML3) of firmware version V1.00 or higher.
• Controls start/stop of field devices with ON/OFF control
output
• Simplifies signal hold circuit of field devices
• Utilizing One-Shot Output reduces the load of PLC side.
27.5 (1.08)
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input, Output: M3 separable screw terminal (torque 0.5
N·m)
130
(5.12)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
109
(4.29)
Isolation: I/O to internal bus or internal power
Output mode setting: One-Shot Output Mode, ON/OFF
Control Output Mode, Continuance Output Mode selectable
with DIP switch
mm (inch)
Data length Setting: 8bit, 4bit selectable with DIP switch
(For ON/OFF Control Output Mode only)
One-shot ON time setting: 0.1 to 25.6 sec. selectable with
DIP switch
MODEL: R3–DAC16A[1][2]
ORDERING INFORMATION
• Code number: R3-DAC16A[1][2]
Specify a code from below for each [1] and [2].
(e.g. R3-DAC16AW/Q)
Max. ON points at once setting: 1, 2 , 4 , 8 selectable with
DIP switch (only in One-Shot Output Mode and ON/OFF
Control Output Mode)
• Specify the specification for option code /Q
(e.g. /C01)
ON/OFF control output setting: Swappable its pair with DIP
switch.
Output hold setting: Setting for communication error with
side DIP SW
NO. OF CHANNELS
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/ green) LED;
Green in normal operating conditions
Red with the abnormal configuration
Status indicator: Red LED;
16: 8 points input, 8 points output
EXCITATION SUPPLY
A: Internal
[1] COMMUNICATION MODE
S: Single
W: Dual
1 to 8: Intput status, turns on with input ON.
9 to 16: Output status, turns on with output ON.
Di read rate setting: 1 / 5 / 10 / 20 / 50 / 70 / 100 / 200
msec. selectable with DIP SW
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
INPUT SPECIFICATIONS
Number of input: 8 points
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Isolation: Optical isolator
Input resistance: Approx. 6 kΩ
Common: All 8 points (4 terminals, common with the
output)
/C02: Polyurethane coating
/C03: Rubber coating
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 1/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
Sensing: 24 V DC +10 %
ON current/resistance: ≥ 2.5 mA, ≤ 5.5 kΩ
OFF current/resistance: ≤ 1.5 mA, ≥ 7 kΩ
Detection levels
Divide the points to be ON at once. When the total of load
current exceeds the maximum load current, "Max. ON
Points at Once" function is activated.
The number of the channel turned ON is output in order
from the lowest.
ON: ≥ 15 V
OFF: ≤ 9 V
Example: Max. ON Points at Once: 1 point; One-shot ON
Time setting: 1 sec.
Ch1, 2, 4, 8 all ON: Ch1→Ch2→Ch4→Ch8 are turned ON in
this order in a total time of 4 seconds.
OUTPUT SPECIFICATIONS
Output: Wet contact, 8 points
Note: When writing in the same channel two or more times,
check the previous output completion status to set the
output.
Common: All 8 points (4 terminals, common with the input)
Output voltage: 24 V DC±10 %
Max. load current: 150 mA per point, common
Load resistance: 160 Ω min.
4sec.
1sec.
INSTALLATION
Ch1
Ch2
Ch4
Ch8
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Output ON time accuracy: Greater between ±5 % of max.
time or ±0.1 sec. setting
Data allocation: 1
Current consumption: 350 mA
Response time: ≤ 0.1 sec. (delay)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (I/O to internal
bus or internal power)
2000 V AC @ 1 minute (internal power to FG; isolated on the
power supply module)
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
•Output Hold
If both are in error, the module holds the signal and stands
by until one of the communications recovers.
•Output OFF
If both are in error, the module outputs OFF signals and
stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is
established and normal data is received.
■ MAX. ON POINTS AT ONCE
Function available for One-Shot Output Mode and ON/OFF
Control Output Mode.
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 2/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
ERR LED
Functions
RUN LED
SW2
SW1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ON/OFF Control
Output
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
I/O Status Indicator LED
One-Shot
ON Time
Max. ON Points at
Once
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Di Read Rate
ON
ON
Functions
SW3
ON
Data Length
Output Mode
Output Hold
4
3
2
1
I/O DATA DESCRIPTIONS
■ ONE-SHOT OUTPUT MODE
8-bit output data (Do 1 through 8) and output (Ch1 through 8) are assigned 1:1.
Do
WRITE
ONE-SHOT OUTPUT/RESET
Ch1 Output
Di
OUTPUT COMPLETION STATUS
Ch1 Output Completion Status
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Di 9
Do 1
Ch1 Output Completion Reset
Ch2 Output
Di 10
Di 11
Di 12
Di 13
Di 14
Di 15
Di 16
Ch2 Output Completion Status
Ch3 Output Completion Status
Ch4 Output Completion Status
Ch5 Output Completion Status
Ch6 Output Completion Status
Ch7 Output Completion Status
Ch8 Output Completion Status
Do 2
Do 3
Do 4
Do 5
Do 6
Do 7
Do 8
Ch2 Output Completion Reset
Ch3 Output
Ch3 Output Completion Reset
Ch4 Output
Ch4 Output Completion Reset
Ch5 Output
Ch5 Output Completion Reset
Ch6 Output
Ch6 Output Completion Reset
Ch7 Output
Ch7 Output Completion Reset
Ch8 Output
Ch8 Output Completion Reset
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 3/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
■ ON/OFF CONTROL OUTPUT MODE
• Data Length: 8 bits
Do 1 through 8 are assigned to Ch1 through 8.
Do
WRITE
ONE-SHOT OUTPUT/RESET
Not Operating
Di
OUTPUT COMPLETION STATUS
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
Ch1 Output
Di 9
Ch1 Output Completion Status
Ch2 Output Completion Status
Do 1 Do 2
Ch2 Output
Di 10
Output Data Reset
Not Operating
Ch3 Output
Di 11
Di 12
Ch3 Output Completion Status
Ch4 Output Completion Status
Do 3 Do 4
Do 5 Do 6
Do 7 Do 8
Ch4 Output
Output Data Reset
Not Operating
Ch5 Output
Di 13
Di 14
Ch5 Output Completion Status
Ch6 Output Completion Status
Ch6 Output
Output Data Reset
Not Operating
Ch7 Output
Di 15
Di 16
Ch7 Output Completion Status
Ch8 Output Completion Status
Ch8 Output
Output Data Reset
The above table shows the case of Not Swapped (SW2-8: OFF). ON/OFF control output is swapped with its pair when SW2-8 is
ON. The following is an example of Do 1 and Do 2.
Do
WRITE
ONE-SHOT OUTPUT/RESET
Not Operating
Di
OUTPUT COMPLETION STATUS
0
1
0
1
0
0
1
1
Ch2 Output
Di 10
Di 9
Ch2 Output Completion Status
Ch1 Output Completion Status
Do 1 Do 2
Ch1 Output
Output Data Reset
• Data Length: 4 bits
Do 1 through 4 are assigned to Ch1 through 8 as 1:2.
Do
WRITE
0
ONE-SHOT OUTPUT/RESET
Ch1 Output
Di
OUTPUT COMPLETION STATUS
Ch1 Output Completion Status
Di 9
Do 1
1
Ch2 Output
Di 10
Ch2 Output Completion Status
0
1
0
1
0
1
Ch3 Output
Ch4 Output
Ch5 Output
Ch6 Output
Ch7 Output
Ch8 Output
Di 11
Di 12
Di 13
Di 14
Di 15
Di 16
Ch3 Output Completion Status
Ch4 Output Completion Status
Ch5 Output Completion Status
Ch6 Output Completion Status
Ch7 Output Completion Status
Ch8 Output Completion Status
Do 2
Do 3
Do 4
The above table shows the case of Not Swapped (SW2-8: OFF). ON/OFF control output is swapped with its pair when SW2-8 is
ON. The following is an example of Do 1.
Do
WRITE
0
ONE-SHOT OUTPUT/RESET
Ch2 Output
Ch1 Output
Di
OUTPUT COMPLETION STATUS
Ch2 Output Completion Status
Di 10
Do 1
1
Di 9
Ch1 Output Completion Status
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 4/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
■ CONTINUOUS OUTPUT MODE
Do 1 through 8 are assigned to and Ch1 through 8. When data Do is “1” output is ON and when it is “0” output is OFF. Output
completion status Di is related to Do.
Do
CONTINUOUS OUTPUT
Ch1 Output
Di
OUTPUT COMPLETION STATUS
Ch1 Output Completion Status
Do 1
Di 9
Do 2
Ch2 Output
Di 10
Ch2 Output Completion Status
Do 3
Do 4
Do 5
Do 6
Do 7
Do 8
Ch3 Output
Ch4 Output
Ch5 Output
Ch6 Output
Ch7 Output
Ch8 Output
Di 11
Di 12
Di 13
Di 14
Di 15
Di 16
Ch3 Output Completion Status
Ch4 Output Completion Status
Ch5 Output Completion Status
Ch6 Output Completion Status
Ch7 Output Completion Status
Ch8 Output Completion Status
DATA ASSIGNMENT
■ Do
15
0
Do 1
Do 2
Do 3
Do 8
Note 1: For 4-bit length ON/OFF control mode, Do 5 through Do 8 are unavailable.
Note 2: For the combination with Modbus communication module (model: R3-NE1, R3-NM1 and such),
use the addresses of Coil (0X) for Modbus I/O assignment.
■ Di
15
0
Di 1
Di 2
Di 3
Di 16
Note 1: Di 9 – 16 data is not practical discrete input data. It is “output completion status” internal data.
Note 2: For the combination with Modbus communication module (model: R3-NE1, R3-NM1 and such),
use the addresses of Input (1X) for Modbus I/O assignment.
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 5/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 6/7
http://www.m-system.co.jp/
MODEL: R3-DAC16A
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
RUN
LED
ERR INDICATOR
LED
DIP SW
LED
INTERNAL BUS A
Input Circuit
Communication
Circuit
1
2
3
4
5
6
7
8
1
2
Di 1
Di 2
Di 3
Di 4
Di 5
Di 6
Di 7
Di 8
COM
COM
INTERNAL BUS B*
3
INTERNAL POWER
4
9
6
7
8
9
Do 1
11
12
13
14
5
10
11
12
13
14
15
16
Do 2
Do 3
Do 4
Control
Circuit
16 Do 5
17 Do 6
18 Do 7
19 Do 8
10 COM
20 COM
15
Output Circuit
Numbers in italic indicate LED No.s assigned to the front panel LEDs.
*For dual redundant communication.
■ Input Circuit
■ Output Circuit
1
1
Di 1
9
6
Do 1
Control
Circuit
Control
Circuit
8
14
Di 8
16
19
Do 8
5
10
20
Excitation supply
15
Specifications are subject to change without notice.
R3-DAC16A SPECIFICATIONS
ES-8342 Rev.3 Page 7/7
http://www.m-system.co.jp/