R3-DS4AW [MSYSTEM]
Remote I/O R3 Series 4 â 20 mA INPUT MODULE;型号: | R3-DS4AW |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series 4 â 20 mA INPUT MODULE 输入元件 |
文件: | 总4页 (文件大小:130K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-DS4A
Remote I/O R3 Series
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
4 – 20 mA INPUT MODULE
(2-wire transmitter exc. supply with switch; 4 points,
isolated)
27.5 (1.08)
Isolation: Input 1 to input 2 to input 3 to input 4 to internal
bus or internal power
Excitation supply switches: DIP switches (front)
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response
failure);
130
(5.12)
109
(4.29)
mm (inch)
Green in normal operating conditions.
MODEL: R3-DS4A[1][2]
SUPPLY OUTPUT
ORDERING INFORMATION
• Code number: R3-DS4A[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-DS4AW/Q)
(across the terminals 1 – 2, 3 – 4, 6 – 7 and 8 – 9)
Output voltage: 24 – 28 V DC with no load
16 V DC min. at 22 mA
Current rating: ≤ 22 mA DC
• Specify the specification for option code /Q
(e.g. /C01/SET)
∙Shortcircuit Protection
Current limited: Approx. 30 mA
Protected time duration: No limit
NO. OF CHANNELS
4A: 4 channels, (with excitation supply switches)
INPUT SPECIFICATIONS
■ DC Current: 4 – 20 mA DC
[1] COMMUNICATION MODE
Input resistance: 250 Ω resistor incorporated
S: Single
W: Dual
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 250 g (0.55 lb)
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8368)
R3-DS4A SPECIFICATIONS
ES-8448 Rev.7 Page 1/4
http://www.m-system.co.jp/
MODEL: R3-DS4A
PERFORMANCE
Conversion accuracy: Refer to the table at the end of this
section.
Conversion rate: 80 / 40 / 20 / 10 msec. selectable
(factory default: 80 msec.)
Data range: 0 – 10000
Data allocation: 4
Current consumption: 210 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Conversion accuracy:
RATE
80 msec. 40 msec. 20 msec. 10 msec.
Accuracy
±±0±ꢀ5
±±0.5
±±0ꢁ5
±±0ꢂ5
EXTERNAL VIEW
■
FRONT VIEW
■ SIDE VIEW
RUN LED
Excitation Supply
1
*
Switches
ERR LED
Conversion Rate
Setting
1
11
2
1
2
3
4
12
3
13
4
SW3
14
5
OFF ON
4
3
15
6
16
7
2
1
Conv.
Rate
17
8
ON
18
9
19
10
20
*1. Excitation supply switches 1 through 4 turn on (ON) or off (OFF)
the power supply to the input 1 through 4 respectively.
(Factory set to ON)
R3-DS4A SPECIFICATIONS
ES-8448 Rev.7 Page 2/4
http://www.m-system.co.jp/
MODEL: R3-DS4A
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Excitation
Supply
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
1
2
EXC. SUPPLY
SW
2W-XMTR (EXC)
CURRENT INPUT
2W-XMTR (EXC)
CURRENT INPUT
2W-XMTR (EXC)
CURRENT INPUT
2W-XMTR (EXC)
CURRENT INPUT
RUN LED ERR LED DIP SW
Input Circuit
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INTERNAL BUS A
Communication
Circuit
11
12
3
INTERNAL BUS B*
250Ω
Control
Circuit
Excitation
Supply
EXC. SUPPLY
SW
INTERNAL POWER
4
Input Circuit
13
14
6
5
250Ω
10
15
20
Excitation
Supply
EXC. SUPPLY
SW
7
Input Circuit
16
17
8
250Ω
Excitation
Supply
EXC. SUPPLY
SW
9
Input Circuit
18
19
250Ω
*For dual redundant communication.
• Unused Input Channels
Turn on the excitation supply switch for the unused channels
and close across the unused input terminals with a resistor
(5 kΩ, 0.5W) as shown below.
INPUT 1
1
INPUT 2
3
INPUT 3
6
INPUT 4
8
5kΩ (0.5W)
2
4
7
9
Unused channels left open are equal to the input lower than
-15%, which sets a data abnormality at the PLC or the host
device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to
connect resistors at the field terminals.
R3-DS4A SPECIFICATIONS
ES-8448 Rev.7 Page 3/4
http://www.m-system.co.jp/
MODEL: R3-DS4A
Specifications are subject to change without notice.
R3-DS4A SPECIFICATIONS
ES-8448 Rev.7 Page 4/4
http://www.m-system.co.jp/
相关型号: