R3-GM1S/CE [MSYSTEM]

Remote I/O R3 Series MODBUS INTERFACE MODULE;
R3-GM1S/CE
型号: R3-GM1S/CE
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series MODBUS INTERFACE MODULE

文件: 总8页 (文件大小:204K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-GM1  
Remote I/O R3 Series  
CAUTION  
• When selecting network modules, note that this unit is not  
designed to be used with network modules of certain types  
or versions.  
MODBUS INTERFACE MODULE  
Functions & Features  
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx,  
and R3-NLx.  
• Enables other protocol interface modules to communicate  
with Modbus data (gateway).  
• This unit CAN be used with:  
• Recognized as an analog I/O mixed module by other  
protocol interface modules.  
R3-NM3 and R3-NML3 of firmware version V1.00 or higher;  
R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1,  
R3-NM4, and R3-NP1 of firmware version V2.00 or higher;  
and  
• Used as Modbus slave device like R3-NM1.  
Typical Applications  
other models of any firmware versions.  
• A gateway for CC-Link and Modbus.  
PACKAGE INCLUDES...  
27.5 [1.08]  
• Terminating resistor (110 Ω, 0.25 W)  
GENERAL SPECIFICATIONS  
Connection  
130  
[5.12]  
Modbus: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm2, stripped length 7  
109  
[4.29]  
mm)  
Internal bus: Via the Installation Base  
(model: R3-BSx)  
mm [inch]  
Internal Power: Via the Installation Base  
(model: R3-BSx)  
MODEL: R3-GM1S[1]  
RUN contact output: M3 separable screw terminal  
(torque 0.5 N·m)  
ORDERING INFORMATION  
• Code number: R3-GM1S[1]  
Specify a code from below for [1].  
(e.g. R3-GM1S/CE/Q)  
Screw terminal: Nickel-plated steel  
Isolation: Modbus to internal bus or internal power to RUN  
contact output  
RUN indicator: Bi-color (green/red) LED  
Green turns ON when Modbus communication is normal and  
fieldbus communication on the R3 Network module side is  
also normal; or  
• Specify the specification for option code /Q  
(e.g. /C01)  
Red turns ON when receiving data.  
COMMUNICATION MODE  
Indication selectable with DIP SW3-4.  
ERR indicator: Bi-color (green/red) LED  
Green turns ON/blinks in communication errors (OFF with  
wire breakdown; Green blinks with setting errors); or  
Red turns ON when transmitting data.  
Indication selectable with DIP SW3-4.  
Module allocation: Set with the side DIP switch.  
RUN CONTACT OUTPUT  
S: Single  
[1] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
/CE: CE marking  
Other Options  
blank: none  
RUN contact: Turns on while the green RUN LED is ON (only  
when Modbus communication and the field bus built-in the  
interface module are in normal).  
/Q: Option other than the above (specify the specification)  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(Less than 50 V AC to conform with EU Directive)  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
/C02: Polyurethane coating  
/C03: Rubber coating  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 1/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
Minimum load: 1 V DC @ 1 mA  
Mechanical life: 2 × 10 cycles (300 cycles/min.)  
7
When driving an inductive load, external contact protection  
and noise quenching recommended.  
MODBUS COMMUNICATION  
Standard: Conforms to TIA/EIA-485-A  
Transmission distance: 500 meters max.  
Transmission media: Shielded twisted-pair cable  
(CPEV-S 0.9 dia.)  
Transmission setting: DIP switch (front)  
Data mode: RTU (Binary) or ASCII  
Parity: None, even or odd  
Baud rate: 4800, 9600, 19.2 k, 38.4 k (bps)  
Node address: Rotary switch; 01 – F7  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Data allocation: 16 × n (Module allocation: 1 to 8)  
Current consumption: 100 mA  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(Modbus to internal bus or internal power to RUN contact  
output)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 2/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
C
Node Address Setting  
Rotary SW, upper digit  
SA1  
SA2  
4
C
4
RUN LED  
ERR LED  
Node Address Setting  
Rotary SW, lower digit  
DIP SW  
Transmisson  
Properties  
SW3  
ON  
SW1  
FG  
SLD  
DG  
DB  
DA  
LED  
Function  
Configuration Jack  
4
3
2
1
8
7
6
5
4
3
2
1
SW6  
Euro Type  
Connector Terminal  
8
7
6
5
4
3
2
1
1
2
3
Module Allocation  
Data Mode  
Parity  
4
ON  
5
6
Baud Rate  
ON  
COMMUNICATION CABLE CONNECTIONS  
HOST PC  
R3-GM1  
DA  
R3-GM1  
DA  
TERMINATOR  
+
Tx / Rx  
+
Tx / Rx  
DB  
DB  
SG  
DG  
DG  
Rx  
Rx-  
SLD  
FG  
SLD  
FG  
FG  
FG  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 3/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
MODBUS FUNCTION CODES & SUPPORTED CODES  
Data & Control Functions  
CODE NAME  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
Read Coil Status  
Digital output from the slave  
Read Input Status  
Read Holding Registers  
Read Input Registers  
Force Single Coil  
X
X
X
Status of digital inputs to the slave  
General purpose register within the slave  
Collected data from the eld by the slave  
Digital output from the slave  
Preset Single Register  
Read Exception Status  
Diagnostics  
X
X
General purpose register within the slave  
Program 484  
Poll 484  
Fetch Comm. Event Counter  
Fetch Comm. Event Log  
Program Controller  
Poll Controller  
Fetch a status word and an event counter  
A status word, an event counter, a message count and a eld of event bytes  
Force Multiple Coils  
Preset Multiple Registers  
Report Slave ID  
X
X
Digital output from the slave  
General purpose register within the slave  
Slave type / ‘RUN’ status  
Program 884/M84  
Reset Comm. Link  
Read General Reference  
Write General Reference  
Mask Write 4X Register  
Read/Write 4X Register  
Read FIFO Queue  
Exception Codes  
CODE NAME  
01  
02  
03  
04  
05  
06  
07  
08  
Illegal Function  
X
X
X
Function code is not allowable for the slave  
Address is not available within the slave  
Data is not valid for the function  
Illegal Data Address  
Illegal Data Value  
Slave Device Failure  
Acknowledge  
Slave Device Busy  
Negative Acknowledge  
Memory Parity Error  
Diagnostic Subfunctions  
CODE NAME  
00  
01  
02  
03  
04  
Return Query Data  
X
X
X
X
X
Loop back test  
Restart Comm. Option  
Return Diagnostic Register  
Change ASCII Input Delimiter  
Force Listen Only Mode  
Reset the slave and clear all counters  
Contents of the diagnostic data (2 bytes)  
Delimiter character of ASCII message  
Force the slave into Listen Only Mode  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 4/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
MODBUS I/O ASSIGNMENT  
ADDRESS  
DATA TYPE  
I
DATA  
MODULE POSITION  
Input (1X)  
1025 – 1032  
1 – 16  
Module Status  
Analog Input  
Input Registers (3X)  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
17 – 32  
33 – 48  
49 – 64  
65 – 80  
81 – 96  
97 – 112  
113 – 128  
257 – 288  
289 – 320  
321 – 352  
353 – 384  
385 – 416  
417 – 448  
449 – 480  
481 – 512  
1 – 16  
F
Analog Input  
Analog Output  
Analog Output  
Holding Registers (4X)  
I
17 – 32  
33 – 48  
49 – 64  
65 – 80  
81 – 96  
97 – 112  
113 – 128  
257 – 288  
289 – 320  
321 – 352  
353 – 384  
385 – 416  
417 – 448  
449 – 480  
481 – 512  
F
DATA TYPE  
I: Integer, 0 – 10000 (0 – 100%)  
F: Floating (32-bit data cannot be accessed via !oating addresses.)  
Note: DO NOT access addresses other than the ones mentioned above. Such access may cause problems such as malfunction.  
• Module Status  
Module Status indicates whether individual I/O module is mounted or not. The bit corresponding to the mounted slot turns to “1,and the  
unmounted slot to “0.”  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 5/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
TRANSMISSION DATA DESCRIPTIONS  
Use the DIP SW located at the side of the module to specify module allocation.  
1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 8 modules (128 words  
input, 128 words output) transmission is available. R3-GM1 seems as if max. 8 I/O modules are mounted to 8 slots via Modbus.  
The input of the module is processed as follows.  
Modbus Communication --> R3-GM1 Module --> R3 Base --> R3 Communication Module  
In responding to the input, the output (Holding Register) command becomes valid via Modbus communication, and the input  
(Input Register) command is valid in the output.  
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot,  
an internal bus error occurs. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the  
data for more than 16 modules.  
WHEN R3-GM1 IS MOUNTED ON SLOT NO. 2 (4 modules)  
Real I/O modules are mounted on Slots No. 1 and 2, however, the network module (R3-NC3) recognizes that each of Slots No. 1  
to 5 is occupied. That is, R3-NC3 recognizes R3-SV4 mounted on Slot No.1 as it is and recognizes R3-GM1 mounted on Slot No.2  
as divided into four modules and occupying Slots No. 2 to 5.  
SLOT  
REAL MODULE VERTUAL MODULE NO. OF WORDS  
R3-BS08  
Slot No.1  
Slot No.2  
Slot No.3  
Slot No.4  
Slot No.5  
Slot No.6  
Slot No.7  
Slot No.8  
R3-SV4  
R3-GM1  
R3-SV4  
R3-GM1 (1/4)  
R3-GM1 (2/4)  
R3-GM1(3/4)  
R3-GM1(4/4)  
No module  
R3-NC3  
4Words  
16Words  
16Words  
16Words  
16Words  
----  
R3-  
R3-  
R3-  
R3-  
SV4 GM1  
NC3 PS1  
No module  
No module  
No module  
No module  
R3-NC3  
----  
1
2
3
4
5
6
7
8
R3-PS1  
R3-PS1  
----  
I/O DATA DESCRIPTIONS  
■ MODULE STATUS, DATA ERROR STATUS  
Shows each module’s availability and error status.  
15  
0
Module 1 (Slot 1)  
Module 2 (Slot 2)  
Module 3 (Slot 3)  
Module 8 (Slot 8)  
■ ANALOG DATA  
16-bit binary data.  
15  
0
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 6/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
6–M3  
SCREW  
1
4
2
5
3
6
TERMINAL  
COVER  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
ROTARY SW  
LED  
Isolation  
Control  
Circuit  
Communication  
Circuit  
FG  
SLD  
DG  
DB  
INTERNAL BUS  
To Other  
Modbus  
Devices  
DIP SW  
DA  
INTERNAL POWER  
1
4
RUN +  
RUN –  
RUN CONTACT OUTPUT  
2
3
5
6
CONFIGURATION JACK  
JACK  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 7/8  
https://www.m-system.co.jp/  
MODEL: R3-GM1  
SYSTEM CONFIGURATION EXAMPLES  
In the following system configuration, Modbus data is converted to CC-Link data via this unit which is used as a gateway.  
CC-Link  
Master unit  
R3- R3- R3-  
GM1 NC3 PS1  
RS-485  
Modbus  
Master unit  
Specifications are subject to change without notice.  
R3-GM1 SPECIFICATIONS  
ES-8463 Rev.9 Page 8/8  
https://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY