R3-MEX2W/Q [MSYSTEM]
Remote I/O R3 Series VALVE POSITIONER MODULE;型号: | R3-MEX2W/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series VALVE POSITIONER MODULE |
文件: | 总4页 (文件大小:122K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-MEX2
/C02: Polyurethane coating
Remote I/O R3 Series
/C03: Rubber coating
VALVE POSITIONER MODULE
(for 2 systems; built-in SSR)
CAUTION
This unit is not designed to be used with the following types
of interface modules (models: R3-NC2, R3-NEIP1, R3-NFx,
R3-NLx).
27.5 (1.08)
Please use this unit with interface modules (models: R3-
NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1, R3-NM4,
R3-NP1) of firmware version V2.00 or higher, and interface
modules (models: R3-NM3, R3-NML3) of firmware version
V1.00 or higher.
130
(5.12)
109
(4.29)
mm (inch)
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input, Output: M3 separable screw terminal
(torque 0.5 N·m)
MODEL: R3–MEX2[1][2]
ORDERING INFORMATION
• Code number: R3-MEX2[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-MEX2W/CE/Q)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
Full-close position setting range:
0 - 25 % (factory default: 0 %)
• Specify the specification for option code /Q
(e.g. /C01)
Full-open position setting range:
75 - 100 % (factory default: 100 %)
Deadband adjustment:
0.1 – 8.0 % adjustable (factory default: 1.5 %)
Restart limiting timer:
VALVE POSITIONER
2: 2 systems
0.5 to 10 sec. (factory default: 2 sec.)
Motor deadlock detecting time:
FEEDBACK RESISTANCE
Potentiometer input
60 – 1000 sec. (factory default: 120 sec.)
Isolation: Cotrol output 1 to control output 2 to feedback
potentiometer 1 or feedback potentiometer 2 or internal bus
or internal power
CONTROL OUTPUT
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating
conditions.
Built-in SSR
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
INPUT SPECIFICATIONS
■ Feedback Potentiometer: 100 Ω – 10 kΩ
Minimum span: 50 % of total resistance
Excitation: Approx. 3.3 V DC
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
R3-MEX2 SPECIFICATIONS
ES-8279 Rev.2 Page 1/4
https://www.m-system.co.jp/
MODEL: R3-MEX2
EMS EN 61000-6-2
OUTPUT SPECIFICATIONS
■ Control Output: SSR (zero-crossing); 20 - 240 V AC 0.1 -
Low Voltage Directive
EN 61010-1, EN 61010-2-201
1 A
Measurement Category II (control output)
Pollution degree 2
Leakage current at OFF: Approx. 10 mA @ 240 V AC
Output operation at loss of communication: When a
communication error occurs in the middle of an output
operation, the operation continues toward until reaching
target position most recently set by Host device.
Position feedback 1 or position feedback 2 to control
output 1 to control output 2: Reinforced insulation (300 V)
RoHS Directive
FUNCTIONS
• SSR (Solid State Relay)
Output Operation: (terminal No. in parentheses)
Deadband
0
▼
SSR consists only of semiconductor elements, and thus SSR
is free from arc discharge and chattering which are typical
with electromagnetic relays.
(2 – 11) ON to min.
–
(1 – 11) ON to max.
+
Deviation
SSR has excellent durability against vibration, physical
impact, and environmental influences.
• Zero-Cross Function
Deadband
0
(7 – 16) ON to min.
–
(6 – 16) ON to max.
+
▼
Deviation
SSR with zero-cross function turns on when AC power
voltage is near zero.
When input is provided in the middle of a wave cycle, SSR
delays switching until the next time the voltage becomes
near zero, thus limiting transient switching noise voltage
and rush current.
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 190 g (0.42 lb)
PERFORMANCE
■ POSITION FEEDBACK INPUT
Conversion accuracy: ±0.4 %
The conversion accuracy is defined against the
potentiometer's full span.
Conversion rate: 10 msec.
Data range: 0 – 1000
Data allocation: 4
Current consumption: Approx. 50 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Temperature coefficient is defined against the
potentiometer's full span.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
2000 V AC @1 minute (control output 1 to control output 2
to position feedback 1 or position feedback 2 or internal bus
or internal power)
2000 V AC @1 minute (power input to FG; isolated on the
power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
R3-MEX2 SPECIFICATIONS
ES-8279 Rev.2 Page 2/4
https://www.m-system.co.jp/
MODEL: R3-MEX2
EXTERNAL VIEW
■ FRONT VIEW
RUN LED
ERR LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
R3-MEX2 SPECIFICATIONS
ES-8279 Rev.2 Page 3/4
https://www.m-system.co.jp/
MODEL: R3-MEX2
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN
LED
ERR
LED
SSR
SSR
Open
Close
1
2
INTERNAL BUS A
Comm.
Circuit
CAPACITOR
MOTOR
M
INTERNAL BUS B*
11
4
Open
Voltage
Reference
+
−
INTERNAL POWER
FEEDBACK
Amplifier
13
14
POTENTIOMETER
3
5
Control
Circuit
Close
8
SSR
SSR
Open
Close
10
12
15
17
20
6
7
CAPACITOR
M
MOTOR
16
9
Open
Voltage
Reference
+
−
FEEDBACK
Amplifier
18
19
POTENTIOMETER
Close
* For dual redundant communication type module only.
Specifications are subject to change without notice.
R3-MEX2 SPECIFICATIONS
ES-8279 Rev.2 Page 4/4
https://www.m-system.co.jp/