R3-MEX2W/Q [MSYSTEM]

Remote I/O R3 Series VALVE POSITIONER MODULE;
R3-MEX2W/Q
型号: R3-MEX2W/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series VALVE POSITIONER MODULE

文件: 总4页 (文件大小:122K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-MEX2  
/C02: Polyurethane coating  
Remote I/O R3 Series  
/C03: Rubber coating  
VALVE POSITIONER MODULE  
(for 2 systems; built-in SSR)  
CAUTION  
This unit is not designed to be used with the following types  
of interface modules (models: R3-NC2, R3-NEIP1, R3-NFx,  
R3-NLx).  
27.5 (1.08)  
Please use this unit with interface modules (models: R3-  
NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1, R3-NM4,  
R3-NP1) of firmware version V2.00 or higher, and interface  
modules (models: R3-NM3, R3-NML3) of firmware version  
V1.00 or higher.  
130  
(5.12)  
109  
(4.29)  
mm (inch)  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input, Output: M3 separable screw terminal  
(torque 0.5 N·m)  
MODEL: R3–MEX2[1][2]  
ORDERING INFORMATION  
• Code number: R3-MEX2[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-MEX2W/CE/Q)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
Full-close position setting range:  
0 - 25 % (factory default: 0 %)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Full-open position setting range:  
75 - 100 % (factory default: 100 %)  
Deadband adjustment:  
0.1 – 8.0 % adjustable (factory default: 1.5 %)  
Restart limiting timer:  
VALVE POSITIONER  
2: 2 systems  
0.5 to 10 sec. (factory default: 2 sec.)  
Motor deadlock detecting time:  
FEEDBACK RESISTANCE  
Potentiometer input  
60 – 1000 sec. (factory default: 120 sec.)  
Isolation: Cotrol output 1 to control output 2 to feedback  
potentiometer 1 or feedback potentiometer 2 or internal bus  
or internal power  
CONTROL OUTPUT  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Green LED turns on in normal operating  
conditions.  
Built-in SSR  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
INPUT SPECIFICATIONS  
■ Feedback Potentiometer: 100 Ω – 10 kΩ  
Minimum span: 50 % of total resistance  
Excitation: Approx. 3.3 V DC  
/CE: CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
R3-MEX2 SPECIFICATIONS  
ES-8279 Rev.2 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3-MEX2  
EMS EN 61000-6-2  
OUTPUT SPECIFICATIONS  
■ Control Output: SSR (zero-crossing); 20 - 240 V AC 0.1 -  
Low Voltage Directive  
EN 61010-1, EN 61010-2-201  
1 A  
Measurement Category II (control output)  
Pollution degree 2  
Leakage current at OFF: Approx. 10 mA @ 240 V AC  
Output operation at loss of communication: When a  
communication error occurs in the middle of an output  
operation, the operation continues toward until reaching  
target position most recently set by Host device.  
Position feedback 1 or position feedback 2 to control  
output 1 to control output 2: Reinforced insulation (300 V)  
RoHS Directive  
FUNCTIONS  
SSR (Solid State Relay)  
Output Operation: (terminal No. in parentheses)  
Deadband  
0
SSR consists only of semiconductor elements, and thus SSR  
is free from arc discharge and chattering which are typical  
with electromagnetic relays.  
(2 – 11) ON to min.  
(1 – 11) ON to max.  
+
Deviation  
SSR has excellent durability against vibration, physical  
impact, and environmental influences.  
Zero-Cross Function  
Deadband  
0
(7 – 16) ON to min.  
(6 – 16) ON to max.  
+
Deviation  
SSR with zero-cross function turns on when AC power  
voltage is near zero.  
When input is provided in the middle of a wave cycle, SSR  
delays switching until the next time the voltage becomes  
near zero, thus limiting transient switching noise voltage  
and rush current.  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 190 g (0.42 lb)  
PERFORMANCE  
■ POSITION FEEDBACK INPUT  
Conversion accuracy: ±0.4 %  
The conversion accuracy is defined against the  
potentiometer's full span.  
Conversion rate: 10 msec.  
Data range: 0 – 1000  
Data allocation: 4  
Current consumption: Approx. 50 mA  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Temperature coefficient is defined against the  
potentiometer's full span.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength:  
2000 V AC @1 minute (control output 1 to control output 2  
to position feedback 1 or position feedback 2 or internal bus  
or internal power)  
2000 V AC @1 minute (power input to FG; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
R3-MEX2 SPECIFICATIONS  
ES-8279 Rev.2 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3-MEX2  
EXTERNAL VIEW  
FRONT VIEW  
RUN LED  
ERR LED  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
R3-MEX2 SPECIFICATIONS  
ES-8279 Rev.2 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3-MEX2  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN  
LED  
ERR  
LED  
SSR  
SSR  
Open  
Close  
1
2
INTERNAL BUS A  
Comm.  
Circuit  
CAPACITOR  
MOTOR  
M
INTERNAL BUS B*  
11  
4
Open  
Voltage  
Reference  
+
INTERNAL POWER  
FEEDBACK  
Amplifier  
13  
14  
POTENTIOMETER  
3
5
Control  
Circuit  
Close  
8
SSR  
SSR  
Open  
Close  
10  
12  
15  
17  
20  
6
7
CAPACITOR  
M
MOTOR  
16  
9
Open  
Voltage  
Reference  
+
FEEDBACK  
Amplifier  
18  
19  
POTENTIOMETER  
Close  
* For dual redundant communication type module only.  
Specifications are subject to change without notice.  
R3-MEX2 SPECIFICATIONS  
ES-8279 Rev.2 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3-MS4

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4S

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4S/CE

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4S/Q

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4W

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4W/CE

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-MS4W/Q

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3-NC1

Remote I/O R3 Series CC-Link INTERFACE MODULE
MSYSTEM

R3-NC1-K3

Remote I/O R3 Series CC-Link INTERFACE MODULE
MSYSTEM

R3-NC1-K3/CE

Remote I/O R3 Series CC-Link INTERFACE MODULE
MSYSTEM

R3-NC1-K3/Q

Remote I/O R3 Series CC-Link INTERFACE MODULE
MSYSTEM

R3-NC1-K3/W

Remote I/O R3 Series CC-Link INTERFACE MODULE
MSYSTEM